1SDA071480R1 ABB Emax 2 E1.2N 1250A Ekip G Hi-Touch LSIG 4P Air Circuit Breaker

1SDA071480R1 ABB Emax 2 E1.2N 1250A Ekip G Hi-Touch LSIG 4P Air Circuit Breaker

ABB 1SDA071480R1 is a SACE Emax 2 E1.2N 1250 A fixed four-pole air circuit breaker with front terminals, an Ekip G Hi-Touch LSIG electronic trip unit, generator-specific protection, 690 V AC rated operational voltage and 66 kA breaking capacity at 380–440 V AC.

SKU: 1SDA071480R1MPN: 1SDA071480R1
Price
List Price £12,780.04 ex VAT
Your Price (ex VAT) Save 25%
£9,585.03 25% OFF
You save £3,195.01 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £9,585.03
Trade pricing is personalised to your account

Manufacturer Lead Time

£9,585.03

Why Choose the ABB 1SDA071480R1 Emax 2 Air Circuit Breaker?

The ABB 1SDA071480R1 is a high-performance SACE Emax 2 E1.2N air circuit breaker (ACB) designed for advanced protection, monitoring and control of low-voltage generator and electrical distribution systems. Rated at 1250 A, this fixed four-pole circuit breaker combines ABB’s compact E1.2 frame with the advanced Ekip G Hi-Touch LSIG electronic trip unit for comprehensive generator-specific and distribution protection.

As part of the ABB SACE Emax 2 series, the E1.2N combines high short-circuit performance with sophisticated measurement, power-quality and protection functionality. The Ekip G Hi-Touch LSIG release provides long-time, short-time, instantaneous and ground-fault protection together with generator-specific protection functions, an integrated Ekip Measuring Pro module and Network Analyzer functionality.

With a rated uninterrupted current of 1250 A, rated operational voltage of 690 V AC and rated ultimate short-circuit breaking capacity of 66 kA at 380–440 V AC, the 1SDA071480R1 provides substantial fault-clearing performance for demanding installations. This version features a fixed four-pole configuration with front terminals, making it particularly suitable for generator switchboards, critical-power systems and high-performance low-voltage distribution assemblies.

Key Advantages

  • High-performance 1250 A air circuit breaker for generator and low-voltage distribution applications.
  • 66 kA ultimate short-circuit breaking capacity at 380–440 V AC.
  • 50 kA short-time withstand current for 1 s supports effective selectivity and protection coordination.
  • Advanced Ekip G Hi-Touch LSIG electronic trip unit with generator-specific protection functions.
  • LSIG functionality provides long-time, short-time, instantaneous and ground-fault protection.
  • Integrated Ekip Measuring Pro supports advanced electrical measurement and monitoring.
  • Integrated Network Analyzer provides real-time power-quality monitoring.
  • Four-pole fixed configuration with front terminals supports straightforward switchboard integration.

Key Features

  • ABB SACE Emax 2 E1.2N air circuit breaker.
  • 1250 A rated uninterrupted current.
  • 690 V AC rated operational voltage.
  • 1000 V AC rated insulation voltage.
  • 66 kA Icu at 380–440 V AC.
  • 50 kA Icu at 500–690 V AC.
  • 50 kA Icw for 1 s.
  • Ekip G Hi-Touch LSIG electronic release.
  • Adjustable long-time overload, short-time, instantaneous and ground-fault protection.
  • Specialised protection functions for generator applications.
  • Integrated Ekip Measuring Pro measurement functionality.
  • Integrated Network Analyzer for power-quality supervision.
  • Touch-sensitive display for protection configuration and monitoring.
  • Fixed four-pole construction.
  • Front terminals for main circuit connections.
  • Designed in accordance with IEC 60947-2.

Advanced Generator and Power Distribution Protection

Air circuit breakers such as the ABB SACE Emax 2 E1.2N protect critical low-voltage circuits against damaging overload, short-circuit and earth-fault conditions. The 1SDA071480R1 combines a 1250 A continuous-current rating with 66 kA ultimate short-circuit breaking capability at 380–440 V AC and 50 kA short-time withstand capability for 1 s, providing the performance required for demanding generator and distribution systems.

The Ekip G Hi-Touch LSIG trip unit extends conventional LSIG protection with functions specifically developed for generator applications. Its touchscreen interface, integrated Ekip Measuring Pro module and Network Analyzer provide advanced protection configuration, electrical measurement and power-quality supervision, helping engineers protect and monitor modern generator installations and critical low-voltage networks.

Typical Applications

  • Generator protection and generator switchboards.
  • Emergency and standby generator systems.
  • Main incoming protection for low-voltage switchboards.
  • Industrial electrical distribution systems.
  • Manufacturing and process facilities.
  • Data centres and critical-power installations.
  • Commercial and infrastructure power distribution.
  • Low-voltage switchgear requiring advanced measurement and power-quality monitoring.

Technical Specifications

Series SACE Emax 2
Frame / sub-type E1.2N
Order code / MPN 1SDA071480R1
EAN / GTIN 8015644753306
Product type Air circuit breaker
Short-circuit performance level N
Rated current (In) 1250 A
Rated uninterrupted current (Iu) 1250 A
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Frequency 50 / 60 Hz
Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 400–415 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500–525 V AC 50 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 50 kA
Rated short-time withstand current (Icw) for 1 s 50 kA
Number of poles 4
Trip unit Ekip G Hi-Touch LSIG
Release type Electronic
Protection functions LSIG
Overload protection adjustment 0.4–1 × In
Overload protection adjustment range 500–1250 A
Short-time protection adjustment 0.6–10 × In
Short-time protection adjustment range 750–12,500 A
Instantaneous protection adjustment 1.5–15 × In
Instantaneous protection adjustment range 1875–18,750 A
Ground-fault protection adjustment 0.1–1 × In
Integrated earth-fault protection Yes
Generator-specific protection Yes
Measurement module Ekip Measuring Pro
Power-quality analysis Integrated Network Analyzer
User interface Touch-sensitive display
Current type AC
Installation version Fixed
Terminal configuration Front terminals
Main circuit connection Bolt connection
Integrated undervoltage release No
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA071480R1 used for?

The ABB 1SDA071480R1 is a 1250 A Emax 2 air circuit breaker designed for advanced protection, monitoring and control of low-voltage generator and electrical distribution systems.

What is the current rating of the ABB 1SDA071480R1?

The circuit breaker has a rated uninterrupted current of 1250 A and a rated operational voltage of 690 V AC.

What breaking capacity does the E1.2N 1250 provide?

The E1.2N 1250 has a rated ultimate short-circuit breaking capacity of 66 kA at 380–440 V AC and 50 kA at 500–690 V AC. Its rated short-time withstand current is 50 kA for 1 s.

What protection does the Ekip G Hi-Touch LSIG trip unit provide?

The Ekip G Hi-Touch LSIG electronic trip unit provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection together with specialised generator protection, advanced measurement and power-quality analysis functionality.

Is the ABB 1SDA071480R1 a fixed or withdrawable circuit breaker?

The 1SDA071480R1 is a fixed four-pole air circuit breaker with front terminals for integration into generator and low-voltage distribution switchboards.

Trusted High-Performance Circuit Protection

ABB SACE Emax 2 air circuit breakers combine advanced electronic protection, generator-specific functionality, high short-circuit performance, electrical measurement and power-quality analysis for dependable operation in modern industrial, commercial and critical-power electrical systems.