1SDA067643R1 ABB XT2L 160 TMA 50-500 3P F F Moulded-Case Circuit Breaker

1SDA067643R1 ABB XT2L 160 TMA 50-500 3P F F Moulded-Case Circuit Breaker

ABB 1SDA067643R1 is a three-pole SACE Tmax XT2L 160 moulded-case circuit-breaker with a 50 A TMA thermomagnetic release, adjustable 35–50 A overload protection, adjustable 300–500 A magnetic protection and fixed front terminals.

SKU: 1SDA067643R1MPN: 1SDA067643R1
Price
List Price £562.02 ex VAT
Your Price (ex VAT) Save 25%
£421.52 25% OFF
You save £140.51 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £421.52
Trade pricing is personalised to your account

Manufacturer Lead Time

£421.52

Why Choose the ABB XT2L 160 TMA 50-500 3P F F Circuit Breaker?

The ABB 1SDA067643R1 is a complete SACE Tmax XT2L 160 moulded-case circuit-breaker designed for low-voltage power distribution. Identified by ABB as XT2L 160 TMA 50-500 3P F F, it combines a three-pole configuration with fixed mounting, front terminals and an integrated TMA thermomagnetic release.

The integrated TMA thermomagnetic release has a rated current of 50 A and provides both overload and short-circuit protection. Its thermal overload setting is adjustable from 35–50 A, while the instantaneous magnetic short-circuit setting is adjustable from 300–500 A, allowing the protection characteristics to be coordinated with the requirements of the protected circuit.

The XT2L performance level provides high short-circuit interruption capability, including a rated ultimate short-circuit breaking capacity of 120 kA at 415 V AC. Combined with its compact XT2 frame, fixed construction and front terminals, the 1SDA067643R1 is well suited to industrial and commercial switchboards where dependable protection and high fault-current performance are required.

Key Advantages

  • Complete ABB SACE Tmax XT2L 160 moulded-case circuit-breaker.
  • 50 A TMA thermomagnetic release for overload and short-circuit protection.
  • Adjustable thermal overload setting from 35–50 A.
  • Adjustable instantaneous magnetic protection from 300–500 A.
  • High 120 kA Icu at 415 V AC short-circuit breaking capacity.
  • Fixed three-pole construction with front terminals for switchboard integration.

Key Features

  • ABB SACE Tmax XT2L 160 moulded-case circuit-breaker.
  • TMA thermomagnetic release.
  • 50 A rated current.
  • Adjustable thermal overload protection from 35–50 A.
  • Adjustable instantaneous magnetic protection from 300–500 A.
  • Magnetic adjustment range of 6–10 × In.
  • Three-pole configuration.
  • Fixed installation.
  • Front terminals for main circuit connections.
  • Rated uninterrupted current of 160 A for the XT2 frame.
  • Rated ultimate short-circuit breaking capacity of 120 kA at 415 V AC.
  • L short-circuit performance level.
  • Designed for power distribution applications.
  • Designed in accordance with IEC 60947-2.

High-Capacity Thermomagnetic Protection for Power Distribution

Thermomagnetic circuit-breakers combine an inverse-time thermal element for sustained overload protection with a magnetic element that responds rapidly to high short-circuit currents. On the ABB 1SDA067643R1, the thermal setting can be adjusted from 35–50 A and the instantaneous magnetic threshold from 300–500 A, providing flexibility when coordinating the circuit-breaker with the protected conductors and connected equipment.

The XT2L performance level provides high interruption capability within the compact XT2 frame. With an Icu of 120 kA at 415 V AC, three-pole construction and fixed front-terminal configuration, this circuit-breaker is suitable for distribution systems where substantial prospective short-circuit currents may be present.

Typical Applications

  • Industrial low-voltage distribution switchboards.
  • Commercial building electrical distribution.
  • Three-phase feeder protection.
  • Main and sub-distribution panels.
  • Machinery and production-line power supplies.
  • Installations requiring high short-circuit breaking capacity.

Technical Specifications

Product group T-Max XT 250 Range
Series SACE Tmax XT2
Performance level XT2L
Frame size XT2 160
ABB order code 1SDA067643R1
EAN / GTIN 8015644695491
Product type Moulded-case circuit-breaker
Trip unit TMA thermomagnetic release
Release type Thermomagnetic
Release rated current 50 A
Thermal overload setting 35–50 A
Thermal adjustment 0.7–1 × In
Instantaneous magnetic setting 300–500 A
Magnetic protection adjustment 6–10 × In
Protection functions Thermal overload and magnetic short-circuit protection
Number of poles 3
Rated uninterrupted current (Iu) 160 A
Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC 120 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 18 kA
Short-circuit performance level L
Mounting Fixed
Main terminals Front terminals
Terminal type Bolt connection
Application Power distribution
Standard IEC 60947-2
Electrical durability 8,000 operating cycles
Mechanical durability 25,000 operating cycles
Product dimensions (W × H × D) 90 × 130 × 82.5 mm
Product net weight 1.2 kg

Frequently Asked Questions

What is the ABB 1SDA067643R1?

The ABB 1SDA067643R1 is a complete XT2L 160 three-pole moulded-case circuit-breaker with fixed mounting, front terminals and a 50 A TMA thermomagnetic release.

What is the overload setting range of the ABB 1SDA067643R1?

The TMA thermal overload release is adjustable from 35–50 A, corresponding to 0.7–1 × In for the 50 A release.

What is the magnetic short-circuit setting range?

The instantaneous magnetic setting is adjustable from 300–500 A, corresponding to 6–10 × In for the 50 A TMA release.

What is the breaking capacity of the ABB 1SDA067643R1?

The XT2L configuration has a rated ultimate short-circuit breaking capacity of 120 kA at 415 V AC and 18 kA at 690 V AC.

How is the ABB 1SDA067643R1 installed?

The 1SDA067643R1 is a fixed three-pole circuit-breaker with front terminals, designed for integration into compatible low-voltage switchboards and distribution assemblies.

Trusted by Electrical Distribution Professionals

ABB SACE Tmax XT moulded-case circuit-breakers combine compact construction, configurable thermomagnetic protection and high short-circuit performance for industrial and commercial low-voltage distribution systems.