ABB 1SDA059403R1 E3S1000 is a 1000 A four-pole fixed SACE Emax air circuit breaker with rear horizontal terminals and a PR122/P-LSI R1000 electronic trip unit providing long-time, short-time and instantaneous overcurrent protection.
£10,699.97
The ABB E3S1000 PR122/P-LSI, order code 1SDA059403R1, is a high-performance 1000 A four-pole fixed air circuit breaker designed for switching and protecting demanding low-voltage power distribution systems. As part of the proven ABB SACE Emax E3S series, it combines robust high-current switching capability with advanced electronic overcurrent protection for industrial, commercial and infrastructure switchgear.
This Emax circuit breaker is equipped with the PR122/P-LSI R1000 electronic trip unit, providing long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection. The electronic release provides adjustable protection characteristics to help safeguard cables, busbars, transformers, switchgear and connected equipment while supporting selective and coordinated protection throughout the electrical distribution system.
With a rated uninterrupted current of 1000 A, rated operational voltage of 690 V AC and rated ultimate and service short-circuit breaking capacities of 75 kA throughout its specified AC voltage range, the E3S1000 is engineered for demanding distribution duties. This model features a four-pole fixed construction with rear horizontal terminals and is fitted with four auxiliary contacts plus circuit-breaker open/closed position indication.
Air circuit breakers such as the ABB SACE Emax E3S are designed to switch and protect high-current low-voltage distribution circuits. The PR122/P electronic trip unit monitors circuit current and initiates breaker operation when configured protection thresholds are exceeded, helping safeguard cables, busbars, transformers, switchgear and connected equipment against damaging overload and short-circuit conditions.
The PR122/P-LSI release combines long-time, short-time and instantaneous protection with the substantial short-circuit capability of the E3S frame. Combined with its four-pole fixed construction and rear horizontal terminals, the E3S1000 is particularly well suited to main and feeder protection where neutral switching, coordinated electronic protection and dependable high-current operation are required.
| Series | SACE Emax |
|---|---|
| ABB order code | 1SDA059403R1 |
| EAN | 8015644617646 |
| Product group | 310513-New Emax |
| HS code | 85362090 |
| Product type | Air circuit breaker |
| Frame / subtype | E3 |
| Short-circuit performance level | S |
| Rated current (In) | 1000 A |
| Rated uninterrupted current (Iu) | 1000 A |
| Rated operational current (Ie) | 1000 A |
| Number of poles | 4 |
| Current type | AC |
| Rated operational voltage | 690 V AC |
| Rated voltage (Ur) | 690 V |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Trip unit | PR122/P-LSI R1000 |
| Release type | Electronic |
| Protection functions | L (long-time overload), S (short-time short-circuit) and I (instantaneous short-circuit) |
| Rated ultimate short-circuit breaking capacity (Icu) | 75 kA at 220–690 V AC |
| Rated service short-circuit breaking capacity (Ics) | 75 kA at 220–690 V AC |
| Rated short-time withstand current (Icw) | 75 kA for 1 s; 65 kA for 3 s |
| Version | Fixed |
| Terminal arrangement | Rear horizontal terminals |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Power loss | 38.4 W |
| Mechanical durability | 20,000 operating cycles |
| Mechanical operating frequency | 60 cycles per hour |
| Electrical durability | 12,000 operating cycles at ≤440 V; 12,000 operating cycles at 500–690 V |
| Electrical operating frequency | 20 cycles per hour |
| Net weight | 90 kg |
| Standard | IEC |
The ABB 1SDA059403R1 is a 1000 A four-pole SACE Emax air circuit breaker designed for switching and protecting demanding high-current low-voltage electrical distribution circuits.
This circuit breaker is equipped with the ABB PR122/P-LSI R1000 electronic trip unit, providing long-time overload, short-time short-circuit and instantaneous short-circuit protection.
The E3S1000 1SDA059403R1 provides rated ultimate and service short-circuit breaking capacities of 75 kA throughout the specified 220–690 V AC range.
The 1SDA059403R1 is a fixed four-pole air circuit breaker fitted with rear horizontal terminals for permanent installation in compatible ABB SACE Emax low-voltage switchgear.
LSI denotes long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection, providing coordinated electronic protection against overloads and short-circuit faults.
ABB SACE Emax air circuit breakers are engineered for dependable low-voltage power distribution, combining high short-circuit performance, advanced electronic protection and robust fixed construction for demanding industrial and commercial switchgear.