Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA062808R1 is a 1000 A three-pole SACE Tmax T7L fixed moulded case circuit breaker with front terminals, a PR332/P LSIRc electronic trip unit, residual-current protection and 120 kA ultimate breaking capacity at 380-415 V AC.
£9,244.07
The ABB 1SDA062808R1 is a high-performance three-pole moulded case circuit breaker (MCCB) from the ABB SACE Tmax T7 range, engineered for demanding low-voltage power distribution applications. Identified as T7L 1000 PR332/P LSIRc In=1000A 3P F F, it combines a 1000 A rated current with ABB's advanced PR332/P electronic trip unit and residual-current protection.
The PR332/P LSIRc electronic trip unit provides comprehensive protection against overload and short-circuit conditions together with Rc residual-current protection. The overload protection is adjustable from 0.4–1 × In, equivalent to 400–1000 A, while magnetic protection is adjustable from 1.5–15 × In. The residual-current function provides an additional protection range of 0.2–1 × In.
The 1SDA062808R1 is supplied as a three-pole fixed circuit breaker with front terminals and lever operating mechanism. Its T7L construction provides an ultimate short-circuit breaking capacity of 120 kA at 380–415 V AC, making it particularly suitable for industrial switchboards, main distribution assemblies and high-current feeder circuits where high fault interruption capability and residual-current protection are required.
The PR332/P LSIRc electronic trip unit combines adjustable overcurrent protection with residual-current monitoring. Its overload protection can be set between 400–1000 A, while the short-circuit protection range extends from 1500–15000 A. These adjustable settings allow the breaker protection characteristics to be coordinated with the electrical installation and other protective devices.
The additional Rc residual-current function detects current imbalance associated with leakage to earth and extends the protection provided by the breaker beyond conventional overcurrent protection. Combined with the T7L platform's 120 kA Icu at 380–415 V AC, this makes the ABB 1SDA062808R1 particularly suitable for high-current distribution systems requiring both substantial short-circuit interruption capability and residual-current protection.
| Series | SACE Tmax T7 |
|---|---|
| Order code / MPN | 1SDA062808R1 |
| Product group | 310511-T-Max T4 - T8 |
| Product type | Moulded case circuit breaker |
| Breaker designation | T7L 1000 |
| Frame size | T7 |
| Short-circuit performance level | L |
| Rated current (In) | 1000 A |
| Rated uninterrupted current (Iu) | 1000 A |
| Number of poles | 3 |
| Trip unit | PR332/P-LSIRc |
| Trip technology | Electronic / solid-state |
| Protection configuration | LSIRc |
| Overload adjustment | 0.4–1 × In |
| Overload release setting range | 400–1000 A |
| Short-circuit protection adjustment | 1.5–15 × In |
| Short-circuit release setting range | 1500–15000 A |
| Residual-current protection adjustment | 0.2–1 × In |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Ultimate breaking capacity (Icu) at 220–230 V AC | 200 kA |
| Ultimate breaking capacity (Icu) at 380–415 V AC | 120 kA |
| Ultimate breaking capacity (Icu) at 440 V AC | 100 kA |
| Ultimate breaking capacity (Icu) at 500 V AC | 85 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 50 kA |
| Service breaking capacity (Ics) at 380–415 V AC | 120 kA |
| Rated short-time withstand current (Icw) | 20 kA for 1 s |
| Installation type | Fixed |
| Terminal configuration | Front terminals |
| Operating mechanism | Lever operated |
| Power loss at rated operating conditions | 30 W per pole |
| Standards | IEC |
| EAN | 8015644653576 |
| Application | Low-voltage power distribution and residual-current protection |
The ABB 1SDA062808R1 is a 1000 A three-pole SACE Tmax T7L moulded case circuit breaker with a PR332/P LSIRc electronic trip unit, residual-current protection, fixed installation and front terminals.
The PR332/P LSIRc trip unit provides adjustable overload and short-circuit protection together with Rc residual-current protection, providing comprehensive protection for demanding low-voltage distribution circuits.
The T7L 1000 provides an ultimate short-circuit breaking capacity of 120 kA at 380–415 V AC. Its voltage-dependent Icu ratings also include 200 kA at 220–230 V AC, 100 kA at 440 V AC, 85 kA at 500 V AC and 50 kA at 690 V AC.
The overload protection is adjustable from 400–1000 A, the short-circuit protection from 1500–15000 A, and the residual-current function from 0.2–1 × In.
3P identifies the three-pole configuration, while F F identifies a fixed circuit breaker with front terminals for permanent installation within a compatible low-voltage switchboard or distribution assembly.
ABB SACE Tmax moulded case circuit breakers combine high short-circuit interruption performance with advanced electronic and residual-current protection, supporting dependable low-voltage power distribution across demanding industrial, commercial and infrastructure applications.
We use cookies