ABB 1SDA060355R1 is a 630 A three-pole PR222DS/PD-LSI solid-state electronic trip unit for compatible SACE Tmax T6 630 circuit breakers, providing long-time, short-time and instantaneous protection with communication capability.
£3,273.50
The ABB 1SDA060355R1 is a PR222DS/PD-LSI three-pole electronic trip unit designed for compatible ABB SACE Tmax T6 630 moulded-case circuit breakers. Rated at 630 A, it provides configurable electronic protection for demanding industrial and commercial low-voltage power distribution applications.
The PR222DS/PD-LSI provides long-time, short-time and instantaneous protection functions, enabling the associated Tmax T6 circuit breaker to respond to overload and short-circuit conditions. Its electronic design allows protection settings to be coordinated more precisely with conductors, loads and other protective devices than conventional fixed protection arrangements.
The PD version adds communication capability to the PR222DS platform, making this release suitable for installations where circuit protection is integrated with supervision, monitoring or communication systems. The unit is designed specifically for a three-pole T6 630 breaker configuration and has a rated current of 630 A.
An electronic trip unit continuously evaluates current conditions through the associated circuit breaker and initiates tripping when configured protection thresholds are exceeded. The LSI functions provide long-time protection against sustained overloads, short-time protection for coordinated short-circuit conditions and instantaneous protection for severe faults requiring rapid interruption.
The PR222DS/PD version combines these protection functions with communication capability, allowing the protection system to form part of a compatible supervisory or power-management architecture. This makes the 1SDA060355R1 particularly suitable for Tmax T6 630 installations requiring both configurable electronic protection and communication functionality.
| Series | SACE Tmax T / Tmax T4–T8 |
|---|---|
| Order code | 1SDA060355R1 |
| Product type | Solid-state electronic trip unit / protection release |
| Compatible breaker frame | Tmax T6 |
| Compatible breaker rating | T6 630 |
| Rated current (In) | 630 A |
| Number of poles | 3 |
| Application | AC power circuit breaker |
| Protection functions | Long-time, short-time and instantaneous (LSI) |
| Instantaneous short-circuit release setting range | 945–7560 A |
| Communication capability | Yes, PD communication version |
| Rated control supply voltage | 24 V DC |
| Actuating voltage type | DC |
| Suitable for power circuit breakers | Yes |
| Suitable for load switches | No |
| Suitable for motor-protection circuit breakers | No |
| EAN | 8015644628239 |
| Country of origin | Italy |
| ABB product group | 310511-T-Max T4 - T8 |
The ABB 1SDA060355R1 is a PR222DS/PD-LSI three-pole solid-state electronic trip unit rated at 630 A for compatible ABB SACE Tmax T6 630 moulded-case circuit breakers.
LSI denotes long-time (L), short-time (S) and instantaneous (I) protection, providing electronic protection against sustained overloads and different levels of short-circuit fault.
The PR222DS/PD-LSI 1SDA060355R1 has a rated current of 630 A and is designed for the ABB Tmax T6 630 breaker platform.
The instantaneous short-circuit release can be adjusted over a range of 945–7560 A, allowing the protection characteristics to be coordinated with the requirements of the electrical distribution system.
The PR222DS/PD is the communication-enabled version of the PR222DS electronic protection platform, combining LSI protection with communication functionality for compatible ABB circuit-breaker supervision and power-management systems.
ABB SACE Tmax electronic releases provide configurable protection for demanding low-voltage distribution systems, with the PR222DS/PD-LSI combining 630 A T6 protection, LSI fault functions and communication capability for integrated industrial power-management applications.