Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071413R1 Emax 2 E1.2B 1000 four-pole fixed air circuit breaker with a 1000 A rating, Ekip Dip LSIG electronic protection, front terminals and 42 kA ultimate breaking capacity up to 690 V AC.
£5,341.74
The ABB E1.2B 1000 Ekip Dip LSIG 4p F F, order code 1SDA071413R1, is a high-performance four-pole air circuit breaker (ACB) designed for protection and switching in low-voltage electrical distribution systems. Part of the ABB SACE Emax 2 series, it combines the compact E1.2 frame with an Ekip Dip LSIG solid-state electronic trip unit for comprehensive circuit protection in industrial, commercial and infrastructure power networks.
This fixed circuit breaker features front terminals and an Ekip Dip LSIG electronic protection release, providing long-time overload, selective short-time short-circuit, instantaneous short-circuit and earth-fault protection. Protection settings are configured using DIP switches, providing a straightforward method of matching the breaker characteristics to the requirements of the electrical installation.
With a rated uninterrupted current of 1000 A, a rated operational voltage of 690 V AC and an ultimate short-circuit breaking capacity of 42 kA across its specified AC operational voltage range, the E1.2B 1000 provides dependable protection for substantial electrical loads. Its four-pole configuration enables switching across three phases and neutral, while its fixed construction and front terminals make it suitable for permanent switchboard installation.
Air circuit breakers such as the ABB SACE Emax 2 E1.2B provide switching and protection for high-current low-voltage distribution circuits. The E1.2B frame combines a compact footprint with 42 kA ultimate short-circuit breaking performance across its specified operational voltage range, making it suitable for main incomers, feeders and other important circuits within industrial and commercial switchboards.
The Ekip Dip LSIG trip unit combines long-time, selective short-time, instantaneous and earth-fault protection. Adjustable overload protection covers 400–1000 A, short-time protection covers 600–10000 A, and instantaneous protection covers 1500–15000 A. The additional earth-fault function provides protection against ground-fault conditions, while DIP-switch adjustment enables straightforward configuration without requiring a touchscreen interface.
| Series | SACE Emax 2 |
|---|---|
| Order code / MPN | 1SDA071413R1 |
| EAN | 8015644752637 |
| Product type | Air circuit breaker |
| Frame | E1.2 |
| Performance level | B |
| Rated uninterrupted current (Iu) | 1000 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated frequency | 50 / 60 Hz |
| Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC | 42 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 400–415 V AC | 42 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 42 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500–525 V AC | 42 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 42 kA |
| Number of poles | 4 |
| Current type | AC |
| Trip unit | Ekip Dip LSIG |
| Release type | Solid-state electronic |
| Overload protection adjustment | 400–1000 A |
| Short-time short-circuit protection adjustment | 600–10000 A |
| Instantaneous short-circuit protection adjustment | 1500–15000 A |
| Earth-fault protection adjustment | 0.1–1 × In |
| Protection functions | Long-time overload, selective short-time short-circuit, instantaneous short-circuit and earth-fault protection |
| Protection setting method | DIP switches |
| Integrated earth-fault protection | Yes |
| Version | Fixed |
| Terminal connection | Front terminals |
| Auxiliary contacts | 4 changeover contacts |
| Position indication | Circuit breaker open / closed |
| Motor operator | Optional |
| Standard | IEC 60947-2 |
The ABB 1SDA071413R1 is an Emax 2 air circuit breaker designed for switching and comprehensive overload, short-circuit and earth-fault protection in low-voltage electrical distribution systems.
The circuit breaker has a rated uninterrupted current of 1000 A, with its long-time overload protection adjustable from 400–1000 A.
The E1.2B 1000 has a rated ultimate short-circuit breaking capacity (Icu) of 42 kA at 380 V AC, 400–415 V AC, 440 V AC, 500–525 V AC and 690 V AC.
The breaker is fitted with an ABB Ekip Dip LSIG solid-state electronic trip unit, providing long-time overload, selective short-time short-circuit, instantaneous short-circuit and earth-fault protection.
The 1SDA071413R1 is a fixed four-pole circuit breaker with front terminals, designed for permanent installation within a low-voltage electrical switchboard.
ABB SACE Emax 2 air circuit breakers combine dependable switching, configurable electronic protection and high short-circuit performance for low-voltage electrical distribution systems across industrial, commercial and infrastructure applications.
We use cookies