1SDA062720R1 ABB T7V 800 PR332/P LSIRc 800 A 4-Pole MCCB

1SDA062720R1 ABB T7V 800 PR332/P LSIRc 800 A 4-Pole MCCB

ABB 1SDA062720R1 is a SACE Tmax T7V 800 A four-pole fixed moulded case circuit breaker with front terminals, a PR332/P-LSIRc electronic trip unit and 150 kA ultimate breaking capacity at 380–415 V AC.

SKU: 1SDA062720R1MPN: 1SDA062720R1
Price
List Price £13,413.06 ex VAT
Your Price (ex VAT) Save 25%
£10,059.80 25% OFF
You save £3,353.27 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £10,059.80
Trade pricing is personalised to your account

Manufacturer Lead Time

£10,059.80

Why Choose the ABB T7V 800 1SDA062720R1 Circuit Breaker?

The ABB 1SDA062720R1 is a high-performance SACE Tmax T7V moulded case circuit breaker (MCCB) designed for protection and control of demanding low-voltage power distribution systems. Identified by ABB as T7V 800 PR332/P LSIRc In=800A 4p F F, it combines an 800 A rated uninterrupted current with the advanced PR332/P-LSIRc electronic trip unit and a four-pole fixed configuration.

The T7V performance level provides an ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC, making this breaker suitable for installations with very high prospective fault currents. Its PR332/P-LSIRc electronic trip unit combines adjustable overload, short-time and instantaneous short-circuit protection with residual-current protection capability for comprehensive circuit protection.

This configuration is a four-pole, fixed circuit breaker with front terminals and a manual lever operating mechanism. Rated at 800 A with an overload adjustment range of 320–800 A, the 1SDA062720R1 is particularly suitable for industrial switchboards, main distribution panels and three-phase four-wire systems requiring high breaking performance and residual-current protection.

Key Advantages

  • High-performance 800 A moulded case circuit breaker for demanding power distribution systems.
  • 150 kA ultimate breaking capacity at 380–415 V AC for very high prospective fault levels.
  • Advanced PR332/P-LSIRc electronic trip unit.
  • Combines overload, short-time, instantaneous and residual-current protection.
  • Four-pole configuration for three-phase four-wire distribution applications.
  • Fixed installation with front terminals for switchboard integration.

Key Features

  • ABB SACE Tmax T7V 800 series.
  • 800 A rated uninterrupted current.
  • 320–800 A overload adjustment range.
  • PR332/P-LSIRc electronic protection trip unit.
  • Long-time overload (L) protection.
  • Short-time short-circuit (S) protection.
  • Instantaneous short-circuit (I) protection.
  • Residual-current (Rc) protection capability.
  • 150 kA Icu at 380–415 V AC.
  • Four-pole (4P) construction.
  • Fixed (F) installation with front terminals (F).
  • Manual lever operating mechanism.

Comprehensive LSIRc Protection for Industrial Power Distribution

Moulded case circuit breakers such as the ABB SACE Tmax T7V protect electrical distribution systems against potentially damaging overload and short-circuit conditions. The 1SDA062720R1 combines an 800 A current rating with an ultimate breaking capacity of 150 kA at 380–415 V AC, providing robust interruption performance for installations with exceptionally high prospective fault currents.

The integrated PR332/P-LSIRc electronic trip unit adds residual-current protection capability to adjustable long-time, short-time and instantaneous protection. Combined with its four-pole construction, this makes the breaker particularly suitable for three-phase four-wire distribution systems where high-performance circuit protection, neutral switching and residual-current fault detection are required.

Typical Applications

  • Industrial low-voltage power distribution systems.
  • Main and sub-main electrical switchboards.
  • Three-phase four-wire distribution systems.
  • Manufacturing and process plant power systems.
  • High-current feeder and cable protection.
  • Distribution systems requiring residual-current protection capability.
  • OEM switchgear and electrical panel assemblies.

Technical Specifications

Series SACE Tmax T7
ABB order code 1SDA062720R1
Product type Moulded case circuit breaker (MCCB)
Frame / breaker size T7 800
Short-circuit performance level V
Rated uninterrupted current 800 A
Overload protection adjustment range 320–800 A
Rated voltage 690 V AC
Ultimate short-circuit breaking capacity (Icu) 200 kA at 220–230 V AC
Number of poles 4
Trip unit PR332/P-LSIRc electronic trip unit
Protection functions Long-time (L), short-time (S), instantaneous (I) and residual current (Rc)
Undelayed short-circuit adjustment range 1200–12000 A
Short-time delayed short-circuit adjustment range 480–8000 A
Residual-current adjustment 0.2–1 × In
Neutral protection settings OFF / 50% / 100% / 150% / 200%
Installation Fixed
Terminal configuration Front terminals
Main circuit connection Bolted connection
Operating mechanism Manual lever
Protection rating IP20
Dimensions (H × W × D) approx. 268 × 235 × 154 mm
Weight approx. 9.9 kg
GTIN / EAN 8015644652692
Application Power distribution protection and control
Product group 310511 – T-Max T4 - T8

Frequently Asked Questions

What is the ABB 1SDA062720R1 used for?

The ABB 1SDA062720R1 is an 800 A four-pole moulded case circuit breaker designed to protect and control low-voltage power distribution circuits against overload, short-circuit and residual-current fault conditions.

What breaking capacity does the ABB T7V 800 1SDA062720R1 provide?

The T7V configuration provides an ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC, with breaking capacity varying according to the system voltage.

Which trip unit is fitted to the ABB 1SDA062720R1?

The circuit breaker is equipped with an ABB PR332/P-LSIRc electronic trip unit, providing long-time overload, short-time short-circuit, instantaneous short-circuit and residual-current protection capability.

What is the current range of the ABB 1SDA062720R1?

The breaker has an 800 A rated uninterrupted current with overload protection adjustable across a range of 320–800 A.

What does LSIRc mean on the ABB PR332/P trip unit?

LSIRc identifies long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and residual-current (Rc) protection functions.

Trusted ABB Power Distribution Protection

ABB SACE Tmax moulded case circuit breakers combine high interruption performance with advanced electronic protection functions, providing dependable protection and control for demanding industrial and commercial power distribution systems.