1SDA071382R1 ABB E1.2C 800 Ekip Dip LSI 4p F F Air Circuit Breaker 800 A

1SDA071382R1 ABB E1.2C 800 Ekip Dip LSI 4p F F Air Circuit Breaker 800 A

ABB 1SDA071382R1 Emax 2 E1.2C 800 Ekip Dip LSI four-pole fixed air circuit breaker with front terminals, an 800 A rated current and 50 kA ultimate short-circuit breaking capacity at 440 V AC.

SKU: 1SDA071382R1MPN: 1SDA071382R1
Price
List Price £6,480.31 ex VAT
Your Price (ex VAT) Save 25%
£4,860.23 25% OFF
You save £1,620.08 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £4,860.23
Trade pricing is personalised to your account

Manufacturer Lead Time

£4,860.23

Why Choose the ABB E1.2C 800 Ekip Dip LSI 4p F F Air Circuit Breaker?

The ABB E1.2C 800 Ekip Dip LSI 4p F F, order code 1SDA071382R1, is a compact four-pole air circuit breaker (ACB) designed for switching and protection in low-voltage power distribution systems. As part of the ABB SACE Emax 2 series, this fixed circuit breaker combines an 800 A rated current, robust short-circuit performance and an Ekip Dip LSI electronic protection release.

The integrated Ekip Dip LSI electronic trip unit provides long-time overload, short-time short-circuit and instantaneous short-circuit protection. This combination supports effective overcurrent protection and selective coordination between protective devices, helping isolate faults while maintaining continuity of supply to unaffected sections of the electrical distribution system.

The E1.2C performance level provides an ultimate short-circuit breaking capacity of 50 kA at 440 V AC and a rated short-time withstand current of 42 kA for 1 s. This version features a four-pole fixed configuration with front terminals, making it suitable for compact three-phase four-wire switchboards and industrial power distribution assemblies.

Key Advantages

  • Compact ABB SACE Emax 2 air circuit breaker for low-voltage power distribution.
  • 800 A rated current for industrial, commercial and infrastructure installations.
  • 50 kA Icu at 440 V AC for dependable short-circuit interruption.
  • 42 kA Icw for 1 s supports robust short-time current withstand capability.
  • Ekip Dip LSI electronic protection release for comprehensive overcurrent protection.
  • Long-time, short-time and instantaneous protection functions support selective coordination.
  • Four-pole fixed construction supports three-phase four-wire distribution systems.
  • Front terminals provide straightforward integration into low-voltage switchboards.

Key Features

  • ABB SACE Emax 2 E1.2C series.
  • 800 A rated current.
  • 50 kA ultimate short-circuit breaking capacity at 440 V AC.
  • 42 kA rated short-time withstand current for 1 s.
  • Ekip Dip LSI electronic protection release.
  • Long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection.
  • DIP-switch configuration for straightforward protection adjustment.
  • Four-pole construction for three-phase systems with a neutral conductor.
  • Fixed breaker construction.
  • Front main circuit terminals.
  • Compact E1.2 frame designed for efficient use of switchboard space.

Selective Protection for Low-Voltage Distribution Systems

Air circuit breakers such as the ABB Emax 2 E1.2C provide switching and protection for low-voltage electrical distribution systems. By detecting overload and short-circuit conditions and interrupting fault current, the breaker helps protect switchboards, cables, busbars and connected electrical equipment while supporting dependable operation of the wider electrical installation.

The Ekip Dip LSI release combines long-time overload, short-time short-circuit and instantaneous short-circuit protection. The addition of short-time protection enables improved selectivity between protective devices, helping faults to be isolated closer to their source while maintaining continuity of supply to unaffected circuits.

Typical Applications

  • Low-voltage main and sub-distribution switchboards.
  • Industrial power distribution systems.
  • Commercial building electrical distribution.
  • Three-phase four-wire distribution networks.
  • Transformer secondary-side protection.
  • Manufacturing and process industry installations.
  • Infrastructure and utility distribution systems.
  • Power distribution panels requiring selective four-pole protection.

Technical Specifications

Series SACE Emax 2
Order code / MPN 1SDA071382R1
Product type Air circuit breaker
Frame / sub-type E1.2
Performance level C
Rated current 800 A
Rated operational voltage Up to 690 V AC
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 50 kA
Rated short-time withstand current (Icw) for 1 s 42 kA
Number of poles 4P
Current type AC
Trip unit Ekip Dip LSI electronic release
Protection functions Long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I)
Integrated earth-fault protection No
Protection setting method DIP switches
Mounting type Fixed
Terminal type Front terminals
Main circuit connection Front connection
Configuration Fixed breaker with front connections
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA071382R1 used for?

The ABB 1SDA071382R1 is a four-pole air circuit breaker designed for switching and protecting low-voltage electrical distribution systems against overload and short-circuit conditions.

What is the rated current of the ABB E1.2C 800?

This Emax 2 air circuit breaker has a rated current of 800 A, making it suitable for industrial, commercial and infrastructure low-voltage distribution systems.

What is the short-circuit performance of the ABB 1SDA071382R1?

The E1.2C 800 has an ultimate short-circuit breaking capacity of 50 kA at 440 V AC and a rated short-time withstand current of 42 kA for 1 s.

What protection functions does the Ekip Dip LSI release provide?

The Ekip Dip LSI electronic release provides long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection, supporting effective selectivity and circuit coordination.

Is the ABB 1SDA071382R1 fixed or withdrawable?

The 1SDA071382R1 is a fixed four-pole air circuit breaker with front main circuit terminals for integration into low-voltage switchboards.

Trusted Low-Voltage Circuit Protection

ABB SACE Emax 2 air circuit breakers combine compact construction, dependable interruption performance and configurable electronic protection for industrial, commercial and infrastructure low-voltage power distribution systems.