1SDA062981R1 ABB T7V 1250 PR332/P LI 1250A 3P Circuit Breaker

1SDA062981R1 ABB T7V 1250 PR332/P LI 1250A 3P Circuit Breaker

ABB 1SDA062981R1 is a SACE Tmax T7V 1250 A three-pole fixed moulded-case circuit breaker with a PR332/P LI electronic trip unit, stored-energy operating mechanism and 150 kA ultimate short-circuit breaking capacity at 400 V AC for adjustable overload and instantaneous short-circuit protection.

SKU: 1SDA062981R1MPN: 1SDA062981R1
Price
List Price £12,497.23 ex VAT
Your Price (ex VAT) Save 25%
£9,372.92 25% OFF
You save £3,124.31 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £9,372.92
Trade pricing is personalised to your account

Manufacturer Lead Time

£9,372.92

Why Choose the ABB T7V 1250 PR332/P LI 1250A Circuit Breaker?

The ABB 1SDA062981R1, designated T7V 1250 PR332/P LI In=1250A 3p F F M, is a high-performance three-pole moulded-case circuit breaker (MCCB) designed for protection and switching in demanding low-voltage power distribution systems. Part of the established ABB SACE Tmax T7 series, it combines a rated uninterrupted current of 1250 A with the PR332/P LI solid-state electronic trip unit for adjustable overload and instantaneous short-circuit protection.

The T7V performance level is engineered for installations with very high prospective fault currents, providing a rated ultimate short-circuit breaking capacity of 150 kA at 400 V AC, 50 Hz. The PR332/P LI electronic release provides adjustable long-time overload protection together with adjustable instantaneous short-circuit protection, enabling the breaker to protect high-current distribution circuits against both sustained overloads and severe fault currents.

The 1SDA062981R1 is a fixed three-pole breaker with front terminals and a stored-energy operating mechanism. It also supports an optional motor drive, making it suitable for installations requiring remote or automated switching as well as dependable local circuit protection in industrial, commercial and infrastructure power distribution systems.

Key Advantages

  • High-performance 1250 A moulded-case circuit breaker for demanding low-voltage distribution systems.
  • 150 kA ultimate short-circuit breaking capacity at 400 V AC, 50 Hz.
  • Advanced PR332/P LI solid-state electronic trip unit.
  • Adjustable long-time overload and instantaneous short-circuit protection.
  • Three-pole configuration designed for three-phase electrical distribution networks.
  • Stored-energy operating mechanism with optional motor drive capability for remote or automated switching.

Key Features

  • ABB SACE Tmax T7V 1250 series.
  • 1250 A rated uninterrupted current.
  • PR332/P LI electronic protection trip unit.
  • 150 kA Icu at 400 V AC, 50 Hz.
  • Three-pole configuration.
  • 500–1250 A adjustable overload release range.
  • 1875–18750 A adjustable instantaneous short-circuit release range.
  • Fixed construction with front main-circuit terminals.
  • Bolt-connected main circuit.
  • Stored-energy operating mechanism.
  • Optional motor drive capability.
  • IP20 degree of protection.

Advanced LI Protection for High-Power Distribution

The ABB Tmax T7V platform is designed for high-current low-voltage systems where substantial fault interruption capability and configurable electronic protection are required. With a rated uninterrupted current of 1250 A and an ultimate short-circuit breaking capacity of 150 kA at 400 V AC, 50 Hz, the 1SDA062981R1 provides robust protection for electrical distribution networks with very high prospective short-circuit currents.

The PR332/P LI electronic trip unit combines adjustable long-time overload protection from 500–1250 A with instantaneous short-circuit protection adjustable from 1875–18750 A. Combined with its fixed three-pole construction, front terminals and stored-energy operating mechanism, the breaker provides a flexible solution for high-current three-phase distribution and can be equipped for motorised operation where required.

Typical Applications

  • Main low-voltage distribution switchboards.
  • Industrial power distribution systems.
  • Manufacturing and process plants.
  • Commercial buildings and infrastructure installations.
  • Transformer secondary and high-current feeder protection.
  • Three-phase electrical distribution networks.
  • High fault-level and remotely operated power distribution systems.

Technical Specifications

Series SACE Tmax T7
ABB order code 1SDA062981R1
ABB product group 310511-T-Max T4 - T8
EAN / GTIN 8015644655303
Product type Moulded-case circuit breaker (MCCB)
Frame T7V 1250
Rated uninterrupted current Iu 1250 A
Number of poles 3
Trip unit PR332/P LI
Release type Solid-state electronic
Protection functions LI – long-time overload and instantaneous short-circuit protection
Overload release current setting 500–1250 A
Instantaneous short-circuit release adjustment 1875–18750 A
Rated voltage 690 V AC
Ultimate short-circuit breaking capacity Icu at 400 V AC, 50 Hz 150 kA
Installation Fixed
Terminal position Front
Main circuit connection Bolt connection
Operating mechanism Stored-energy mechanism
Optional motor drive Yes
Degree of protection IP20
Country of origin Italy
Weight approx. 12.5 kg

Frequently Asked Questions

What is the ABB 1SDA062981R1 used for?

The ABB 1SDA062981R1 is a 1250 A three-pole moulded-case circuit breaker designed for switching and protection against overload and short-circuit conditions in high-current three-phase low-voltage electrical distribution systems.

What trip unit is fitted to the ABB T7V 1250 1SDA062981R1?

The circuit breaker is fitted with an ABB PR332/P LI solid-state electronic trip unit, providing adjustable long-time overload and instantaneous short-circuit protection.

What is the breaking capacity of the ABB 1SDA062981R1?

The ABB T7V 1250 1SDA062981R1 has a rated ultimate short-circuit breaking capacity of 150 kA at 400 V AC, 50 Hz, making it suitable for installations with very high prospective fault currents.

What are the protection adjustment ranges of the ABB 1SDA062981R1?

The overload release can be adjusted from 500–1250 A, while the instantaneous short-circuit release can be adjusted from 1875–18750 A.

Can the ABB 1SDA062981R1 be motor operated?

Yes. The breaker uses a stored-energy operating mechanism and supports an optional motor drive, allowing it to be incorporated into remote or automated switching systems when suitably equipped.