Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071440R1 SACE Emax 2 E1.2N 1000 four-pole fixed air circuit breaker with front terminals, Ekip G Hi-Touch LSIG protection, 1000 A rated current and 66 kA ultimate breaking capacity at 400–440 V AC.
£9,359.34
The ABB E1.2N 1000 Ekip G Hi-Touch LSIG 4p F F, order code 1SDA071440R1, is a high-performance SACE Emax 2 air circuit breaker (ACB) designed for advanced protection, switching and power management in low-voltage distribution and generator systems. This fixed four-pole E1.2N breaker combines a 1000 A rated uninterrupted current with ABB's sophisticated Ekip G Hi-Touch LSIG electronic trip unit.
The Ekip G Hi-Touch LSIG release provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and ground-fault protection. Its generator-oriented Hi-Touch platform adds advanced protection, measurement and power-management capabilities, making this configuration particularly suitable for generator installations and critical electrical distribution systems.
The E1.2N performance level provides an ultimate short-circuit breaking capacity of 66 kA at 400–440 V AC and 50 kA at 500–690 V AC. The fixed four-pole construction uses front terminals and includes four change-over auxiliary contacts, providing a compact and capable solution for generator switchboards, critical incoming feeders and industrial power distribution.
The ABB SACE Emax 2 E1.2N combines switching, isolation and advanced electronic protection in a compact air circuit breaker platform. Its 1000 A rated current, four-pole configuration and 66 kA ultimate breaking capacity at 400–440 V AC provide robust fault-interruption capability for demanding generator and low-voltage distribution systems.
The Ekip G Hi-Touch LSIG release combines adjustable long-time, short-time, instantaneous and ground-fault protection with generator-oriented protection and advanced electrical supervision. This comprehensive functionality supports selective fault coordination and dependable protection of generators, conductors, busbars and connected equipment in critical power systems.
| Series | SACE Emax 2 |
|---|---|
| Frame | E1.2N |
| ABB order code | 1SDA071440R1 |
| Product type | Air circuit breaker |
| Rated uninterrupted current (Iu) | 1000 A |
| Rated current (In) | 1000 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Frequency | 50/60 Hz |
| Number of poles | 4 |
| Short-circuit performance level | N |
| Trip unit | Ekip G Hi-Touch LSIG |
| Release type | Solid-state electronic release |
| Protection functions | L, S, I and G |
| Long-time overload adjustment | 0.4–1 × In / 400–1000 A |
| Short-time protection adjustment | 0.6–10 × In / 600–10000 A |
| Instantaneous protection adjustment | 1.5–15 × In / 1500–15000 A |
| Ground-fault protection adjustment | 0.1–1 × In / 100–1000 A |
| Ultimate short-circuit breaking capacity (Icu) at 400/415 V AC | 66 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 66 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500/525 V AC | 50 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 50 kA |
| Integrated earth-fault protection | Yes |
| Execution | Fixed |
| Terminal arrangement | Front terminals |
| Main-circuit connection | Bolt connection |
| Auxiliary contacts | 4 change-over contacts |
| Switched-off indication | Yes |
| Integrated undervoltage release | No |
| Motor drive integrated | No |
| Motor drive | Optional |
| Degree of protection | IP30 |
| Net weight | 11 kg |
| Country of origin | Italy |
| ABB product group | Emax2 Air Circuit Breaker |
The ABB 1SDA071440R1 is a SACE Emax 2 E1.2N 1000 Ekip G Hi-Touch LSIG four-pole fixed air circuit breaker with front terminals, a 1000 A rated current and advanced generator-oriented electronic protection.
The breaker has a rated uninterrupted current of 1000 A, with adjustable long-time overload protection from 400–1000 A.
The Ekip G Hi-Touch LSIG electronic trip unit provides long-time overload (L), short-time delayed short-circuit (S), instantaneous short-circuit (I) and ground-fault (G) protection together with generator-oriented protection, measurement and power-management functionality.
The E1.2N 1000 has an ultimate short-circuit breaking capacity of 66 kA at 400–440 V AC and 50 kA at 500–690 V AC.
It is typically used in generator switchboards, standby power systems, industrial low-voltage distribution boards, critical incoming feeders and four-pole circuits requiring comprehensive LSIG protection and advanced electrical supervision.
ABB SACE Emax 2 air circuit breakers combine advanced electronic protection, measurement and power-management capabilities with high short-circuit performance, providing comprehensive protection for generator installations and critical low-voltage distribution systems.