ABB 1SDA056820R1 E4H3200PR122/P-LSI is a 3200 A three-pole fixed SACE Emax air circuit breaker with rear horizontal terminals, a PR122/P-LSI R3200 electronic overcurrent release and 100 kA breaking capacity at 400/415 V AC.
£22,647.53
The ABB E4H3200PR122/P-LSI, order code 1SDA056820R1, is a high-performance 3200 A three-pole air circuit breaker designed for reliable switching and protection in demanding low-voltage electrical distribution systems. Part of the proven ABB SACE Emax E4 series, this fixed breaker combines the E4H high short-circuit performance level with the advanced PR122/P electronic overcurrent release.
The breaker is equipped with an ABB PR122/P-LSI R3200 electronic overcurrent release, providing long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. These LSI functions support effective protection coordination while safeguarding cables, busbars, transformers and downstream equipment against damaging overcurrents and short-circuit faults.
With a rated uninterrupted current of 3200 A, a three-pole fixed configuration and rear horizontal terminals, the E4H3200PR122/P-LSI is engineered for permanent integration into high-capacity switchgear. The E4H platform provides an ultimate short-circuit breaking capacity of 100 kA at 400/415 V AC, making it particularly suitable for networks with high prospective fault currents.
Air circuit breakers such as the ABB SACE Emax E4 protect low-voltage electrical networks against damaging overcurrents while providing dependable switching and isolation of high-current circuits. The E4H performance class offers particularly high fault interruption capability, making it suitable for main incomers, transformer secondaries, large feeders and other circuits where substantial prospective short-circuit currents can occur.
The PR122/P electronic release continuously monitors circuit current and initiates breaker operation when configured protection thresholds are exceeded. In this LSI configuration, long-time protection responds to sustained overloads, short-time protection enables coordinated response to short-circuit conditions, and instantaneous protection provides rapid interruption of severe faults.
| Series | SACE Emax E4 |
|---|---|
| ABB order code | 1SDA056820R1 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker |
| Frame / performance class | E4H 3200 |
| Short-circuit performance level | H |
| Rated current (In) | 3200 A |
| Rated uninterrupted current (Iu) | 3200 A |
| Rated operational voltage (Ue) | 690 V AC |
| Number of poles | 3 |
| Execution | Fixed (F) |
| Terminal connection | Rear horizontal (HR) |
| Protection release | PR122/P-LSI R3200 electronic overcurrent release |
| Release type | Electronic |
| Protection functions | L (long-time), S (short-time) and I (instantaneous) |
| Ultimate short-circuit breaking capacity (Icu) at 400 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 660 V AC | 85 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 85 kA |
| Service short-circuit breaking capacity (Ics) at 415 V AC | 100 kA |
| Rated short-time withstand current (Icw), 1 s | 100 kA |
| Rated short-time withstand current (Icw), 3 s | 75 kA |
| Auxiliary contacts | 4 |
| Position indication | Open / closed breaker indication |
| Standard | IEC |
| EAN | 8015644581602 |
This ABB SACE Emax air circuit breaker is designed for switching and protecting high-current low-voltage distribution circuits, particularly installations requiring high short-circuit interruption capability and electronic LSI protection.
The ABB 1SDA056820R1 has a rated uninterrupted current of 3200 A and uses a three-pole fixed E4H air circuit breaker configuration.
The breaker is fitted with an ABB PR122/P-LSI R3200 electronic overcurrent release, providing long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection.
The E4H3200 provides an ultimate short-circuit breaking capacity of 100 kA at 400/415 V AC. Its Icu remains 100 kA through 500 V AC and is 85 kA at 660–690 V AC.
The ABB 1SDA056820R1 is a three-pole fixed air circuit breaker with rear horizontal terminals, designed for permanent integration into compatible low-voltage switchgear assemblies.
ABB SACE Emax air circuit breakers are engineered for dependable protection, switching and control of demanding low-voltage electrical distribution systems, combining high-current capability, high short-circuit performance and advanced electronic protection technology.