1SDA057463R1 ABB E3S-A 1600 PR121/P-LI 1600 A 3-Pole Fixed Air Circuit Breaker

1SDA057463R1 ABB E3S-A 1600 PR121/P-LI 1600 A 3-Pole Fixed Air Circuit Breaker

ABB 1SDA057463R1 is a SACE Emax E3S-A three-pole fixed air circuit breaker rated at 1600 A with horizontal rear terminals, 65 kA short-circuit capability at 480 V and a PR121/P-LI electronic release providing long-time and instantaneous protection.

SKU: 1SDA057463R1MPN: 1SDA057463R1
Price
List Price £10,085.45 ex VAT
Your Price (ex VAT) Save 25%
£7,564.09 25% OFF
You save £2,521.36 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £7,564.09
Trade pricing is personalised to your account

Manufacturer Lead Time

£7,564.09

Why Choose the ABB 1SDA057463R1 E3S-A 1600 Air Circuit Breaker?

The ABB 1SDA057463R1 is a SACE Emax E3S-A air circuit breaker designed for switching and protection in demanding low-voltage power distribution systems. Identified as E3S-A 1600 PR121/P-LI In=1600A 3p F HR, this three-pole fixed breaker combines a 1600 A rated current with the ABB PR121/P-LI electronic overcurrent release.

As part of the ABB SACE Emax E3 platform, the E3S-A provides high short-circuit performance for industrial, commercial and infrastructure distribution applications. This version uses a fixed construction with horizontal rear terminals and has a short-circuit current rating of 65 kA at 480 V, making it suitable for installations where substantial fault-current capability is required.

The integrated PR121/P-LI electronic trip unit provides long-time overload and instantaneous short-circuit protection. The breaker is equipped with an R1600 overcurrent release, an Im 24000 A instantaneous reference, four auxiliary contacts and open/closed breaker position indication for integration with switchboard control and status-monitoring systems.

Key Advantages

  • Genuine ABB SACE Emax E3S-A air circuit breaker.
  • 1600 A rated current for substantial low-voltage distribution loads.
  • PR121/P-LI electronic overcurrent release for overload and short-circuit protection.
  • LI protection provides long-time and instantaneous protection functions.
  • 65 kA short-circuit current rating at 480 V.
  • Three-pole fixed configuration for three-phase electrical distribution systems.
  • Horizontal rear terminals for permanent switchgear installation.
  • Four auxiliary contacts and open/closed position indication support monitoring and control integration.

Key Features

  • ABB SACE Emax E3S-A 1600 air circuit breaker platform.
  • 1600 A rated current.
  • Three-pole configuration.
  • Fixed circuit breaker construction.
  • Horizontal rear terminals.
  • PR121/P-LI electronic overcurrent release.
  • Long-time overload protection.
  • Instantaneous short-circuit protection.
  • R1600 overcurrent release rating.
  • Im 24000 A instantaneous reference.
  • 65 kA short-circuit current rating at 480 V.
  • 65 kA short-time current rating.
  • Four auxiliary contacts.
  • Circuit breaker open/closed position indication.
  • UL-oriented configuration for applicable low-voltage power distribution installations.

LI Electronic Protection for High-Current Power Distribution

Air circuit breakers such as the ABB SACE Emax E3S-A are used to switch and protect substantial low-voltage electrical loads. The E3S-A performance level combines a 1600 A frame size with 65 kA short-circuit capability at 480 V, providing robust protection for switchboards serving industrial equipment, transformers, generators and other high-current distribution loads.

The PR121/P-LI release provides two principal overcurrent protection functions. Long-time protection responds to sustained overload conditions, while instantaneous protection provides rapid interruption during severe short-circuit events. This combination provides straightforward electronic protection for applications where long-time overload and instantaneous fault protection are required without additional short-time or ground-fault functions in the trip unit.

Typical Applications

  • Main low-voltage distribution switchboards.
  • Industrial power distribution systems.
  • Manufacturing and process facilities.
  • Commercial building electrical distribution.
  • Infrastructure power systems.
  • Transformer secondary distribution.
  • Generator distribution and protection systems.
  • Switchgear requiring a 1600 A three-pole fixed air circuit breaker with LI electronic protection and high short-circuit performance.

Technical Specifications

Product group 310513-New Emax
Series SACE Emax
ABB order code 1SDA057463R1
Product type Air circuit breaker
Frame E3
Performance level S-A
Frame size 1600 A
Rated current (In) 1600 A
Overcurrent release rating R1600
Instantaneous reference Im 24000 A
Number of poles 3
Execution Fixed
Terminal arrangement Horizontal rear
Trip unit PR121/P-LI electronic overcurrent release
Protection functions Long-time and instantaneous
Long-time protection L
Instantaneous protection I
Short-circuit current at 480 V 65 kA
Short-time current 65 kA
Auxiliary contacts 4
Position indication Circuit breaker open / closed
Current type AC
Release type Electronic
Configuration UL
Net weight 60 kg
EAN 8015644597269
HS code 85362090

Frequently Asked Questions

What is the ABB 1SDA057463R1 used for?

The ABB 1SDA057463R1 is a 1600 A three-pole SACE Emax E3S-A air circuit breaker used for switching and protecting demanding low-voltage electrical distribution systems against overload and short-circuit conditions.

What is the rated current of the ABB 1SDA057463R1?

The breaker has a rated current of 1600 A and uses an R1600 electronic overcurrent release configuration.

Which trip unit is fitted to the ABB 1SDA057463R1?

The 1SDA057463R1 is fitted with an ABB PR121/P-LI electronic overcurrent release, providing long-time overload and instantaneous short-circuit protection.

Is the ABB 1SDA057463R1 fixed or withdrawable?

This model is a three-pole fixed air circuit breaker with horizontal rear terminals for permanent installation within compatible SACE Emax low-voltage switchgear.

What is the short-circuit capability of the ABB E3S-A 1600?

The E3S-A 1600 configuration has a 65 kA short-circuit current rating at 480 V and a 65 kA short-time current rating, providing strong fault-current performance for demanding distribution applications.

Trusted Low-Voltage Circuit Protection from ABB

ABB SACE Emax air circuit breakers provide dependable switching and electronic overcurrent protection for demanding low-voltage power distribution systems, combining robust breaker construction, high short-circuit performance and configurable protection functions for industrial, commercial and infrastructure applications.