1SDA057154R1 ABB E6V 6300 PR121/P-LSIG 6300A 3P Withdrawable Air Circuit Breaker

1SDA057154R1 ABB E6V 6300 PR121/P-LSIG 6300A 3P Withdrawable Air Circuit Breaker

ABB 1SDA057154R1 is a SACE Emax E6V 6300 A three-pole withdrawable air circuit breaker moving part with a PR121/P-LSIG R6300 electronic release providing long-time, short-time, instantaneous and earth-fault protection.

SKU: 1SDA057154R1MPN: 1SDA057154R1
Price
List Price £107,391.50 ex VAT
Your Price (ex VAT) Save 25%
£80,543.63 25% OFF
You save £26,847.88 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £80,543.63
Trade pricing is personalised to your account

Manufacturer Lead Time

£80,543.63

Why Choose the ABB E6V 6300 PR121/P-LSIG 6300A 3P Withdrawable Air Circuit Breaker?

The ABB 1SDA057154R1 is a high-performance SACE Emax E6V air circuit breaker moving part engineered for protection and switching in demanding high-current low-voltage power distribution systems. Rated at 6300 A, this three-pole withdrawable breaker incorporates an ABB PR121/P-LSIG R6300 electronic overcurrent release providing long-time overload, short-time delayed, instantaneous short-circuit and earth-fault protection.

As part of the proven ABB SACE Emax series, the E6V 6300 combines very high current-carrying capability with exceptional fault interruption performance. Its withdrawable moving-part construction is designed for use with the corresponding Emax fixed part, allowing isolation and removal of the circuit breaker for inspection, servicing or replacement in critical switchboard installations.

With a rated operational voltage of 690 V AC, an ultimate short-circuit breaking capacity of 150 kA at 415 V AC and 100 kA at 690 V AC, the E6V delivers robust protection where substantial prospective fault currents are present. Its 100 kA short-time withstand current for 1 s further supports selective protection and coordination in high-capacity distribution networks.

Key Advantages

  • High-current 6300 A SACE Emax air circuit breaker moving part.
  • Three-pole configuration for high-capacity three-phase electrical networks.
  • PR121/P-LSIG R6300 electronic overcurrent release.
  • LSIG functionality provides long-time, short-time, instantaneous and earth-fault protection.
  • 150 kA ultimate breaking capacity at 415 V AC.
  • 100 kA ultimate breaking capacity at 690 V AC.
  • 100 kA short-time withstand current for 1 s.
  • Withdrawable construction supports efficient inspection, maintenance and replacement.

Key Features

  • ABB SACE Emax E6V air circuit breaker platform.
  • 6300 A rated uninterrupted current.
  • Three-pole configuration.
  • Withdrawable moving-part execution.
  • PR121/P-LSIG R6300 electronic overcurrent release.
  • Long-time overload protection.
  • Short-time delayed short-circuit protection.
  • Instantaneous short-circuit protection.
  • Integrated earth-fault protection.
  • 690 V AC rated operational voltage.
  • Four auxiliary contacts.
  • Open/closed circuit-breaker position indication.

Comprehensive Protection for High-Current Power Distribution

Air circuit breakers such as the ABB SACE Emax E6V provide switching and comprehensive overcurrent protection for major low-voltage distribution circuits. The electronic trip unit monitors current conditions and initiates circuit-breaker operation when configured overload, short-circuit or earth-fault thresholds are exceeded, helping protect busbars, cables, transformers and connected electrical equipment.

The PR121/P-LSIG release combines long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection with the exceptional fault-interruption capability of the E6V frame. Its 6300 A rating, 150 kA Icu at 415 V AC and withdrawable construction make this breaker particularly suitable for critical high-capacity distribution systems requiring comprehensive protection and maintainability.

Typical Applications

  • Main incoming circuit breakers in high-current low-voltage switchboards.
  • Industrial power distribution systems.
  • High-capacity feeder protection.
  • Transformer secondary protection and switching.
  • Manufacturing and process plants.
  • Commercial and infrastructure power distribution.
  • Generator and utility distribution systems.
  • Switchboards requiring withdrawable 6300 A breakers with comprehensive LSIG protection.

Technical Specifications

Series SACE Emax
Frame / type E6V
ABB order code 1SDA057154R1
EAN 8015644584948
Product type Air circuit breaker moving part
Execution Withdrawable
Number of poles 3
Rated current (In) 6300 A
Rated uninterrupted current (Iu) 6300 A
Rated operational current (Ie) 6300 A
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Trip unit PR121/P-LSIG R6300
Release type Electronic overcurrent release
Protection functions LSIG – long-time, short-time, instantaneous and earth-fault
Ultimate short-circuit breaking capacity (Icu) at 400 V AC 150 kA
Ultimate short-circuit breaking capacity (Icu) at 415 V AC 150 kA
Ultimate short-circuit breaking capacity (Icu) at 440 V AC 150 kA
Ultimate short-circuit breaking capacity (Icu) at 500 V AC 130 kA
Ultimate short-circuit breaking capacity (Icu) at 690 V AC 100 kA
Service short-circuit breaking capacity (Ics) at 400 V AC 150 kA
Service short-circuit breaking capacity (Ics) at 415 V AC 150 kA
Service short-circuit breaking capacity (Ics) at 440 V AC 125 kA
Service short-circuit breaking capacity (Ics) at 500 V AC 100 kA
Service short-circuit breaking capacity (Ics) at 690 V AC 100 kA
Short-time withstand current (Icw), 1 s 100 kA
Short-time withstand current (Icw), 3 s 85 kA
Integrated earth-fault protection Yes
Auxiliary contacts 4
Position indication Circuit breaker open / closed
Installation Moving part for withdrawable circuit breaker
Power loss 1100 W
Mechanical durability 12000 cycles
Electrical durability at 500–690 V AC 1500 cycles
Product net weight 138 kg
HS code 85362090
Standard IEC
Short-circuit performance level V
Product group 310513-New Emax

Frequently Asked Questions

What is the ABB 1SDA057154R1?

The ABB 1SDA057154R1 is a SACE Emax E6V 6300 A three-pole withdrawable air circuit breaker moving part equipped with a PR121/P-LSIG R6300 electronic overcurrent release.

What protection functions does the PR121/P-LSIG trip unit provide?

The PR121/P-LSIG electronic release provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection.

What is the breaking capacity of the ABB 1SDA057154R1?

The ABB 1SDA057154R1 has an ultimate short-circuit breaking capacity of 150 kA at 415 V AC, 130 kA at 500 V AC and 100 kA at 690 V AC.

What is the rated current of the ABB 1SDA057154R1?

The ABB 1SDA057154R1 has a rated uninterrupted current of 6300 A, making it suitable for major high-current low-voltage power distribution circuits.

Is the ABB 1SDA057154R1 fixed or withdrawable?

The 1SDA057154R1 is a withdrawable moving-part version designed for installation with the corresponding ABB SACE Emax fixed part or cradle.

Trusted by Power Distribution Professionals Worldwide

ABB SACE Emax air circuit breakers are engineered for reliable protection and switching in demanding low-voltage power distribution systems, combining high-current capability, comprehensive electronic protection, exceptional short-circuit performance and maintainable withdrawable construction.