1SDA071463R1 ABB E1.2C 1250 Ekip Dip LSIG 4p F F Air Circuit Breaker

1SDA071463R1 ABB E1.2C 1250 Ekip Dip LSIG 4p F F Air Circuit Breaker

ABB 1SDA071463R1 Emax 2 E1.2C 1250 A four-pole fixed air circuit breaker with Ekip Dip LSIG electronic overload, short-circuit and earth-fault protection for low-voltage power distribution systems.

SKU: 1SDA071463R1MPN: 1SDA071463R1
Price
List Price £7,764.32 ex VAT
Your Price (ex VAT) Save 25%
£5,823.24 25% OFF
You save £1,941.08 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £5,823.24
Trade pricing is personalised to your account

Manufacturer Lead Time

£5,823.24

Why Choose the ABB E1.2C 1250 Ekip Dip LSIG 4p F F Air Circuit Breaker?

The ABB E1.2C 1250 Ekip Dip LSIG 4p F F, order code 1SDA071463R1, is a high-performance four-pole air circuit breaker (ACB) designed for protection and switching in low-voltage power distribution systems. As part of the advanced ABB Emax 2 E1.2 series, it combines a compact breaker frame with the Ekip Dip LSIG electronic trip unit for comprehensive overload, short-circuit and earth-fault protection.

Rated at 1250 A, this E1.2C breaker features a fixed installation configuration with front terminals. Its Ekip Dip LSIG electronic release provides long-time overload, short-time selective short-circuit, instantaneous short-circuit and earth-fault protection, with protection parameters conveniently adjustable through DIP switches.

The E1.2C performance level provides an ultimate short-circuit breaking capacity of 50 kA at 380–440 V AC and 42 kA at 500–690 V AC. With a rated operational voltage up to 690 V AC, a rated insulation voltage of 1000 V AC and compliance with IEC 60947-2, this breaker is well suited to industrial switchboards and demanding electrical distribution installations.

Key Advantages

  • High-performance ABB Emax 2 air circuit breaker for low-voltage distribution.
  • 1250 A rated current for demanding power distribution applications.
  • Four-pole configuration for switching and protecting three-phase systems with neutral.
  • Ekip Dip LSIG electronic trip unit provides comprehensive circuit protection.
  • Integrated earth-fault protection in addition to overload and short-circuit functions.
  • Ultimate breaking capacity up to 50 kA at common industrial supply voltages.
  • Fixed-mounted construction with front terminals for switchboard integration.
  • DIP-switch adjustment enables straightforward configuration of protection parameters.
  • Designed in accordance with IEC 60947-2.

Key Features

  • ABB Emax 2 E1.2C air circuit breaker.
  • 1250 A rated uninterrupted current.
  • 4-pole construction.
  • Fixed installation configuration.
  • Front terminals.
  • Ekip Dip LSIG electronic protection.
  • Long-time overload protection.
  • Short-time selective short-circuit protection.
  • Instantaneous short-circuit protection.
  • Integrated earth-fault protection.
  • 690 V AC maximum rated operational voltage.
  • 50 / 60 Hz operating frequency.

Comprehensive LSIG Protection for Power Distribution

The Ekip Dip LSIG electronic trip unit provides four essential protection functions for electrical distribution networks. Long-time protection responds to sustained overloads, short-time protection supports selective coordination during short circuits, instantaneous protection rapidly interrupts severe faults, and the integrated ground protection function detects potentially hazardous earth-fault currents.

ABB Emax 2 circuit breakers combine high electrical performance with compact switchboard integration. The fixed E1.2C configuration is particularly suitable for installations requiring dependable protection, high breaking capacity and configurable electronic protection for critical low-voltage distribution circuits.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial power distribution systems.
  • Manufacturing and process plants.
  • Commercial and infrastructure electrical systems.
  • Generator and transformer distribution boards.
  • Industrial distribution and power control centres.

Technical Specifications

Series Emax 2 E1.2
Order code / MPN 1SDA071463R1
Product type Air circuit breaker (ACB)
Rated current 1250 A
Number of poles 4
Performance level C
Trip unit Ekip Dip LSIG
Protection functions L (overload), S (selective short circuit), I (instantaneous short circuit), G (earth fault)
Mounting Fixed
Terminals Front
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Ultimate breaking capacity (Icu) at 380 V AC 50 kA
Ultimate breaking capacity (Icu) at 400 / 415 V AC 50 kA
Ultimate breaking capacity (Icu) at 440 V AC 50 kA
Ultimate breaking capacity (Icu) at 500 / 525 V AC 42 kA
Ultimate breaking capacity (Icu) at 690 V AC 42 kA
Rated service breaking capacity (Ics) 100% of Icu
Rated short-time withstand current (Icw) 42 kA for 1 s
Frequency 50 / 60 Hz
Dimensions (H × W × D) 296 × 280 × 183 mm
Net weight approx. 16 kg
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA071463R1?

The ABB 1SDA071463R1 is an Emax 2 E1.2C four-pole fixed air circuit breaker rated at 1250 A and equipped with an Ekip Dip LSIG electronic trip unit.

What protection functions does the Ekip Dip LSIG trip unit provide?

The Ekip Dip LSIG provides long-time overload (L), short-time selective short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection.

What is the breaking capacity of the E1.2C 1250 breaker?

Its ultimate short-circuit breaking capacity is 50 kA at 380–440 V AC and 42 kA at 500–690 V AC.

Does the ABB 1SDA071463R1 include earth-fault protection?

Yes. The G function of the Ekip Dip LSIG trip unit provides adjustable earth-fault protection in addition to overload and short-circuit protection.

Is the ABB 1SDA071463R1 fixed or withdrawable?

This model is a fixed-mounted Emax 2 air circuit breaker with front terminals for integration into low-voltage switchboards.

Trusted Low-Voltage Protection from ABB

ABB Emax 2 air circuit breakers provide dependable protection and switching for demanding low-voltage electrical distribution systems, combining high breaking performance, configurable electronic protection and flexible switchboard integration.