Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA056873R1 E4H4000 PR121/P-LSI is a 4000 A four-pole withdrawable SACE Emax air circuit breaker moving part with electronic LSI overcurrent protection for demanding low-voltage power distribution systems.
£38,704.23
The ABB 1SDA056873R1, extended product type E4H4000PR121/P-LSIIn=4000A4pWMP, is a high-performance SACE Emax air circuit breaker moving part designed for protection and switching in demanding low-voltage electrical distribution systems. Part of the ABB SACE Emax E4 series, this four-pole withdrawable unit combines a 4000 A current rating with the electronic PR121/P-LSI overcurrent release for comprehensive circuit protection.
The E4H4000 is engineered for high-current industrial and commercial power distribution applications where dependable protection against overloads and short circuits is essential. Its PR121/P-LSI electronic trip unit provides long-time, short-time and instantaneous protection functions, allowing the breaker to respond to different types of overcurrent conditions while helping protect cables, switchgear and connected electrical equipment.
With a rated uninterrupted current of 4000 A, a rated voltage of 690 V AC and an ultimate short-circuit breaking capacity of 100 kA at 400 V AC, the E4H4000 is suited to substantial power distribution systems. This version is a four-pole withdrawable moving part fitted with four auxiliary contacts and circuit-breaker open/closed position indication for integration into compatible SACE Emax switchgear.
Air circuit breakers such as the ABB SACE Emax E4H4000 protect low-voltage distribution networks by interrupting potentially damaging currents when overload or short-circuit conditions occur. The E4H platform combines a high continuous current rating with substantial short-circuit breaking performance, making it particularly suitable for main switchboards, industrial distribution systems and other installations carrying significant electrical loads.
The PR121/P-LSI electronic release provides three complementary protection functions. Long-time protection responds to sustained overloads, short-time protection supports selective coordination during short-circuit conditions, and instantaneous protection provides rapid interruption of severe faults. The withdrawable construction also allows the moving part to be removed from its compatible fixed section, supporting maintenance and servicing strategies in critical electrical distribution systems.
| Series | SACE Emax E4 |
|---|---|
| ABB product group | 310513-New Emax |
| ABB order code | 1SDA056873R1 |
| Extended product type | E4H4000PR121/P-LSIIn=4000A4pWMP |
| Product type | Air circuit breaker moving part |
| Rated current (In) | 4000 A |
| Rated uninterrupted current (Iu) | 4000 A |
| Rated voltage | 690 V AC |
| Number of poles | 4 |
| Version | Withdrawable |
| Component type | Moving part |
| Trip unit | PR121/P-LSI |
| Release type | Electronic |
| Protection functions | Long-time, short-time and instantaneous (LSI) |
| Overload release adjustment range | 1600–4000 A |
| Short-time delayed short-circuit adjustment range | 4000–40000 A |
| Instantaneous short-circuit adjustment range | 6000–60000 A |
| Short-circuit performance level | H |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 660 V AC | 85 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 85 kA |
| Auxiliary contacts | 4 change-over contacts |
| Position indication | Circuit breaker open/closed |
| Motor drive | Optional |
| EAN | 8015644582135 |
| Standard | IEC |
The ABB 1SDA056873R1 is a SACE Emax E4H withdrawable air circuit breaker moving part designed for switching and protecting high-current low-voltage electrical distribution systems.
The E4H4000 has a rated uninterrupted current of 4000 A, making it suitable for substantial industrial, infrastructure and commercial power distribution applications.
The PR121/P-LSI electronic overcurrent release provides long-time overload, short-time short-circuit and instantaneous short-circuit protection functions.
The E4H4000 has a rated ultimate short-circuit breaking capacity of 100 kA at 400 V AC and 85 kA at 690 V AC.
The 1SDA056873R1 is a four-pole withdrawable moving part designed for use with the corresponding ABB SACE Emax fixed part.
ABB SACE Emax air circuit breakers are designed for dependable switching and protection in demanding low-voltage power distribution systems, combining high breaking performance with configurable electronic overcurrent protection for industrial, commercial and infrastructure installations.
We use cookies