Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA057132R1 SACE Emax E6V5000 four-pole withdrawable air circuit breaker moving part with a 5000 A rated current, PR122/P-LSI R5000 electronic protection release and ultimate short-circuit breaking capacity of up to 150 kA.
£71,818.03
The ABB 1SDA057132R1 is a high-performance SACE Emax E6V air circuit breaker moving part designed for protection and switching of high-current low-voltage electrical distribution systems. Part of the ABB New Emax series, the E6V5000 combines a 5000 A current rating with the PR122/P-LSI electronic overcurrent release for dependable protection in demanding industrial, commercial and infrastructure power distribution applications.
This four-pole withdrawable circuit breaker moving part is equipped with the PR122/P-LSI R5000 electronic trip unit. Its LSI protection functions provide long-time overload (L), selective short-circuit (S) and instantaneous short-circuit (I) protection, supporting coordinated protection strategies in high-capacity electrical distribution networks.
The E6V5000 provides an ultimate short-circuit breaking capacity of up to 150 kA at 220–440 V AC, with 130 kA at 500 V AC and 100 kA at 660–690 V AC. Combined with its 5000 A current capability, four-pole construction and withdrawable configuration, the 1SDA057132R1 is suited to critical distribution systems requiring high fault-clearing performance and serviceable switchgear.
Air circuit breakers such as the ABB SACE Emax E6V5000 provide switching and protection for high-current low-voltage distribution circuits. The electronic trip unit monitors electrical conditions and initiates circuit interruption when configured protection thresholds are exceeded, helping protect busbars, cables, transformers and connected equipment against damaging overload and short-circuit currents.
The PR122/P-LSI release combines long-time overload, selective short-circuit and instantaneous short-circuit protection, supporting coordinated protection within complex electrical distribution networks. Together with the E6V5000's 5000 A current capability, short-circuit breaking capacity of up to 150 kA, four-pole construction and withdrawable design, the 1SDA057132R1 is particularly suited to critical installations requiring robust protection and maintainable switchgear.
| Series | SACE Emax / New Emax |
|---|---|
| Order code | 1SDA057132R1 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker moving part |
| Frame / sub-type | E6 |
| Short-circuit performance level | V |
| Rated current (In) | 5000 A |
| Rated operational current (Ie) | 5000 A |
| Rated uninterrupted current (Iu) | 5000 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Number of poles | 4 |
| Trip unit | PR122/P-LSI R5000 |
| Trip unit type | Electronic |
| Protection functions | Long-time overload, selective short-circuit and instantaneous short-circuit protection (LSI) |
| Ultimate short-circuit breaking capacity (Icu), 220–440 V AC | 150 kA |
| Ultimate short-circuit breaking capacity (Icu), 500 V AC | 130 kA |
| Ultimate short-circuit breaking capacity (Icu), 660–690 V AC | 100 kA |
| Service short-circuit breaking capacity (Ics), 220–415 V AC | 150 kA |
| Service short-circuit breaking capacity (Ics), 440 V AC | 125 kA |
| Service short-circuit breaking capacity (Ics), 500–690 V AC | 100 kA |
| Rated short-time withstand current (Icw), 1 s | 100 kA |
| Rated short-time withstand current (Icw), 3 s | 85 kA |
| Version | Withdrawable |
| Installation component | Moving part (MP) |
| Terminal connection type | Withdrawable circuit breaker |
| Auxiliary contacts | 4 contacts with open / closed circuit-breaker position indication |
| Power loss | 700 W |
| Electrical durability at Ue ≤ 440 V | 3000 cycles |
| Electrical durability at Ue 500–690 V | 2000 cycles |
| Mechanical durability | 12,000 cycles |
| Maximum electrical operating frequency | 10 cycles per hour |
| Maximum mechanical operating frequency | 60 cycles per hour |
| Dimensions (W × H × D) | 936 × 461 × 396.5 mm |
| Net weight | 134 kg |
| EAN | 8015644584726 |
| Customs tariff number | 85362090 |
| Current type | AC |
| Reference standard | IEC |
The ABB 1SDA057132R1 is a 5000 A four-pole withdrawable air circuit breaker moving part designed for switching and protection of high-current low-voltage electrical distribution systems.
The E6V5000 has a rated operational and uninterrupted current of 5000 A, making it suitable for major high-capacity power distribution applications.
The circuit breaker is fitted with an electronic ABB PR122/P-LSI R5000 overcurrent release providing long-time overload, selective short-circuit and instantaneous short-circuit protection.
The E6V5000 has an ultimate short-circuit breaking capacity of 150 kA at 220–440 V AC, 130 kA at 500 V AC and 100 kA at 660–690 V AC.
The 1SDA057132R1 is a four-pole withdrawable moving part designed for use with the corresponding fixed part of an ABB SACE Emax E6 withdrawable circuit-breaker installation.
ABB SACE Emax air circuit breakers are engineered for reliable protection and switching in demanding low-voltage power distribution systems, combining high current capacity, advanced electronic protection, robust short-circuit performance and serviceable withdrawable configurations for industrial and infrastructure applications.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.