1SDA062858R1 ABB T7V 1000 PR231/P LS/I 1000 A 4-Pole MCCB

1SDA062858R1 ABB T7V 1000 PR231/P LS/I 1000 A 4-Pole MCCB

ABB 1SDA062858R1 is a SACE Tmax T7V 1000 A four-pole fixed motorisable moulded case circuit breaker with front terminals, a PR231/P-LS/I electronic trip unit and 150 kA ultimate breaking capacity at 380–415 V AC.

SKU: 1SDA062858R1MPN: 1SDA062858R1
Price
List Price £8,185.88 ex VAT
Your Price (ex VAT) Save 25%
£6,139.41 25% OFF
You save £2,046.47 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £6,139.41
Trade pricing is personalised to your account

Manufacturer Lead Time

£6,139.41

Why Choose the ABB T7V 1000 1SDA062858R1 Circuit Breaker?

The ABB 1SDA062858R1 is a high-performance SACE Tmax T7V moulded case circuit breaker (MCCB) designed for demanding low-voltage power distribution systems. ABB identifies this order code as T7V 1000 PR231/P LS/I In=1000A 4p F F M, combining a 1000 A rated current, four-pole construction and the PR231/P-LS/I electronic trip unit.

The T7V performance level provides an ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC, making this breaker suitable for installations with very high prospective fault currents. Its PR231/P-LS/I electronic trip unit provides adjustable overload and short-circuit protection, with a long-time setting range of 400–1000 A and a short-circuit threshold range of 1000–10000 A.

This version is a four-pole, fixed circuit breaker with front terminals in ABB's motorisable T7V configuration. Its combination of high interruption performance, adjustable electronic protection and four-pole switching makes the 1SDA062858R1 well suited to industrial switchboards, main distribution assemblies and automated three-phase four-wire power distribution systems.

Key Advantages

  • High-performance 1000 A moulded case circuit breaker for demanding power distribution applications.
  • 150 kA ultimate breaking capacity at 380–415 V AC for very high prospective fault levels.
  • PR231/P-LS/I electronic trip unit for adjustable overload and short-circuit protection.
  • Long-time protection adjustable from 400–1000 A.
  • Short-circuit protection threshold adjustable from 1000–10000 A.
  • Four-pole construction for three-phase four-wire distribution systems.
  • Fixed installation with front terminals for switchboard integration.
  • Motorisable T7V configuration suitable for automated power distribution systems.

Key Features

  • ABB SACE Tmax T7V 1000 series.
  • 1000 A rated current.
  • PR231/P-LS/I electronic protection trip unit.
  • Adjustable long-time overload protection.
  • Adjustable short-circuit protection.
  • 400–1000 A long-time protection setting range.
  • 1000–10000 A short-circuit protection threshold range.
  • 150 kA Icu at 380–415 V AC.
  • Four-pole (4P) construction.
  • Fixed (F) installation.
  • Front terminals (F).
  • Motorisable (M) configuration.
  • ABB order code 1SDA062858R1.

Adjustable Electronic Protection for High-Current Distribution

The ABB SACE Tmax T7V platform is designed for high-current low-voltage distribution systems where substantial short-circuit interruption capability is required. The 1SDA062858R1 combines a 1000 A rating with an ultimate breaking capacity of 150 kA at 380–415 V AC, providing robust protection for switchboards, feeders and distribution assemblies exposed to very high prospective fault currents.

The PR231/P-LS/I electronic trip unit provides adjustable protection characteristics for coordinating the breaker with the protected circuit. Its 400–1000 A long-time setting range allows overload protection to be matched to the installation, while the 1000–10000 A short-circuit threshold provides adjustable response to higher fault currents. Four-pole construction and a motorisable operating configuration further support integration into sophisticated industrial power distribution systems.

Typical Applications

  • Industrial low-voltage power distribution systems.
  • Main and sub-main electrical switchboards.
  • Three-phase four-wire distribution systems.
  • High-current feeder and cable protection.
  • Manufacturing and process plant electrical systems.
  • Automated power distribution switchgear.
  • Commercial and infrastructure distribution assemblies.
  • OEM switchgear and electrical panel systems.

Technical Specifications

Series SACE Tmax T7
ABB order code 1SDA062858R1
Product type Moulded case circuit breaker (MCCB)
Frame / breaker size T7 1000
Short-circuit performance level V
Rated current (In) 1000 A
Long-time protection setting range 400–1000 A
Short-circuit protection threshold 1000–10000 A
Ultimate short-circuit breaking capacity (Icu) 150 kA at 380–415 V AC
Number of poles 4
Trip unit PR231/P-LS/I electronic trip unit
Protection Adjustable overload and short-circuit protection
Installation Fixed
Terminal configuration Front terminals
Operating configuration Motorisable
Application Power distribution and high-current circuit protection
Product group 310511 – T-Max T4 - T8

Frequently Asked Questions

What is the ABB 1SDA062858R1 used for?

The ABB 1SDA062858R1 is a 1000 A four-pole moulded case circuit breaker designed for protection and control of high-current low-voltage power distribution circuits.

What breaking capacity does the ABB T7V 1000 1SDA062858R1 provide?

The T7V configuration provides an ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC, making it suitable for installations with very high prospective fault currents.

Which trip unit is fitted to the ABB 1SDA062858R1?

The breaker is equipped with an ABB PR231/P-LS/I electronic trip unit, providing adjustable overload and short-circuit protection for power distribution applications.

What are the protection settings of the ABB 1SDA062858R1?

The long-time protection setting is adjustable from 400–1000 A, while the short-circuit protection threshold is adjustable from 1000–10000 A.

What does 4p F F M mean on the ABB 1SDA062858R1?

4p identifies a four-pole circuit breaker, F F denotes fixed installation with front terminals, and M identifies ABB's motorisable T7V operating configuration.

Trusted ABB Power Distribution Protection

ABB SACE Tmax moulded case circuit breakers combine high short-circuit interruption performance with adjustable electronic protection and flexible operating configurations for dependable protection and control of demanding industrial and commercial power distribution systems.