1SDA071521R1 ABB Emax 2 E2.2N 800A Ekip Dip LI 4P FHR Air Circuit Breaker

1SDA071521R1 ABB Emax 2 E2.2N 800A Ekip Dip LI 4P FHR Air Circuit Breaker

ABB 1SDA071521R1 is a SACE Emax 2 E2.2N 800 A fixed four-pole air circuit breaker with rear horizontal terminals, an Ekip Dip LI electronic trip unit, 66 kA breaking capacity at 440 V AC and 66 kA short-time withstand current for 1 s.

SKU: 1SDA071521R1MPN: 1SDA071521R1
Price
List Price £7,133.21 ex VAT
Your Price (ex VAT) Save 25%
£5,349.91 25% OFF
You save £1,783.30 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £5,349.91
Trade pricing is personalised to your account

Manufacturer Lead Time

£5,349.91

Why Choose the ABB 1SDA071521R1 Emax 2 Air Circuit Breaker?

The ABB 1SDA071521R1 is a high-performance SACE Emax 2 E2.2N air circuit breaker (ACB) designed for dependable protection and control of low-voltage electrical distribution systems. Rated at 800 A, this fixed four-pole circuit breaker combines ABB’s E2.2 frame with the Ekip Dip LI solid-state electronic trip unit for adjustable overload and instantaneous short-circuit protection.

As part of the ABB SACE Emax 2 series, the E2.2N provides substantial short-circuit performance for industrial, commercial and infrastructure power systems. The Ekip Dip LI release provides long-time overload and instantaneous protection in a straightforward electronic platform, making it well suited to installations that require reliable circuit protection without short-time delayed or integrated ground-fault functions.

With a rated uninterrupted current of 800 A, rated ultimate short-circuit breaking capacity of 66 kA at 440 V AC and rated short-time withstand current of 66 kA for 1 s, the 1SDA071521R1 provides robust fault-handling capability. This version features a fixed four-pole configuration with rear horizontal terminals, four auxiliary contacts and open/closed circuit-breaker position indication.

Key Advantages

  • High-performance 800 A air circuit breaker for low-voltage power distribution.
  • 66 kA ultimate short-circuit breaking capacity at 440 V AC.
  • 66 kA rated short-time withstand current for 1 s supports demanding protection and selectivity requirements.
  • Ekip Dip LI electronic trip unit provides dependable overload and instantaneous short-circuit protection.
  • Straightforward electronic protection architecture simplifies configuration and commissioning.
  • Fixed four-pole construction provides switching and protection across all four poles.
  • Rear horizontal terminals support efficient busbar connection within switchboard assemblies.
  • Supplied with four auxiliary contacts and circuit-breaker open/closed position indication.

Key Features

  • ABB SACE Emax 2 E2.2N air circuit breaker.
  • 800 A rated uninterrupted current.
  • 66 kA Icu at 440 V AC.
  • 66 kA Icw for 1 s.
  • Ekip Dip LI solid-state electronic release.
  • Long-time overload and instantaneous short-circuit protection.
  • LI protection architecture without short-time delayed or integrated ground-fault protection.
  • Fixed four-pole construction.
  • Rear horizontal terminals for main circuit connections.
  • Supplied with four auxiliary contacts.
  • Open/closed circuit-breaker position indication.
  • Suitable for demanding low-voltage power distribution applications.
  • Part of ABB’s modular SACE Emax 2 air circuit breaker platform.

High-Performance Protection for Low-Voltage Distribution

Air circuit breakers such as the ABB SACE Emax 2 E2.2N provide protection for important low-voltage distribution circuits against damaging overload and short-circuit conditions. The 1SDA071521R1 combines an 800 A current rating with 66 kA ultimate short-circuit breaking capability at 440 V AC and an impressive 66 kA short-time withstand capability for 1 s, supporting demanding switchboard and distribution applications.

The Ekip Dip LI trip unit provides electronic long-time overload and instantaneous short-circuit protection in a straightforward format. Combined with the fixed four-pole construction and rear horizontal terminal arrangement, the breaker is particularly well suited to switchboards where high fault capability, dependable protection and practical rear busbar connectivity are required.

Typical Applications

  • Main incoming protection for low-voltage switchboards.
  • Industrial electrical distribution systems.
  • Commercial building power distribution.
  • Transformer secondary protection.
  • Manufacturing and process facilities.
  • Distribution feeders requiring high short-circuit performance.
  • Infrastructure and utility installations.
  • Low-voltage switchgear with rear busbar connections.

Technical Specifications

Series SACE Emax 2
Frame / sub-type E2.2N
Order code / MPN 1SDA071521R1
EAN / GTIN 8015644753719
Product type Air circuit breaker
Short-circuit performance level N
Rated current (In) 800 A
Rated uninterrupted current (Iu) 800 A
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 66 kA
Rated short-time withstand current (Icw) for 1 s 66 kA
Number of poles 4
Trip unit Ekip Dip LI
Release type Solid-state electronic
Protection functions LI
Long-time overload protection Yes
Instantaneous short-circuit protection Yes
Short-time delayed short-circuit protection No
Integrated ground-fault protection No
Current type AC
Installation version Fixed
Terminal configuration Rear horizontal
Auxiliary contacts 4
Circuit-breaker position indication Open / closed
Product net weight 53 kg

Frequently Asked Questions

What is the ABB 1SDA071521R1 used for?

The ABB 1SDA071521R1 is an 800 A Emax 2 air circuit breaker designed to protect and control low-voltage electrical distribution circuits in industrial, commercial and infrastructure switchboards.

What is the current rating of the ABB 1SDA071521R1?

The ABB 1SDA071521R1 has a rated uninterrupted current of 800 A and uses the E2.2N performance level within the SACE Emax 2 range.

What breaking capacity does the E2.2N 800 provide?

The E2.2N 800 has a rated ultimate short-circuit breaking capacity of 66 kA at 440 V AC and a rated short-time withstand current of 66 kA for 1 s.

What protection does the Ekip Dip LI trip unit provide?

The Ekip Dip LI solid-state electronic trip unit provides long-time overload and instantaneous short-circuit protection. This LI configuration does not include short-time delayed or integrated ground-fault protection.

What terminal configuration does the ABB 1SDA071521R1 use?

The 1SDA071521R1 is a fixed four-pole air circuit breaker with rear horizontal terminals, providing a practical connection arrangement for busbars within low-voltage switchboard assemblies.

Trusted High-Performance Circuit Protection

ABB SACE Emax 2 air circuit breakers combine dependable electronic protection, high short-circuit performance and flexible installation configurations for modern industrial, commercial and infrastructure low-voltage distribution systems.