ABB 1SDA070929R1 Emax 2 E2.2N 1000 air circuit breaker, a fixed three-pole 1000 A ACB with horizontal rear terminals and Ekip Hi-Touch LSIG electronic overload, short-circuit and earth-fault protection.
£7,878.72
The ABB E2.2N 1000 Ekip Hi-Touch LSIG 3p FHR, order code 1SDA070929R1, is a high-performance SACE Emax 2 air circuit breaker (ACB) designed for advanced protection and switching in demanding low-voltage AC power distribution systems. Part of the ABB Emax 2 E2.2 series, it combines a 1000 A current rating with the E2.2N performance class and ABB's advanced Ekip Hi-Touch electronic protection platform.
This model is a fixed, three-pole circuit breaker with horizontal rear terminals equipped with an Ekip Hi-Touch LSIG solid-state electronic release. Its LSIG protection functions provide long-time overload, short-time delayed short-circuit, instantaneous short-circuit and integrated earth-fault protection, supporting comprehensive protection and selective coordination throughout low-voltage distribution networks.
With a rated uninterrupted current of 1000 A, rated voltage of 690 V AC and rated ultimate short-circuit breaking capacity of 66 kA at 400 V AC, the E2.2N 1000 is engineered for substantial industrial and infrastructure loads. Four auxiliary change-over contacts, open/closed position indication and optional motorised operation further support integration into sophisticated switchboard control and automation systems.
Air circuit breakers such as the ABB Emax 2 E2.2N protect low-voltage electrical networks by interrupting current when hazardous overload, short-circuit or earth-fault conditions occur. The Ekip Hi-Touch LSIG electronic release provides independently configurable long-time, short-time, instantaneous and ground-fault protection functions, supporting comprehensive protection and effective coordination between upstream and downstream devices.
The E2.2N platform combines 66 kA short-circuit breaking performance at 400 V AC with advanced electronic protection and robust Emax 2 construction. Its horizontal rear terminals facilitate connection to switchboard busbars, while auxiliary contacts, position indication and optional motorised operation make the 1SDA070929R1 well suited to intelligent industrial and infrastructure power-distribution systems.
| Series | SACE Emax 2 E2.2 |
|---|---|
| ABB order code | 1SDA070929R1 |
| EAN | 8015644747794 |
| Product type | Air circuit breaker |
| Frame / performance class | E2.2N |
| Rated uninterrupted current (Iu) | 1000 A |
| Rated voltage | 690 V AC |
| Number of poles | 3 |
| Version | Fixed |
| Terminal arrangement | Horizontal rear terminals |
| Trip unit | Ekip Hi-Touch LSIG electronic release |
| Release technology | Solid-state electronic |
| Protection functions | L (long-time overload), S (short-time short circuit), I (instantaneous short circuit), G (earth fault) |
| Integrated earth-fault protection | Yes |
| Overload release setting | 400–1000 A |
| Short-time delayed short-circuit setting | 600–10000 A |
| Instantaneous short-circuit setting | 1500–15000 A |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC, 50 Hz | 66 kA |
| Auxiliary contacts | 4 change-over contacts |
| Position indication | Circuit breaker open / closed |
| Complete device with protection unit | Yes |
| Integrated motor drive | No |
| Optional motor drive | Yes |
| Integrated undervoltage release | No |
| DIN rail mounting | No |
| Dimensions | 371 × 276 × 270 mm |
| Net weight | 41 kg |
| Standard / approval | IEC |
The ABB 1SDA070929R1 is an Emax 2 E2.2N air circuit breaker designed for switching and protecting high-current low-voltage AC distribution circuits, including systems requiring selective overcurrent and integrated earth-fault protection.
The circuit breaker has a rated uninterrupted current of 1000 A and a rated voltage of 690 V AC.
The Ekip Hi-Touch LSIG electronic trip unit provides long-time overload (L), short-time delayed short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection.
The E2.2N 1000 has a rated ultimate short-circuit breaking capacity of 66 kA at 400 V AC, 50 Hz, providing robust fault interruption for demanding low-voltage distribution systems.
The FHR configuration identifies a fixed circuit breaker with horizontal rear terminals, providing a connection arrangement particularly suited to integration with busbars inside low-voltage switchboards.
ABB SACE Emax 2 air circuit breakers combine advanced electronic protection, robust short-circuit performance and flexible switchboard integration to provide dependable protection and selective control for modern low-voltage power distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.