ABB 1SDA071465R1 is a SACE Emax 2 E1.2C 1250 A fixed four-pole air circuit breaker with front terminals, an Ekip Touch LSI electronic trip unit, 690 V AC rated operational voltage, 50 kA breaking capacity at 440 V AC and 42 kA short-time withstand current for 1 s.
£5,432.03
The ABB 1SDA071465R1 is a high-performance SACE Emax 2 E1.2C air circuit breaker (ACB) designed for advanced protection and control of low-voltage electrical distribution systems. Rated at 1250 A, this fixed four-pole circuit breaker combines ABB’s compact E1.2 frame with the advanced Ekip Touch LSI electronic trip unit for configurable overload, short-time and instantaneous short-circuit protection.
As part of the ABB SACE Emax 2 series, the E1.2C is engineered to provide dependable fault interruption and selective protection in demanding industrial and commercial installations. The Ekip Touch LSI solid-state release provides long-time, short-time and instantaneous protection functions, while its touchscreen interface supports intuitive configuration, commissioning and access to electrical information.
With a rated uninterrupted current of 1250 A, rated operational voltage of 690 V AC, rated ultimate short-circuit breaking capacity of 50 kA at 440 V AC and rated short-time withstand current of 42 kA for 1 s, the 1SDA071465R1 provides robust protection for demanding low-voltage networks. This version features a fixed four-pole configuration with front terminals for straightforward integration into switchboards and distribution assemblies.
Air circuit breakers such as the ABB SACE Emax 2 E1.2C protect important low-voltage distribution circuits against damaging overload and short-circuit conditions. The 1SDA071465R1 combines a 1250 A continuous-current rating with 50 kA short-circuit breaking capability at 440 V AC and 42 kA short-time withstand capability for 1 s, making it suitable for demanding main and distribution circuits.
The Ekip Touch LSI trip unit adds short-time delayed protection to the long-time and instantaneous functions, enabling more sophisticated protection coordination than an LI-only release. This makes the breaker particularly useful where selectivity between upstream and downstream protective devices is important, while the touchscreen interface provides convenient access to protection configuration and operating information.
| Series | SACE Emax 2 |
|---|---|
| Frame / sub-type | E1.2C |
| Order code / MPN | 1SDA071465R1 |
| EAN / GTIN | 8015644753153 |
| Product type | Air circuit breaker |
| Short-circuit performance level | C |
| Rated current (In) | 1250 A |
| Rated uninterrupted current (Iu) | 1250 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 50 kA |
| Rated short-time withstand current (Icw) for 1 s | 42 kA |
| Number of poles | 4 |
| Neutral pole current | 100% of Iu |
| Trip unit | Ekip Touch LSI |
| Release type | Solid-state electronic |
| Protection functions | LSI |
| Long-time overload protection | Yes |
| Short-time delayed short-circuit protection | Yes |
| Instantaneous short-circuit protection | Yes |
| Integrated earth-fault protection | No |
| Current type | AC |
| Installation version | Fixed |
| Terminal configuration | Front terminals |
| Main circuit connection type | Bolt connection |
| Connecting capacity | 1000 mm² |
| Auxiliary contacts | 4 change-over contacts |
| Circuit-breaker position indication | Open / closed |
| Integrated undervoltage release | No |
| Integrated motor drive | No |
| Optional motor drive | Yes |
| Degree of protection | IP30 |
| Power loss | 122 W |
| Electrical durability at ≤440 V AC | 8000 operating cycles |
| Electrical durability at 500–690 V AC | 6500 operating cycles |
| Mechanical durability | 20,000 operating cycles |
| Product net width | 280 mm |
| Product net height | 296 mm |
| Product net depth | 183 mm |
| Product net weight | 16 kg |
The ABB 1SDA071465R1 is a 1250 A Emax 2 air circuit breaker designed to protect and control low-voltage electrical distribution circuits in industrial, commercial and infrastructure switchboards.
The circuit breaker has a rated uninterrupted current of 1250 A and a rated operational voltage of 690 V AC.
The E1.2C 1250 has a rated ultimate short-circuit breaking capacity of 50 kA at 440 V AC and a rated short-time withstand current of 42 kA for 1 s.
The Ekip Touch LSI solid-state electronic trip unit provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. This LSI configuration does not include integrated ground-fault protection.
The 1SDA071465R1 is a fixed four-pole air circuit breaker with front terminals for integration into low-voltage switchboards and distribution assemblies.
ABB SACE Emax 2 air circuit breakers combine advanced electronic protection, high short-circuit performance and flexible protection coordination for dependable operation in modern industrial, commercial and critical-power low-voltage distribution systems.