Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071167R1 is a SACE Emax 2 E4.2H 3200 A fixed three-pole air circuit breaker with rear horizontal terminals, Ekip G Touch LSIG electronic protection and 100 kA ultimate breaking capacity at 400/415/440 V AC.
£15,333.46
The ABB E4.2H 3200 Ekip G Touch LSIG 3p FHR, order code 1SDA071167R1, is a high-performance SACE Emax 2 air circuit breaker (ACB) designed for advanced protection, switching and control of demanding low-voltage generator and power distribution systems. Rated at 3200 A, this three-pole fixed circuit breaker combines the E4.2H frame with ABB's advanced Ekip G Touch LSIG solid-state electronic trip unit.
The Ekip G Touch LSIG release provides comprehensive long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection together with functionality tailored to generator and critical power applications. Its electronic architecture supports sophisticated protection coordination, monitoring and power-system management in installations where continuity and dependable fault protection are essential.
This configuration is a fixed three-pole breaker equipped with rear horizontal (HR) terminals. The E4.2H performance level provides an ultimate short-circuit breaking capacity of 100 kA at 400/415/440 V AC, 85 kA at 690 V AC and a rated short-time withstand current of 85 kA for 1 s, making the 1SDA071167R1 suitable for demanding high-current switchboards and generator distribution systems.
Air circuit breakers such as the ABB SACE Emax 2 provide switching, isolation and fault protection for high-current low-voltage networks. The E4.2H frame combines a substantial 3200 A current rating with 100 kA breaking capacity at 400/415/440 V AC and 85 kA one-second withstand capability, making it suitable for main incomers, generator circuits and major distribution feeders.
The Ekip G Touch LSIG trip unit combines adjustable overload, short-time, instantaneous and earth-fault protection with advanced functionality for generator applications. This allows the breaker to support sophisticated power distribution architectures where selective coordination, system supervision, continuity of supply and intelligent electrical management are important requirements.
| Series | SACE Emax 2 |
|---|---|
| Frame | E4.2H |
| ABB order code | 1SDA071167R1 |
| EAN / GTIN | 8015644750176 |
| Product type | Air circuit breaker |
| Rated uninterrupted current (Iu) | 3200 A |
| Rated current (In) | 3200 A |
| Number of poles | 3 |
| Trip unit | Ekip G Touch LSIG |
| Release type | Solid-state electronic |
| Protection functions | L, S, I and G |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Ultimate short-circuit breaking capacity (Icu) at 400/415/440 V AC | 100 kA |
| Service short-circuit breaking capacity (Ics) at 400/415/440 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500/525 V AC | 85 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 85 kA |
| Service short-circuit breaking capacity (Ics) at 690 V AC | 85 kA |
| Rated short-time withstand current (Icw, 1 s) | 85 kA |
| Rated short-time withstand current (Icw, 3 s) | 66 kA |
| Rated service breaking capacity | 100% of Icu |
| Current type | AC |
| Short-circuit performance level | H |
| Installation | Fixed |
| Terminal configuration | Rear flat horizontal (HR) |
| Auxiliary contacts | 4 |
| Circuit-breaker position indication | Open / closed |
| Mechanical durability | 20000 cycles |
| Electrical durability | 7000 cycles |
| Power loss | 425 W |
| Dimensions | 384 × 371 × 270 mm |
| Standard | IEC |
| Product group | Emax2 Air Circuit Breaker |
The ABB 1SDA071167R1 is a SACE Emax 2 E4.2H fixed three-pole air circuit breaker rated at 3200 A and equipped with an Ekip G Touch LSIG solid-state electronic trip unit.
The trip unit provides long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection together with advanced functionality for generator and critical power applications.
The circuit breaker has a rated uninterrupted current of 3200 A.
The E4.2H provides an ultimate short-circuit breaking capacity of 100 kA at 400/415/440 V AC and 85 kA at 690 V AC.
The circuit breaker has a rated short-time withstand current of 85 kA for 1 s and 66 kA for 3 s.
Yes. The G function within the Ekip G Touch LSIG release provides integrated earth-fault protection in addition to long-time, short-time and instantaneous overcurrent protection.
Yes. The Ekip G Touch trip unit is designed with functionality for generator and power-system applications, making this breaker suitable for generator switchboards, standby power systems and critical distribution networks.
The 1SDA071167R1 is a fixed-version circuit breaker equipped with rear horizontal terminals for permanent installation within a low-voltage switchboard.
ABB SACE Emax 2 air circuit breakers combine high-current switching and protection with advanced electronic trip technology, monitoring and power-management capabilities for demanding industrial, infrastructure and power-generation applications worldwide.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.