1SDA070998R1 ABB E2.2N 1600 Ekip Hi-Touch LSI 3P Air Circuit Breaker

1SDA070998R1 ABB E2.2N 1600 Ekip Hi-Touch LSI 3P Air Circuit Breaker

ABB 1SDA070998R1 E2.2N 1600 Ekip Hi-Touch LSI three-pole fixed SACE Emax 2 air circuit breaker rated at 1600 A with advanced long-time, short-time and instantaneous electronic protection.

SKU: 1SDA070998R1MPN: 1SDA070998R1
Price
List Price £10,290.52 ex VAT
Your Price (ex VAT) Save 25%
£7,717.89 25% OFF
You save £2,572.63 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £7,717.89
Trade pricing is personalised to your account

Manufacturer Lead Time

£7,717.89

Why Choose the ABB E2.2N 1600 Ekip Hi-Touch LSI 3P Air Circuit Breaker?

The ABB E2.2N 1600 Ekip Hi-Touch LSI 3P, order code 1SDA070998R1, is a high-performance SACE Emax 2 air circuit breaker (ACB) designed for advanced protection and switching in demanding low-voltage electrical distribution systems. This fixed three-pole E2.2N breaker combines a rated uninterrupted current of 1600 A with ABB's advanced Ekip Hi-Touch LSI solid-state electronic trip unit.

The Ekip Hi-Touch LSI release provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. Its advanced electronic architecture supports precise protection settings, selective coordination and detailed electrical monitoring, helping protect cables, busbars, transformers and connected equipment while supporting continuity of service.

The E2.2N performance level provides an ultimate short-circuit breaking capacity of 66 kA at 400 V AC. This configuration is a fixed three-pole breaker with rear horizontal terminals and is fitted with four auxiliary changeover contacts plus circuit-breaker open/closed position indication for integration into modern switchboards.

Key Advantages

  • Advanced ABB SACE Emax 2 air circuit breaker for demanding low-voltage power distribution.
  • 1600 A rated uninterrupted current for high-current industrial and commercial applications.
  • Ekip Hi-Touch LSI electronic trip unit combines advanced functionality with comprehensive overcurrent protection.
  • Short-time delayed protection supports selective coordination between upstream and downstream protective devices.
  • 66 kA ultimate short-circuit breaking capacity at 400 V AC.
  • Fixed three-pole construction with rear horizontal terminals for efficient switchboard integration.

Key Features

  • ABB SACE Emax 2 E2.2N frame.
  • 1600 A rated uninterrupted current.
  • Three-pole construction.
  • Fixed-mounted execution.
  • Rear horizontal main terminals.
  • Ekip Hi-Touch LSI solid-state electronic protection release.
  • Long-time overload protection.
  • Short-time delayed short-circuit protection.
  • Instantaneous short-circuit protection.
  • Overload setting range from 640–1600 A.
  • Short-time delayed short-circuit adjustment from 960–16000 A.
  • Instantaneous short-circuit adjustment from 2400–24000 A.
  • Four auxiliary changeover contacts.
  • Circuit-breaker open/closed position indication.

Advanced Hi-Touch LSI Protection for Low-Voltage Distribution

ABB SACE Emax 2 air circuit breakers combine robust switching performance with advanced electronic protection for modern low-voltage networks. The E2.2N 1600 provides the current-carrying and fault-interruption capability required for main distribution boards, transformer-fed systems, industrial switchboards and high-current feeder circuits.

The Ekip Hi-Touch LSI release combines long-time overload protection with short-time delayed and instantaneous short-circuit functions. The short-time function supports selective coordination between protective devices, helping isolate downstream faults without unnecessarily disconnecting healthy sections of the electrical network, while the Hi-Touch platform provides enhanced functionality for sophisticated power-distribution applications.

Typical Applications

  • Main low-voltage electrical switchboards.
  • Industrial power distribution systems.
  • Commercial building electrical distribution.
  • Transformer incomer and secondary protection.
  • High-current feeder protection.
  • Manufacturing and process facilities.
  • Infrastructure and utility installations.
  • Power systems requiring advanced selective protection and monitoring.

Technical Specifications

Series SACE Emax 2 E2.2
ABB order code 1SDA070998R1
EAN 8015644748487
Product type Air circuit breaker (ACB)
Performance level N
Rated uninterrupted current (Iu) 1600 A
Rated voltage 690 V AC
Current type AC
Number of poles 3
Trip unit Ekip Hi-Touch LSI
Release type Solid-state electronic
Protection functions LSI (Long-time, Short-time, Instantaneous)
Overload release adjustment 640–1600 A
Short-time delayed short-circuit adjustment 960–16000 A
Instantaneous short-circuit adjustment 2400–24000 A
Ultimate short-circuit breaking capacity (Icu) at 400 V AC 66 kA
Integrated ground-fault protection No
Mounting Fixed
Main terminals Rear horizontal
Auxiliary changeover contacts 4
Position indication Circuit breaker open / closed
Motor operator Optional
Product width 276 mm
Product height 371 mm
Product depth 270 mm
Product net weight 45 kg
Mechanical durability 25,000 cycles
Electrical durability at up to 440 V 12,000 cycles
Electrical durability at 500–690 V 10,000 cycles

Frequently Asked Questions

What is the ABB 1SDA070998R1 used for?

The ABB 1SDA070998R1 is an Emax 2 air circuit breaker designed for advanced switching and protection of demanding low-voltage electrical distribution circuits against overload and short-circuit conditions.

What is the current rating of the ABB E2.2N 1600?

The circuit breaker has a rated uninterrupted current of 1600 A.

What protection functions does the Ekip Hi-Touch LSI trip unit provide?

The Ekip Hi-Touch LSI electronic trip unit provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection.

What is the breaking capacity of the ABB E2.2N 1600?

The E2.2N 1600 provides an ultimate short-circuit breaking capacity of 66 kA at 400 V AC.

What terminal configuration does the ABB 1SDA070998R1 use?

This fixed three-pole circuit breaker uses rear horizontal terminals for integration into low-voltage switchboard and busbar systems.

Trusted ABB Power Distribution Technology

ABB SACE Emax 2 air circuit breakers combine advanced electronic protection, robust switching and selective coordination capabilities to safeguard modern industrial, commercial and infrastructure low-voltage power distribution systems.