Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071268R1 Emax 2 E6.2H 5000 air circuit breaker, a 5000 A three-pole fixed ACB with Ekip Hi-Touch LSI electronic protection, 100 kA short-circuit breaking capacity at 440 V AC and 100 kA short-time withstand current for 1 s.
£29,292.92
The ABB E6.2H 5000 Ekip Hi-Touch LSI 3p F HR, order code 1SDA071268R1, is a high-performance Emax 2 air circuit breaker (ACB) designed for protection, switching and isolation in demanding high-current low-voltage electrical distribution systems. As part of the ABB SACE Emax 2 series, it combines a 5000 A rated uninterrupted current with the E6.2 frame and H short-circuit performance level for industrial, infrastructure and critical power applications.
This fixed three-pole circuit breaker incorporates the advanced Ekip Hi-Touch LSI solid-state electronic trip unit, providing long-time overload, selective short-time and instantaneous short-circuit protection. The Hi-Touch platform is designed for applications requiring sophisticated electronic protection, measurement and monitoring capabilities, while the LSI functions support selective coordination throughout complex low-voltage distribution systems.
With a 5000 A current rating, an ultimate short-circuit breaking capacity of 100 kA at 440 V AC and a rated short-time withstand current of 100 kA for 1 s, the E6.2H is engineered for high-current installations with substantial prospective fault levels. Its fixed three-pole construction and rear flat horizontal terminals provide a robust solution for integration into large low-voltage switchboards.
Air circuit breakers such as the ABB Emax 2 E6.2H provide switching, isolation and protection for high-current low-voltage distribution systems. With a 5000 A rated uninterrupted current, 100 kA ultimate short-circuit breaking capacity at 440 V AC and 100 kA short-time withstand capability for 1 s, this configuration is suited to main distribution points and other critical sections of installations with substantial prospective fault currents.
The Ekip Hi-Touch LSI electronic trip unit combines long-time overload protection with selective short-time and instantaneous short-circuit protection. Selective short-time protection assists coordination with downstream protective devices, while the Hi-Touch platform provides advanced electronic functionality for demanding power distribution and energy-management applications.
| Series | SACE Emax 2 |
|---|---|
| Order code / MPN | 1SDA071268R1 |
| EAN | 8015644751180 |
| Product type | Air circuit breaker (ACB) |
| Frame | E6.2 |
| Short-circuit performance level | H |
| Rated current | 5000 A |
| Rated uninterrupted current (Iu) | 5000 A |
| Rated ultimate short-circuit breaking capacity (Icu) | 100 kA at 440 V AC |
| Rated short-time withstand current (Icw) | 100 kA for 1 s |
| Number of poles | 3 |
| Current type | AC |
| Trip unit | Ekip Hi-Touch LSI |
| Release type | Solid-state electronic |
| Protection functions | Long-time overload, selective short-time and instantaneous short circuit |
| Integrated earth-fault protection | No |
| Mounting type | Fixed |
| Terminal connection | Rear flat horizontal |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Mechanical durability | 12,000 cycles |
| Electrical durability | 3,000 cycles at Ue ≤ 440 V; 2,000 cycles at Ue 500–690 V |
| Dimensions (H × W × D) | 371 × 762 × 270 mm |
| Net weight | 112 kg |
| Country of origin | Italy |
| Standard | IEC |
The ABB 1SDA071268R1 is an Emax 2 air circuit breaker designed for switching and protection of high-current low-voltage electrical distribution systems, including main incomers, transformer secondaries and high-current feeders requiring advanced LSI protection.
The circuit breaker has a rated uninterrupted current of 5000 A, making it suitable for demanding industrial, infrastructure and critical high-current power distribution systems.
The E6.2H 5000 provides an ultimate short-circuit breaking capacity of 100 kA at 440 V AC and a rated short-time withstand current of 100 kA for 1 s.
The Ekip Hi-Touch LSI solid-state electronic trip unit provides long-time overload, selective short-time and instantaneous short-circuit protection. This LSI configuration does not include integrated earth-fault protection.
The 1SDA071268R1 is a fixed three-pole air circuit breaker equipped with rear flat horizontal terminals for integration into high-current low-voltage switchboards.
ABB SACE Emax 2 air circuit breakers combine high-current capability, robust short-circuit performance and advanced Ekip electronic protection for demanding industrial, infrastructure and critical low-voltage power distribution applications.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.