Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA059272R1 E2N1000 is a 1000 A four-pole withdrawable SACE Emax air circuit breaker moving part with a PR122/P-LI R1000 electronic trip unit for overload and instantaneous short-circuit protection.
£9,725.75
The ABB E2N1000 PR122/P-LI, order code 1SDA059272R1, is a high-performance 1000 A four-pole withdrawable air circuit breaker moving part designed for switching and protecting demanding low-voltage power distribution systems. As part of the proven ABB SACE Emax E2N series, it combines robust high-current switching capability with advanced electronic overcurrent protection for industrial, commercial and infrastructure switchgear.
This Emax circuit breaker is equipped with the PR122/P-LI R1000 electronic trip unit, providing long-time overload (L) and instantaneous short-circuit (I) protection. Its electronic release enables accurate circuit protection, while the E2N performance level provides substantial short-circuit interruption capability for installations with high prospective fault currents.
With a rated uninterrupted current of 1000 A and a rated operational voltage of up to 690 V AC, the E2N1000 is suitable for demanding distribution applications. This model is supplied as the four-pole moving part of a withdrawable circuit breaker and includes four auxiliary contacts with open/closed position indication, supporting efficient maintenance and integration into compatible SACE Emax switchgear.
Air circuit breakers such as the ABB SACE Emax E2N are designed to switch and protect high-current low-voltage distribution circuits. The electronic trip unit monitors circuit current and initiates breaker operation when configured protection thresholds are exceeded, helping safeguard cables, busbars, switchgear and connected equipment against damaging overload and short-circuit conditions.
The PR122/P-LI release provides long-time and instantaneous protection, while the E2N performance level delivers substantial fault interruption capability. Combined with its four-pole withdrawable construction, the E2N1000 is particularly well suited to installations where dependable high-current protection, neutral switching and straightforward switchgear maintenance are required.
| Series | SACE Emax |
|---|---|
| ABB order code | 1SDA059272R1 |
| EAN | 8015644616335 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker moving part |
| Frame / subtype | E2 |
| Short-circuit performance level | N |
| Rated current (In) | 1000 A |
| Rated uninterrupted current (Iu) | 1000 A |
| Rated operational current (Ie) | 1000 A |
| Number of poles | 4 |
| Current type | AC |
| Rated operational voltage | 690 V AC |
| Rated voltage (Ur) | 690 V |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Trip unit | PR122/P-LI R1000 |
| Release type | Electronic |
| Protection functions | L (overload) and I (instantaneous short-circuit) |
| Instantaneous short-circuit release adjustment range | 1500–15000 A |
| Rated ultimate short-circuit breaking capacity (Icu) | 65 kA at 220–440 V AC; 55 kA at 500–690 V AC |
| Rated service short-circuit breaking capacity (Ics) | 65 kA at 220–440 V AC; 55 kA at 500–690 V AC |
| Rated short-time withstand current (Icw) | 55 kA for 1 s; 42 kA for 3 s |
| Version | Withdrawable moving part |
| Auxiliary contacts | 4 for circuit-breaker open/closed position indication |
| Power loss | 83.2 W |
| Mechanical durability | 25,000 operating cycles |
| Electrical durability | 15,000 operating cycles |
| Dimensions (W × H × D) | 414 × 461 × 396.5 mm |
| Net weight | 61 kg |
| Protection rating | IP2X |
| Standard | IEC |
The ABB 1SDA059272R1 is a 1000 A four-pole SACE Emax air circuit breaker moving part designed for switching and protecting high-current low-voltage electrical distribution circuits.
This circuit breaker is equipped with the ABB PR122/P-LI R1000 electronic trip unit, providing long-time overload and instantaneous short-circuit protection.
The E2N1000 provides rated ultimate and service short-circuit breaking capacities of 65 kA at 400/415 V AC and 55 kA at 500–690 V AC.
The 1SDA059272R1 is the moving part of a withdrawable four-pole circuit breaker, designed for use with the appropriate compatible SACE Emax fixed part.
The circuit breaker moving part includes four auxiliary contacts with circuit-breaker open and closed position indication for switchboard monitoring and control.
ABB SACE Emax air circuit breakers are engineered for dependable low-voltage power distribution, combining robust switching performance, advanced electronic circuit protection and service-friendly withdrawable construction for demanding industrial and commercial switchgear.