1SDA071498R1 ABB E1.2B 1600 Ekip Hi-Touch LSI 4-Pole Air Circuit Breaker

1SDA071498R1 ABB E1.2B 1600 Ekip Hi-Touch LSI 4-Pole Air Circuit Breaker

ABB 1SDA071498R1 is a SACE Emax 2 E1.2B 1600 A fixed four-pole air circuit breaker with an Ekip Hi-Touch LSI electronic trip unit providing advanced overload, selective short-circuit and instantaneous protection for low-voltage power distribution systems.

SKU: 1SDA071498R1MPN: 1SDA071498R1
Price
List Price £10,593.20 ex VAT
Your Price (ex VAT) Save 25%
£7,944.90 25% OFF
You save £2,648.30 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £7,944.90
Trade pricing is personalised to your account

Manufacturer Lead Time

£7,944.90

Why Choose the ABB 1SDA071498R1 E1.2B 1600 Ekip Hi-Touch LSI Air Circuit Breaker?

The ABB 1SDA071498R1 is a high-performance SACE Emax 2 E1.2B air circuit breaker designed for advanced protection, measurement and switching in low-voltage power distribution systems. Rated at 1600 A, this four-pole fixed breaker combines ABB's compact E1.2B frame with the advanced Ekip Hi-Touch LSI electronic trip unit.

The Ekip Hi-Touch LSI release provides long-time overload (L), short-time selective short-circuit (S) and instantaneous short-circuit (I) protection. Its advanced interface and monitoring capabilities support precise protection configuration, system supervision and selective coordination in demanding electrical distribution networks.

The 1SDA071498R1 is supplied in a fixed four-pole configuration with front connections. With a rated voltage of 690 V AC, an ultimate short-circuit breaking capacity of 42 kA at 400 V AC and adjustable overload protection from 640–1600 A, it is engineered for substantial industrial, commercial and infrastructure power distribution applications.

Key Advantages

  • 1600 A SACE Emax 2 air circuit breaker for high-current low-voltage distribution circuits.
  • Compact E1.2B frame supports space-efficient switchboard design.
  • Advanced Ekip Hi-Touch LSI electronic trip unit.
  • Long-time, short-time and instantaneous protection functions.
  • Short-time protection supports selective coordination with suitable downstream protective devices.
  • 42 kA ultimate short-circuit breaking capacity at 400 V AC.
  • Advanced monitoring and Network Analyzer capabilities associated with the Ekip Hi-Touch platform.
  • Four-pole fixed construction for permanent installation in low-voltage switchgear.

Key Features

  • ABB SACE Emax 2 E1.2B series.
  • 1600 A rated uninterrupted current.
  • 4-pole fixed configuration.
  • Front connection arrangement.
  • Ekip Hi-Touch LSI electronic protection release.
  • Long-time overload protection (L).
  • Short-time selective short-circuit protection (S).
  • Instantaneous short-circuit protection (I).
  • 640–1600 A overload release setting range.
  • 960–16000 A short-time delayed short-circuit setting range.
  • 2400–24000 A instantaneous short-circuit setting range.
  • 690 V AC rated voltage.
  • 42 kA Icu at 400 V AC.
  • Four change-over auxiliary contacts.
  • Trip indication for enhanced operating supervision.
  • Optional motor operation and communication expansion within the Emax 2 platform.

Advanced LSI Protection for High-Current Distribution

The ABB SACE Emax 2 E1.2B platform combines compact construction with electronic circuit protection for substantial low-voltage distribution loads. With a rated current of 1600 A and a breaking capacity of 42 kA at 400 V AC, the 1SDA071498R1 is well suited to switchboards where high current capacity, selective protection and efficient use of panel space are important.

The Ekip Hi-Touch LSI release protects against sustained overloads, delayed short circuits and severe instantaneous short circuits. Its advanced monitoring platform supports electrical-system supervision and integration with ABB Emax 2 communication and configuration technologies, making the breaker suitable for modern industrial power distribution and intelligent switchgear applications.

Typical Applications

  • Low-voltage main switchboard incomers.
  • Industrial power distribution systems.
  • Commercial building electrical distribution.
  • Transformer secondary protection.
  • High-current feeder protection.
  • Manufacturing and process facilities.
  • Infrastructure and critical electrical installations.
  • Distribution systems requiring selective LSI protection.
  • Intelligent switchgear and monitored power distribution systems.

Technical Specifications

Series SACE Emax 2
Frame E1.2B
ABB order code 1SDA071498R1
EAN 8015644753481
Product type Air circuit breaker
Rated uninterrupted current (Iu) 1600 A
Number of poles 4
Installation Fixed
Connection arrangement Front
Main circuit connection type Bolted connection
Trip unit Ekip Hi-Touch LSI
Release type Electronic
Protection functions Long-time (L), short-time (S), instantaneous (I)
Overload release setting range 640–1600 A
Short-time delayed short-circuit setting range 960–16000 A
Instantaneous short-circuit setting range 2400–24000 A
Integrated earth-fault protection No
Rated voltage 690 V AC
Ultimate short-circuit breaking capacity at 400 V, 50 Hz 42 kA
Auxiliary contacts 4 change-over contacts
Trip indication Yes
Integrated undervoltage release No
Integrated motor operator No
Optional motor operation Yes
Degree of protection IP30
Power loss 201 W
Network analysis Network Analyzer functionality available with Ekip Hi-Touch
Configuration and diagnostics Ekip Connect compatible
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA071498R1?

The ABB 1SDA071498R1 is a SACE Emax 2 E1.2B 1600 A four-pole fixed air circuit breaker with an Ekip Hi-Touch LSI electronic protection release.

What protection functions does the Ekip Hi-Touch LSI trip unit provide?

The Ekip Hi-Touch LSI release provides long-time overload protection (L), short-time selective short-circuit protection (S) and instantaneous short-circuit protection (I).

What is the breaking capacity of the ABB E1.2B 1600?

The ABB E1.2B 1600 has an ultimate short-circuit breaking capacity of 42 kA at 400 V AC, 50 Hz.

What is the overload setting range of the ABB 1SDA071498R1?

The overload release is adjustable from 640–1600 A, allowing the long-time protection function to be configured for the protected circuit.

What are the short-circuit protection setting ranges?

The short-time delayed short-circuit setting range is 960–16000 A, while the instantaneous short-circuit setting range is 2400–24000 A.

Does the ABB 1SDA071498R1 include earth-fault protection?

No. This model uses an LSI protection configuration providing long-time, short-time and instantaneous protection; an LSIG configuration is required where integrated earth-fault protection is specified.

Is the ABB 1SDA071498R1 fixed or withdrawable?

This model is a fixed four-pole air circuit breaker, designed for permanent installation within a suitable low-voltage switchboard or power distribution assembly.