Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA058948R1 is a SACE Emax E2N/MS 1250 A four-pole fixed switch-disconnector with rear flat horizontal terminals for reliable switching and isolation in low-voltage power distribution systems.
£8,096.51
The ABB E2N/MS 1250, order code 1SDA058948R1, is a SACE Emax switch-disconnector designed for dependable switching and isolation in low-voltage power distribution systems. It combines a 1250 A rated uninterrupted current with four-pole construction, fixed installation and rear flat horizontal terminals.
As part of the ABB SACE Emax E2N/MS series, this device provides switching and isolation rather than integral electronic overcurrent protection. Its N short-circuit performance level and robust Emax construction make it suitable for industrial, commercial and infrastructure switchboards where circuit protection is coordinated separately.
The E2N/MS 1250 4P F HR configuration is rated for operation up to 690 V AC and provides a rated short-time withstand current of 55 kA for 1 s. Its four-pole fixed construction and horizontal rear terminals provide a practical arrangement for permanent switchboard installations requiring switching of three phases and neutral.
Switch-disconnectors provide controlled switching and isolation of electrical circuits, allowing downstream equipment to be separated from the electrical supply for operation, inspection or maintenance. The ABB E2N/MS 1250 combines this function with the proven SACE Emax platform and substantial short-time current withstand capability for demanding low-voltage installations.
Its four-pole construction allows simultaneous switching of three phases and neutral where required by the system design. Fixed installation and horizontal rear terminals make the E2N/MS 1250 particularly suitable for permanent switchboard applications using rear busbar connections.
| Series | SACE Emax |
|---|---|
| Order code | 1SDA058948R1 |
| Product type | Switch-disconnector |
| Frame / sub-type | E2 |
| Short-circuit performance level | N |
| Rated current (In) | 1250 A |
| Rated operational current (Ie) | 1250 A |
| Rated uninterrupted current (Iu) | 1250 A |
| Number of poles | 4P |
| Current type | AC |
| Rated operational voltage | 690 V AC / 250 V DC |
| Rated voltage (Ur) | 690 V |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated short-time withstand current (Icw) | 55 kA for 1 s / 42 kA for 3 s |
| Installation | Fixed (F) |
| Terminal arrangement | Rear flat horizontal (HR) |
| Power loss | 70 W |
| Electrical durability | 15,000 cycles |
| Mechanical durability | 25,000 cycles |
| Standard | IEC |
| Dimensions (W × H × D) | 386 × 418 × 302 mm |
| Product net weight | 56 kg |
| EAN | 8015644613075 |
It is an ABB SACE Emax E2N/MS 1250 switch-disconnector with a 1250 A rated uninterrupted current, four poles, fixed installation and rear flat horizontal terminals.
The switch-disconnector has a rated uninterrupted current of 1250 A.
This model has a four-pole (4P) configuration, making it suitable for systems requiring simultaneous switching of three phases and neutral.
The device has a rated short-time withstand current of 55 kA for 1 s and 42 kA for 3 s.
The switch-disconnector uses rear flat horizontal (HR) terminals and is a fixed version intended for permanent installation in compatible low-voltage switchboards.
ABB SACE Emax switch-disconnectors provide dependable high-current switching and isolation for low-voltage power distribution, combining robust electrical performance with practical configurations for industrial, commercial and infrastructure switchgear.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.