1SDA071305R1 ABB E6.2V 6300 Ekip Touch LSI 3-Pole Air Circuit Breaker

1SDA071305R1 ABB E6.2V 6300 Ekip Touch LSI 3-Pole Air Circuit Breaker

ABB 1SDA071305R1 is a SACE Emax 2 E6.2V 6300 A fixed three-pole air circuit breaker with rear horizontal terminals and an Ekip Touch LSI electronic release for selective high-current low-voltage power distribution protection.

SKU: 1SDA071305R1MPN: 1SDA071305R1
Price
List Price £56,558.95 ex VAT
Your Price (ex VAT) Save 25%
£42,419.21 25% OFF
You save £14,139.74 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £42,419.21
Trade pricing is personalised to your account

Manufacturer Lead Time

£42,419.21

Why Choose the ABB 1SDA071305R1 E6.2V 6300 Ekip Touch LSI Air Circuit Breaker?

The ABB 1SDA071305R1 is a high-performance SACE Emax 2 E6.2V air circuit breaker designed for protection and switching in demanding low-voltage power distribution systems. Rated at 6300 A, this three-pole fixed breaker combines the high short-circuit performance of the E6.2V frame with ABB's advanced Ekip Touch LSI electronic trip unit.

The Ekip Touch LSI solid-state release provides long-time overload (L), short-time selective short-circuit (S) and instantaneous short-circuit (I) protection. Its electronic protection architecture and touchscreen interface enable accurate configuration and monitoring, supporting selective coordination and dependable protection in complex industrial electrical networks.

The 1SDA071305R1 is supplied in a fixed three-pole configuration with rear horizontal terminals. With a rated operational voltage of up to 690 V AC, an ultimate short-circuit breaking capacity of 150 kA at 400–440 V AC and a rated short-time withstand current of 100 kA, it is engineered for major switchboards and critical high-current power distribution installations.

Key Advantages

  • High-current 6300 A SACE Emax 2 air circuit breaker.
  • E6.2V high-breaking-capacity frame for demanding low-voltage power systems.
  • Advanced Ekip Touch LSI electronic protection release.
  • Long-time, short-time and instantaneous protection functions support selective system protection.
  • 150 kA ultimate short-circuit breaking capacity at 400–440 V AC.
  • 100 kA short-time withstand current for 1 s and 3 s.
  • Fixed three-pole construction with rear flat horizontal terminals.
  • Suitable for transformer, generator, feeder and installation protection in major power distribution systems.

Key Features

  • ABB SACE Emax 2 E6.2V series.
  • 6300 A rated uninterrupted current.
  • 3-pole fixed configuration.
  • Ekip Touch LSI solid-state electronic trip unit.
  • Long-time overload protection (L).
  • Short-time selective short-circuit protection (S).
  • Instantaneous short-circuit protection (I).
  • 690 V AC rated operational voltage.
  • 1000 V AC rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • 150 kA Icu at 400–440 V AC.
  • 100 kA Icw for 1 s and 3 s.
  • Rear flat horizontal main terminals.
  • Supplied with four auxiliary contacts and circuit-breaker open/closed position indication.
  • Suitable for IT networks up to 690 V.

High-Current Selective Protection for Power Distribution

Air circuit breakers such as the ABB SACE Emax 2 E6.2V provide switching, isolation and fault protection for high-current low-voltage electrical networks. The E6.2V frame combines substantial continuous-current capability with high short-circuit interruption and short-time withstand performance, supporting dependable protection and selective coordination in large switchboards.

The Ekip Touch LSI electronic release continuously monitors the circuit and provides configurable long-time overload, short-time selective short-circuit and instantaneous short-circuit protection. Combined with the breaker's 6300 A rating and high fault-interruption capability, this makes the 1SDA071305R1 suitable for major industrial facilities, transformer and generator systems and critical electrical distribution infrastructure.

Typical Applications

  • Main incomer protection in high-current low-voltage switchboards.
  • Industrial power distribution systems.
  • Transformer and generator protection.
  • High-current feeder and busbar protection.
  • Manufacturing and process plants.
  • Data centres and critical infrastructure.
  • Utility and infrastructure electrical systems.
  • Large switchgear and power distribution assemblies.

Technical Specifications

Series SACE Emax 2
Frame E6.2V
ABB order code 1SDA071305R1
EAN 8015644751555
Product type Air circuit breaker
Rated current (In) 6300 A
Rated uninterrupted current (Iu) 6300 A
Number of poles 3
Installation Fixed
Main terminal arrangement Rear flat horizontal
Trip unit Ekip Touch LSI
Release type Electronic / solid-state
Protection functions Long-time (L), short-time (S), instantaneous (I)
Current type AC
Rated operational voltage (Ue) up to 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Ultimate short-circuit breaking capacity (Icu) at 400–440 V AC 150 kA
Ultimate short-circuit breaking capacity (Icu) at 500–525 V AC 130 kA
Ultimate short-circuit breaking capacity (Icu) at 690 V AC 100 kA
Service short-circuit breaking capacity (Ics) 100% of Icu
Rated short-time withstand current (Icw) 100 kA for 1 s / 3 s
Electrical durability 2000 cycles
Mechanical durability 12000 cycles
Power loss 767 W
Terminal type Bolt
Connecting capacity 6000 mm²
Tightening torque 70 N·m
Dimensions (W × H × D) 762 × 371 × 270 mm
Net weight approx. 112 kg
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA071305R1?

The ABB 1SDA071305R1 is a SACE Emax 2 E6.2V 6300 A three-pole fixed air circuit breaker equipped with an Ekip Touch LSI electronic protection release and rear horizontal terminals.

What is the rated current of the ABB 1SDA071305R1?

The circuit breaker has a rated uninterrupted current of 6300 A, making it suitable for very high-current low-voltage power distribution systems.

What protection functions does the Ekip Touch LSI trip unit provide?

The Ekip Touch LSI release provides long-time overload protection (L), short-time selective short-circuit protection (S) and instantaneous short-circuit protection (I).

What is the breaking capacity of the ABB E6.2V 6300?

The E6.2V 6300 has an ultimate short-circuit breaking capacity of 150 kA at 400–440 V AC, 130 kA at 500–525 V AC and 100 kA at 690 V AC.

Is the ABB 1SDA071305R1 fixed or withdrawable?

This model is a fixed three-pole air circuit breaker with rear flat horizontal main terminals.

What is the maximum rated operational voltage?

The ABB 1SDA071305R1 has a rated operational voltage of up to 690 V AC.