Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA056856R1 E4H4000 PR121/P-LI is a 4000 A four-pole fixed SACE Emax air circuit breaker with rear horizontal terminals and a PR121/P-LI R4000 electronic release providing long-time overload and instantaneous short-circuit protection.
£33,043.46
The ABB E4H4000 PR121/P-LI, order code 1SDA056856R1, is a high-performance SACE Emax E4H air circuit breaker designed for protection and switching in high-current low-voltage electrical distribution systems. Rated at 4000 A, this four-pole fixed circuit breaker combines the robust ABB SACE Emax platform with a PR121/P-LI R4000 electronic overcurrent release.
The PR121/P-LI release provides long-time (L) and instantaneous (I) overcurrent protection, helping protect electrical installations against sustained overloads and severe short-circuit conditions. The E4H performance level provides substantial fault-interruption capability for main distribution switchboards, industrial power systems and other high-capacity installations.
This configuration is supplied as a four-pole fixed circuit breaker with rear horizontal terminals. It is rated for operation up to 690 V AC and provides an ultimate and service short-circuit breaking capacity of 100 kA from 400 V to 500 V AC and 85 kA at 690 V AC, making it suitable for demanding high-fault-level distribution systems.
The ABB SACE Emax E4H platform is designed for high-capacity low-voltage distribution systems where substantial short-circuit performance is required. The PR121/P-LI electronic release combines long-time overload and instantaneous short-circuit protection, helping safeguard busbars, feeders and connected electrical equipment against damaging overcurrent conditions.
The E4H4000 PR121/P-LI combines a substantial 4000 A current rating, four-pole construction and fixed rear-connected design with up to 100 kA ultimate and service short-circuit breaking capacity. These characteristics make it particularly suitable for main switchboards and other high-capacity distribution assemblies where dependable fault interruption and electronic overcurrent protection are essential.
| Series | SACE Emax E4H |
|---|---|
| ABB order code | 1SDA056856R1 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker |
| Rated current (In) | 4000 A |
| Rated operational current (Ie) | 4000 A |
| Rated uninterrupted current (Iu) | 4000 A |
| Number of poles | 4 |
| Execution | Fixed |
| Main terminal arrangement | Rear horizontal |
| Protection release | PR121/P-LI R4000 |
| Release technology | Electronic |
| Protection functions | Long-time (L) and instantaneous (I) |
| Current type | AC |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Ultimate short-circuit breaking capacity (Icu) at 400 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 85 kA |
| Service short-circuit breaking capacity (Ics) at 400 V AC | 100 kA |
| Service short-circuit breaking capacity (Ics) at 415 V AC | 100 kA |
| Service short-circuit breaking capacity (Ics) at 440 V AC | 100 kA |
| Service short-circuit breaking capacity (Ics) at 500 V AC | 100 kA |
| Service short-circuit breaking capacity (Ics) at 690 V AC | 85 kA |
| Rated short-time withstand current (Icw), 1 s | 100 kA |
| Rated short-time withstand current (Icw), 3 s | 75 kA |
| Short-circuit performance level | H |
| Mechanical endurance | 15000 cycles |
| Electrical endurance at ≤440 V AC | 5000 cycles |
| Electrical endurance at 500–690 V AC | 4000 cycles |
| Power loss | 360 W |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Dimensions (W × H × D) | 656 × 418 × 302 mm |
| Net weight | 92 kg |
| Standard | IEC |
| EAN | 8015644581961 |
| HS code | 85362090 |
The ABB 1SDA056856R1 is an E4H4000 SACE Emax air circuit breaker rated at 4000 A, with four poles, fixed construction, rear horizontal terminals and a PR121/P-LI R4000 electronic overcurrent release.
The ABB E4H4000 PR121/P-LI 1SDA056856R1 has a rated operational and uninterrupted current of 4000 A.
The PR121/P-LI electronic release provides long-time overload protection (L) and instantaneous short-circuit protection (I).
ABB 1SDA056856R1 is a fixed four-pole air circuit breaker equipped with rear horizontal main terminals.
The E4H4000 PR121/P-LI has a rated operational voltage of 690 V AC, a rated insulation voltage of 1000 V and a rated impulse withstand voltage of 12 kV.
The E4H4000 provides ultimate and service short-circuit breaking capacities of 100 kA from 400 V to 500 V AC and 85 kA at 690 V AC.
ABB SACE Emax air circuit breakers are widely used in industrial, commercial and infrastructure power distribution systems where dependable high-current switching, electronic overcurrent protection and high short-circuit performance are required.
We use cookies