1SDA056824R1 ABB E4H3200 PR121/P-LI 3200 A 4-Pole Fixed Air Circuit Breaker

1SDA056824R1 ABB E4H3200 PR121/P-LI 3200 A 4-Pole Fixed Air Circuit Breaker

ABB 1SDA056824R1 E4H3200 is a 3200 A four-pole fixed SACE Emax air circuit breaker with a PR121/P-LI electronic trip unit providing long-time overload and instantaneous short-circuit protection for high-current low-voltage power distribution systems.

SKU: 1SDA056824R1MPN: 1SDA056824R1
Price
List Price £35,815.10 ex VAT
Your Price (ex VAT) Save 25%
£26,861.33 25% OFF
You save £8,953.78 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £26,861.33
Trade pricing is personalised to your account

Manufacturer Lead Time

£26,861.33

Why Choose the ABB E4H3200 PR121/P-LI Air Circuit Breaker?

The ABB 1SDA056824R1 is a high-performance SACE Emax E4H air circuit breaker designed for switching and protection in high-current low-voltage electrical distribution systems. Identified as E4H3200 PR121/P-LI, this four-pole fixed circuit breaker combines a 3200 A rated current with ABB's PR121/P-LI electronic overcurrent release for dependable overload and instantaneous short-circuit protection.

As part of the ABB SACE Emax / New Emax range, the E4H3200 is engineered for demanding industrial, commercial and infrastructure power distribution applications. Its H short-circuit performance level provides an ultimate short-circuit breaking capacity of 100 kA at 400 V AC and 85 kA at 690 V AC. The fixed construction with rear horizontal terminals provides a robust arrangement for permanent installation within low-voltage switchboards.

The integrated PR121/P-LI electronic trip unit provides long-time overload (L) and instantaneous short-circuit (I) protection. With a rated operational voltage of up to 690 V AC, four-pole configuration and 3200 A rated uninterrupted current, the 1SDA056824R1 is well suited to main incoming and distribution protection duties where high breaking capacity and switched-neutral capability are required.

Key Advantages

  • High-capacity 3200 A air circuit breaker for demanding low-voltage power distribution.
  • Four-pole configuration provides simultaneous switching of three phases and neutral.
  • PR121/P-LI electronic trip unit provides long-time overload and instantaneous short-circuit protection.
  • High 100 kA Icu at 400 V AC ultimate short-circuit breaking capacity.
  • Maintains 85 kA Icu at 690 V AC for demanding higher-voltage distribution systems.
  • 100 kA short-time withstand current for 1 s.
  • Fixed construction with rear horizontal terminals for permanent switchboard installation.
  • Fitted with four auxiliary contacts and open/closed circuit breaker position indication.

Key Features

  • ABB SACE Emax E4H series.
  • 3200 A rated uninterrupted current.
  • Four-pole circuit breaker configuration.
  • PR121/P-LI electronic overcurrent release.
  • Long-time overload and instantaneous short-circuit protection.
  • 690 V AC rated operational voltage.
  • 1000 V rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • 100 kA Icu at 400 V AC.
  • 85 kA Icu at 690 V AC.
  • 100 kA rated short-time withstand current for 1 s.
  • 75 kA rated short-time withstand current for 3 s.
  • Fixed circuit breaker design with rear horizontal terminals.
  • Fitted with four auxiliary contacts and open/closed position indication.

High Breaking Capacity for Critical Power Distribution

Air circuit breakers such as the ABB E4H3200 provide switching and protection for high-current low-voltage distribution systems. The E4H performance level is designed for installations with substantial prospective fault currents, offering an ultimate short-circuit breaking capacity of 100 kA through the 220–500 V AC range and 85 kA at 660–690 V AC.

The PR121/P-LI electronic release provides long-time overload and instantaneous short-circuit protection, while the four-pole construction enables switching of the neutral together with all three phases. Combined with the E4H's high breaking and short-time withstand performance, the 1SDA056824R1 is suitable for major switchboards and industrial distribution systems requiring robust fixed circuit protection.

Typical Applications

  • Main incoming circuit protection in high-current low-voltage switchboards.
  • Four-wire three-phase electrical distribution systems.
  • Industrial power distribution systems.
  • Transformer secondary distribution and protection.
  • Protection of high-current distribution feeders and busbar systems.
  • Large commercial and infrastructure electrical installations.
  • Manufacturing plants and process facilities.
  • High-fault-level switchgear and electrical distribution assemblies.

Technical Specifications

Series SACE Emax / New Emax
Product group 310513-New Emax
ABB order code 1SDA056824R1
Product type Air circuit breaker
Frame E4
Short-circuit performance level H
Rated current (In) 3200 A
Rated uninterrupted current (Iu) 3200 A
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Number of poles 4
Current type AC
Trip unit PR121/P-LI
Trip unit type Electronic
Protection functions L and I
Ultimate short-circuit breaking capacity (Icu) at 220 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 230 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 380 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 400 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 415 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 440 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 500 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 660 V AC 85 kA
Ultimate short-circuit breaking capacity (Icu) at 690 V AC 85 kA
Rated short-time withstand current (Icw), 1 s 100 kA
Rated short-time withstand current (Icw), 3 s 75 kA
Installation type Fixed
Terminal connection Rear flat horizontal
Version F
Auxiliary contacts 4
Position indication Open / closed
Standard IEC
EAN 8015644581640

Frequently Asked Questions

What is the ABB 1SDA056824R1 used for?

The ABB 1SDA056824R1 is a 3200 A four-pole fixed air circuit breaker used for switching and protecting high-current low-voltage electrical distribution systems.

What trip unit is fitted to the ABB E4H3200?

This circuit breaker is fitted with the ABB PR121/P-LI electronic trip unit, providing long-time overload and instantaneous short-circuit protection.

What is the rated current of the ABB 1SDA056824R1?

The circuit breaker has a rated uninterrupted current of 3200 A.

What is the breaking capacity of the ABB E4H3200?

The E4H3200 has an ultimate short-circuit breaking capacity (Icu) of 100 kA at 400 V AC and 85 kA at 690 V AC, together with a rated short-time withstand current of 100 kA for 1 s.

Is the ABB 1SDA056824R1 fixed or withdrawable?

The 1SDA056824R1 is a fixed four-pole SACE Emax circuit breaker with rear flat horizontal terminals, designed for permanent installation within low-voltage switchboards and power distribution assemblies.

Trusted ABB Power Distribution Protection

ABB SACE Emax air circuit breakers are designed for demanding low-voltage power distribution applications, combining high breaking performance, electronic protection and robust construction for dependable high-current electrical system protection.