1SDA057141R1 ABB E6V6300 PR122/P-LSIG 6300A 3-Pole Fixed Air Circuit Breaker

1SDA057141R1 ABB E6V6300 PR122/P-LSIG 6300A 3-Pole Fixed Air Circuit Breaker

ABB 1SDA057141R1 E6V6300 PR122/P-LSIG is a 6300 A three-pole fixed SACE Emax air circuit breaker with electronic LSIG protection and high short-circuit performance for demanding low-voltage power distribution systems.

SKU: 1SDA057141R1MPN: 1SDA057141R1
Price
List Price £95,625.94 ex VAT
Your Price (ex VAT) Save 25%
£71,719.46 25% OFF
You save £23,906.49 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £71,719.46
Trade pricing is personalised to your account

Manufacturer Lead Time

£71,719.46

Why Choose the ABB E6V6300 PR122/P-LSIG 6300A 3-Pole Fixed Air Circuit Breaker?

The ABB 1SDA057141R1, product designation E6V6300PR122/P-LSIGIn=6300A3pF, is a high-performance SACE Emax air circuit breaker designed for switching and protection in demanding low-voltage electrical distribution systems. Part of the ABB SACE Emax E6V series, this three-pole fixed circuit breaker combines a 6300 A rated current with the advanced PR122/P-LSIG electronic overcurrent release.

The E6V6300 is engineered for high-current industrial, commercial and infrastructure installations where comprehensive circuit protection and substantial fault-clearing capability are required. Its PR122/P-LSIG R6300 electronic trip unit provides long-time, short-time, instantaneous and ground-fault protection, helping protect busbars, cables, switchgear and connected equipment while supporting selective coordination within complex electrical distribution networks.

The E6V performance level provides an ultimate short-circuit breaking capacity of up to 150 kA at 400–440 V AC, with high breaking performance maintained at higher operating voltages. This three-pole fixed version is suited to permanent integration into high-capacity switchboards and provides a robust protection solution for installations with substantial prospective fault currents.

Key Advantages

  • High-performance ABB SACE Emax E6V air circuit breaker for demanding low-voltage distribution systems.
  • 6300 A rated current for high-capacity industrial and infrastructure installations.
  • PR122/P-LSIG R6300 electronic overcurrent release with comprehensive LSIG protection.
  • Ground-fault protection adds an additional protective function beyond conventional LSI configurations.
  • 150 kA ultimate short-circuit breaking capacity at 400–440 V AC.
  • Three-pole fixed configuration for permanent integration into high-current switchboards.
  • Short-time protection supports selective coordination between upstream and downstream protective devices.

Key Features

  • ABB SACE Emax E6V series.
  • 6300 A rated current.
  • Three-pole configuration.
  • Fixed circuit breaker.
  • PR122/P-LSIG R6300 electronic trip unit.
  • Long-time overload protection.
  • Short-time short-circuit protection.
  • Instantaneous short-circuit protection.
  • Ground-fault protection.
  • 690 V AC rated operational voltage.
  • 1000 V rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • 150 kA Icu at 400–440 V AC.
  • 100 kA short-time withstand current for 1 s.
  • 85 kA short-time withstand current for 3 s.

Reliable Protection for High-Current Power Distribution

Air circuit breakers such as the ABB SACE Emax E6V6300 provide switching and protection for high-capacity low-voltage distribution networks. With a rated current of 6300 A and V-level short-circuit performance, the E6V platform is particularly suited to main incoming supplies, large switchboards, transformer secondary systems and industrial distribution networks where substantial loads and high prospective fault currents must be safely managed.

The PR122/P-LSIG electronic release provides four complementary protection functions. Long-time protection responds to sustained overloads, short-time protection supports controlled fault clearing and selective coordination, instantaneous protection responds rapidly to severe short circuits, and ground-fault protection provides additional protection against earth-fault conditions. This combination makes the breaker well suited to sophisticated high-current distribution systems requiring comprehensive electronic protection.

Typical Applications

  • Main low-voltage electrical distribution switchboards.
  • High-current industrial power distribution systems.
  • Large switchgear and busbar assemblies.
  • Transformer secondary protection and distribution.
  • Manufacturing and heavy process plants.
  • Data centre and critical infrastructure power distribution.
  • Commercial and infrastructure electrical installations.
  • High-capacity distribution systems requiring selective LSIG protection.

Technical Specifications

Series SACE Emax E6V
ABB product group 310513-New Emax
ABB order code 1SDA057141R1
Product designation E6V6300PR122/P-LSIGIn=6300A3pF
Product type Air circuit breaker
Rated current (In) 6300 A
Rated operational current (Ie) 6300 A
Rated uninterrupted current (Iu) 6300 A
Number of poles 3
Version Fixed
Trip unit PR122/P-LSIG R6300
Release type Electronic
Protection functions Long-time, short-time, instantaneous and ground-fault (LSIG)
Integrated ground-fault protection Yes
Performance level V
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Rated ultimate short-circuit breaking capacity (Icu) at 400–415 V AC 150 kA
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 150 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC 130 kA
Rated ultimate short-circuit breaking capacity (Icu) at 660–690 V AC 100 kA
Rated service short-circuit breaking capacity (Ics) at 400–415 V AC 150 kA
Rated service short-circuit breaking capacity (Ics) at 440 V AC 125 kA
Rated service short-circuit breaking capacity (Ics) at 500 V AC 100 kA
Rated service short-circuit breaking capacity (Ics) at 660–690 V AC 100 kA
Rated short-time withstand current (Icw) 100 kA for 1 s; 85 kA for 3 s
Overload release adjustment range 2520–6300 A
Standard IEC

Frequently Asked Questions

What is the ABB 1SDA057141R1 used for?

The ABB 1SDA057141R1 is a SACE Emax E6V air circuit breaker designed for switching and protecting high-current low-voltage electrical distribution systems, including main switchboards, transformer secondary systems and major industrial installations.

What is the rated current of the ABB E6V6300?

The E6V6300 has a rated current of 6300 A, making it suitable for very high-current industrial, commercial and infrastructure power distribution applications.

What protection does the PR122/P-LSIG trip unit provide?

The PR122/P-LSIG R6300 electronic overcurrent release provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection.

What is the short-circuit performance of the ABB E6V6300?

The E6V6300 provides an ultimate short-circuit breaking capacity of 150 kA at 400–440 V AC, 130 kA at 500 V AC and 100 kA at 660–690 V AC. Its rated short-time withstand current is 100 kA for 1 s and 85 kA for 3 s.

Is the ABB 1SDA057141R1 fixed or withdrawable, and how many poles does it have?

The 1SDA057141R1 is a three-pole fixed air circuit breaker designed for permanent installation within compatible ABB SACE Emax low-voltage switchgear assemblies.

Trusted ABB Power Distribution Technology

ABB SACE Emax air circuit breakers are engineered for dependable switching and protection in demanding low-voltage power distribution systems, combining high current capacity and substantial short-circuit performance with advanced electronic protection for industrial, commercial and infrastructure installations.