ABB 1SDA071156R1 E4.2S 3200 Ekip Touch LSIG 3p F HR is a fixed three-pole 3200 A SACE Emax 2 air circuit breaker with 85 kA short-circuit breaking capacity at 415 V AC and Ekip Touch LSIG electronic protection including earth-fault protection.
£12,161.55
The ABB E4.2S 3200 Ekip Touch LSIG 3p F HR, order code 1SDA071156R1, is a high-performance air circuit breaker (ACB) designed for protection, control and isolation in demanding low-voltage electrical distribution systems. Part of the ABB SACE Emax 2 series, this fixed three-pole circuit breaker combines a 3200 A rated current with the Ekip Touch LSIG solid-state electronic trip unit.
The Ekip Touch LSIG release provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection. Its configurable electronic protection functions and touchscreen interface support effective protection coordination while providing an accessible platform for setting and supervising the circuit breaker's protection parameters.
The E4.2S performance level provides an ultimate short-circuit breaking capacity of 85 kA at 415 V AC, making this breaker suitable for high-current systems with substantial prospective fault levels. This version features a fixed three-pole construction with rear horizontal terminals, four auxiliary contacts and circuit-breaker open/closed position indication.
Air circuit breakers such as the ABB SACE Emax 2 protect low-voltage electrical distribution systems against overloads, short circuits and earth faults while providing dependable switching and isolation. The E4.2S frame combines a substantial 3200 A current rating with 85 kA short-circuit breaking performance at 415 V AC, making it suitable for main distribution systems and other high-current installations with demanding fault levels.
The Ekip Touch LSIG electronic trip unit combines long-time overload, short-time delayed, instantaneous short-circuit and earth-fault protection. The combination of configurable protection functions and the Ekip Touch interface supports selective coordination with other protective devices, helping isolate faults while maintaining continuity on unaffected parts of the electrical distribution system.
| Series | SACE Emax 2 |
|---|---|
| ABB product group | Emax2 Air Circuit Breaker |
| Frame | E4.2S |
| ABB order code / MPN | 1SDA071156R1 |
| Product type | Air circuit breaker |
| Rated current | 3200 A |
| Rated operational voltage | 690 V AC |
| Ultimate short-circuit breaking capacity (Icu) | 85 kA at 415 V AC |
| Number of poles | 3 |
| Current type | AC |
| Trip unit | Ekip Touch LSIG |
| Release type | Solid-state electronic |
| Protection functions | LSIG |
| Long-time protection | Overload protection |
| Short-time protection | Delayed short-circuit protection |
| Instantaneous protection | Short-circuit protection |
| Earth-fault protection | Integrated |
| Short-circuit performance level | S |
| Installation version | Fixed |
| Main terminal position | Rear |
| Main terminal orientation | Rear horizontal |
| Terminal type | Bolt |
| Auxiliary contacts | 4 |
| Open/closed position indication | Yes |
| Mechanical durability | 20,000 cycles |
| Electrical durability | 7,000 cycles at Ue ≤ 440 V; 7,000 cycles at Ue 500–690 V |
| Power loss | 425 W |
| Dimensions (W × H × D) | 384 × 371 × 270 mm |
| Net weight | 60 kg |
| Standard | IEC 60947-2 |
| Country of origin | Italy |
| EAN / GTIN | 8015644750060 |
The ABB 1SDA071156R1 is an Emax 2 air circuit breaker designed to protect, control and isolate high-current low-voltage electrical distribution circuits in industrial, commercial and infrastructure applications, including systems requiring integrated earth-fault protection.
The circuit breaker has a rated current of 3200 A, making it suitable for substantial low-voltage power distribution circuits and high-current main incomer applications.
The E4.2S 3200 provides an ultimate short-circuit breaking capacity of 85 kA at 415 V AC, providing high fault interruption capability for demanding low-voltage distribution systems.
The Ekip Touch LSIG trip unit provides long-time overload (L), short-time delayed short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection.
The 1SDA071156R1 is a fixed three-pole air circuit breaker equipped with rear horizontal terminals for integration into low-voltage switchboards.
ABB SACE Emax 2 air circuit breakers are designed for reliable protection, control and monitoring of low-voltage power distribution systems, combining high short-circuit performance with advanced electronic protection for demanding industrial and commercial installations.