ABB T7V 1000 PR231/P LS/I 4-pole moulded case circuit breaker with a 1000 A rated current, fixed front-terminal configuration, adjustable electronic protection and 150 kA breaking capacity at 380/415 V AC.
£5,581.27
The ABB T7V 1000 PR231/P LS/I is a high-performance 4-pole moulded case circuit breaker (MCCB) designed for protection and control of demanding low-voltage power distribution systems. As part of the established ABB Tmax T7 series, it combines a 1000 A rated uninterrupted current with an electronic protection unit and very high short-circuit breaking capability.
Equipped with the PR231/P LS/I solid-state electronic release, the T7V 1000 provides adjustable overload and short-circuit protection for power distribution applications. The overload release can be set from 400–1000 A, while the short-circuit protection adjustment extends from 1000–10000 A, supporting effective coordination within industrial and commercial electrical networks.
With an ultimate short-circuit breaking capacity of 150 kA at 380/415 V AC, a rated voltage of 690 V AC and a fixed four-pole configuration with front terminals, the T7V 1000 is engineered for switchboards and distribution assemblies where dependable protection against high prospective fault currents is essential.
Moulded case circuit breakers such as the ABB Tmax T7 protect electrical distribution circuits against overload and short-circuit conditions. The electronic protection unit monitors current and initiates circuit interruption when configured protection thresholds are exceeded, helping protect cables, switchgear and connected equipment from damaging fault currents.
The T7V 1000 combines a high current rating with very high short-circuit breaking capability and adjustable PR231/P LS/I protection. Its four-pole construction allows it to be incorporated into three-phase distribution systems with a neutral conductor, while the fixed front-terminal arrangement supports installation in low-voltage switchboards and distribution assemblies.
| Series | Tmax T7 |
|---|---|
| ABB order code | 1SDA062842R1 |
| Product type | Moulded case circuit breaker |
| Rated uninterrupted current (Iu) | 1000 A |
| Rated voltage | 690 V AC |
| Number of poles | 4 |
| Trip unit | PR231/P |
| Protection functions | LS/I |
| Ultimate short-circuit breaking capacity (Icu) | 200 kA at 220/230 V AC |
| Overload release adjustment range | 400–1000 A |
| Short-circuit release adjustment range | 1000–10000 A |
| Neutral protection settings | OFF / 50% / 100% |
| Earth-fault protection | Not integrated |
| Mounting type | Fixed |
| Terminal configuration | Front terminals |
| Operating mechanism | Manual lever |
| Motor drive | Not integrated |
| Dimensions (H × W × D) | approx. 268 × 235 × 154 mm |
| Weight | approx. 9.9 kg |
| ABB product group | 310511-T-Max T4 - T8 |
This moulded case circuit breaker is designed to protect high-current low-voltage distribution circuits against overload and short-circuit conditions in industrial and commercial electrical systems.
The ABB T7V 1000 1SDA062842R1 has a rated uninterrupted current of 1000 A, with adjustable overload protection from 400–1000 A.
The breaker has an ultimate short-circuit breaking capacity of 150 kA at 380/415 V AC, with voltage-dependent breaking capacities up to 200 kA at 220/230 V AC.
This model is equipped with the ABB PR231/P LS/I solid-state electronic release, providing adjustable overload and short-circuit protection for power distribution applications.
This version has a 4-pole configuration, making it suitable for three-phase distribution systems incorporating a neutral conductor.
ABB order code 1SDA062842R1 is a fixed-mounted circuit breaker with front terminals and a manual lever operating mechanism.
ABB Tmax moulded case circuit breakers are widely used by electrical engineers, panel builders and industrial operators for dependable circuit protection, power distribution and control in demanding low-voltage installations.