Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA059215R1 is a SACE Emax E1N 1000 A four-pole fixed air circuit breaker with rear horizontal terminals and a PR121/P-LI R1000 electronic release providing long-time overload and instantaneous short-circuit protection.
£9,251.05
The ABB 1SDA059215R1 is a SACE Emax E1N 1000 air circuit breaker designed for dependable protection and switching in industrial low-voltage power-distribution systems. This four-pole fixed version is rated at 1000 A and is equipped with ABB's PR121/P-LI R1000 electronic overcurrent release.
The PR121/P-LI provides long-time (L) overload and instantaneous (I) short-circuit protection. Its adjustable overload setting covers 400–1000 A, while the instantaneous short-circuit setting covers 1500–15000 A, allowing the breaker protection to be coordinated with the requirements of the connected distribution system.
The 1SDA059215R1 combines its E1N performance level with a rated ultimate short-circuit breaking capacity of 50 kA at 400 V AC. Its fixed construction uses rear horizontal terminals, while four auxiliary changeover contacts and open/closed indication support integration into switchboard signalling and control systems.
The ABB PR121/P-LI electronic release provides two fundamental protection functions for industrial distribution circuits. Long-time protection responds to sustained overload conditions, while instantaneous protection provides rapid tripping when severe short-circuit currents occur, helping protect conductors and connected equipment against damaging fault energy.
Combined with the E1N breaker's 1000 A current rating, 50 kA ultimate breaking capacity at 400 V AC and four-pole fixed construction, the 1SDA059215R1 provides a robust solution for switchboards requiring adjustable electronic protection, substantial fault-interruption capability and permanent rear-connected installation.
| Series | SACE Emax |
|---|---|
| ABB order code | 1SDA059215R1 |
| Extended product type | E1N1000PR121/P-LIIn=1000A4pFHR |
| Product type | Air circuit breaker |
| Frame | E1 |
| Performance level | N |
| Rated current (In) | 1000 A |
| Rated uninterrupted current (Iu) | 1000 A |
| Rated voltage | 690 V AC |
| Number of poles | 4 |
| Release | PR121/P-LI R1000 |
| Release type | Electronic overcurrent release |
| Protection functions | L, I |
| Overload release adjustment range | 400–1000 A |
| Instantaneous short-circuit release adjustment range | 1500–15000 A |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC | 50 kA |
| Integrated earth-fault protection | No |
| Installation | Fixed |
| Main terminal position | Rear |
| Terminal orientation | Horizontal rear (HR) |
| Main-circuit connection | Bolted connection |
| Auxiliary contacts | 4 changeover contacts |
| Position indication | Circuit breaker open / closed |
| Motor drive | Optional |
| Net weight | 62 kg |
| EAN | 8015644615765 |
The ABB 1SDA059215R1 is a SACE Emax E1N 1000 A four-pole fixed air circuit breaker with rear horizontal terminals and a PR121/P-LI R1000 electronic overcurrent release.
The PR121/P-LI provides long-time overload protection and instantaneous short-circuit protection, identified as LI protection.
The E1N breaker has a rated ultimate short-circuit breaking capacity of 50 kA at 400 V AC.
The 1SDA059215R1 is a fixed air circuit breaker with rear horizontal main terminals for permanent installation in compatible switchgear.
No. The fitted PR121/P-LI release provides long-time and instantaneous overcurrent protection; integrated earth-fault protection is not included in this LI configuration.
ABB SACE Emax air circuit breakers combine high-current switching, adjustable electronic protection and robust switchboard integration to provide dependable protection for demanding industrial low-voltage distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.