1SDA060576R1 ABB Tmax T6L 1000A PR222DS/P-LSI 3-Pole Circuit Breaker

1SDA060576R1 ABB Tmax T6L 1000A PR222DS/P-LSI 3-Pole Circuit Breaker

ABB 1SDA060576R1 is a fixed three-pole Tmax T6L 1000 A moulded-case circuit breaker with front terminals, 100 kA breaking capacity at 380/415 V AC and a PR222DS/P-LSI electronic trip unit for adjustable LSI protection.

SKU: 1SDA060576R1MPN: 1SDA060576R1
Price
List Price £11,101.43 ex VAT
Your Price (ex VAT) Save 25%
£8,326.07 25% OFF
You save £2,775.36 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £8,326.07
Trade pricing is personalised to your account

Manufacturer Lead Time

£8,326.07

Why Choose the ABB 1SDA060576R1 Tmax T6L 1000 Circuit Breaker?

The ABB 1SDA060576R1 is a high-performance Tmax T6L moulded-case circuit breaker (MCCB) designed for protection and switching in demanding low-voltage power distribution systems. Configured as a three-pole fixed circuit breaker with front terminals, it combines a rated uninterrupted current of 1000 A with the advanced PR222DS/P-LSI electronic trip unit.

As part of the ABB SACE Tmax T6 series, the T6L 1000 provides high breaking performance together with adjustable electronic protection. The PR222DS/P-LSI trip unit provides long-time overload, short-time short-circuit and instantaneous short-circuit protection (LSI), allowing the breaker protection characteristics to be coordinated with the requirements of the electrical distribution system.

With a rated operating voltage of up to 690 V AC and an ultimate short-circuit breaking capacity of 100 kA at 380/415 V AC, the 1SDA060576R1 is suitable for high-current industrial feeders and distribution circuits. Its fixed mounting arrangement, front bolted terminals and electronic protection make it well suited to industrial switchboards, infrastructure and commercial power distribution.

Key Advantages

  • High-capacity 1000 A Tmax T6L moulded-case circuit breaker.
  • PR222DS/P-LSI electronic trip unit provides LSI protection functions.
  • 100 kA ultimate breaking capacity at 380/415 V AC.
  • Three-pole fixed configuration with front terminals.
  • Adjustable overload protection from 400–1000 A.
  • Short-time and instantaneous short-circuit protection supports selective power distribution design.

Key Features

  • ABB SACE Tmax T6L 1000 circuit breaker.
  • 1000 A rated uninterrupted current.
  • Three-pole configuration.
  • PR222DS/P-LSI solid-state electronic trip unit.
  • Long-time, short-time and instantaneous (LSI) protection functions.
  • 400–1000 A overload release adjustment range.
  • 600–7600 A short-time delayed short-circuit adjustment range.
  • 1500–10500 A instantaneous short-circuit adjustment range.
  • Rated operating voltage up to 690 V AC.
  • 100 kA Icu at 380/415 V AC.
  • Fixed mounting with front bolted terminals.
  • IP20 protection rating.

Advanced LSI Protection for High-Current Power Distribution

Electronic moulded-case circuit breakers protect electrical distribution systems against overloads and short circuits while allowing protection characteristics to be coordinated with downstream and upstream devices. LSI protection combines long-time overload protection with short-time delayed and instantaneous short-circuit protection, providing greater flexibility than a basic fixed protection arrangement.

The ABB 1SDA060576R1 combines the high breaking performance of the Tmax T6L platform with the configurable PR222DS/P-LSI electronic trip unit. Its adjustable protection thresholds allow the breaker to be matched to high-current distribution circuits while supporting selectivity and dependable fault interruption within industrial electrical systems.

Typical Applications

  • Industrial low-voltage power distribution.
  • Main and sub-main electrical feeders.
  • High-current switchboards and distribution panels.
  • Manufacturing and process plant electrical systems.
  • Commercial and infrastructure power distribution.
  • Applications requiring adjustable LSI circuit protection.

Technical Specifications

Series SACE Tmax T6
Order code 1SDA060576R1
Product type Moulded-case circuit breaker (MCCB)
Breaker designation T6L 1000
Rated uninterrupted current (Iu) 1000 A
Number of poles 3
Trip unit PR222DS/P-LSI electronic
Protection functions LSI – long-time, short-time and instantaneous
Overload release adjustment range 400–1000 A
Short-time delayed short-circuit adjustment range 600–7600 A
Instantaneous short-circuit adjustment range 1500–10500 A
Rated operating voltage up to 690 V AC
Ultimate breaking capacity (Icu) at 220/230 V AC 200 kA
Ultimate breaking capacity (Icu) at 380/415 V AC 100 kA
Ultimate breaking capacity (Icu) at 440 V AC 80 kA
Ultimate breaking capacity (Icu) at 500 V AC 65 kA
Ultimate breaking capacity (Icu) at 690 V AC 30 kA
Mounting type Fixed
Main connection position Front
Main-circuit connection Bolted connection
Operating mechanism Toggle
Protection rating IP20
Motor operator Optional
Electrical durability 4000 cycles at up to 60 cycles per hour
Mechanical durability 20000 cycles at up to 120 cycles per hour
Dimensions (H × W × D) 268 × 210 × 103.5 mm
Net weight 9.5 kg
EAN / GTIN 8015644630355
ABB product group 310511-T-Max T4 - T8

Frequently Asked Questions

What is the ABB 1SDA060576R1 used for?

The ABB 1SDA060576R1 is a 1000 A moulded-case circuit breaker used for overload and short-circuit protection in high-current industrial and commercial low-voltage power distribution systems.

What trip unit is fitted to the ABB 1SDA060576R1?

The breaker is fitted with an ABB PR222DS/P-LSI electronic trip unit, providing long-time overload, short-time short-circuit and instantaneous short-circuit protection.

What is the breaking capacity of the ABB 1SDA060576R1?

The T6L 1000 has an ultimate short-circuit breaking capacity of 100 kA at 380/415 V AC, with voltage-dependent Icu ratings extending from 200 kA at 220/230 V AC to 30 kA at 690 V AC.

What is the current adjustment range of the PR222DS/P-LSI trip unit?

The overload release can be adjusted from 400–1000 A, while the trip unit also provides adjustable short-time and instantaneous short-circuit protection.

Is the ABB 1SDA060576R1 fixed or withdrawable?

The 1SDA060576R1 is a fixed three-pole circuit breaker with front bolted terminals, designed for permanent installation within compatible electrical switchboards and distribution panels.

Trusted ABB Circuit Protection

ABB SACE Tmax moulded-case circuit breakers combine high breaking performance with configurable electronic protection, providing dependable overload and short-circuit protection for demanding industrial and commercial low-voltage distribution systems.