Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA056812R1 E4S4000 PR122/P-LSI is a 4000 A four-pole withdrawable SACE Emax air circuit breaker moving part with a PR122/P-LSI R4000 electronic release providing long-time, short-time and instantaneous overcurrent protection.
£38,545.80
The ABB E4S4000 PR122/P-LSI, order code 1SDA056812R1, is a high-performance SACE Emax E4S air circuit breaker moving part designed for protection and switching in high-current low-voltage electrical distribution systems. Rated at 4000 A, this four-pole withdrawable configuration combines the robust ABB SACE Emax platform with a PR122/P-LSI R4000 electronic overcurrent release.
The PR122/P-LSI release provides long-time (L), short-time (S) and instantaneous (I) overcurrent protection, helping protect electrical installations against sustained overloads and short-circuit conditions while supporting selective coordination within distribution networks. The E4S performance level provides high short-circuit capability for demanding main distribution, industrial and infrastructure applications.
This version is supplied as the four-pole withdrawable moving part of the E4S4000 circuit breaker and is designed for use with the corresponding SACE Emax fixed part. Its withdrawable construction facilitates inspection, servicing and replacement, while four auxiliary contacts and circuit-breaker open/closed position indication support integration with switchboard monitoring and control systems.
Air circuit breakers such as the ABB SACE Emax E4S are designed to protect high-capacity low-voltage distribution systems against damaging overcurrent conditions. The PR122/P-LSI electronic release combines long-time overload, short-time short-circuit and instantaneous short-circuit protection, helping safeguard busbars, feeders and connected electrical equipment while supporting coordinated system protection.
The withdrawable E4S4000 configuration is particularly suitable for switchboards where serviceability and operational flexibility are important. The circuit-breaker moving part can be withdrawn from its corresponding fixed part for inspection, maintenance or replacement, while its 4000 A rating, four-pole configuration and 75 kA short-circuit performance make it suitable for substantial industrial and infrastructure distribution systems.
| Series | SACE Emax E4S |
|---|---|
| ABB order code | 1SDA056812R1 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker moving part |
| Rated current (In) | 4000 A |
| Rated uninterrupted current (Iu) | 4000 A |
| Number of poles | 4 |
| Execution | Withdrawable |
| Component | Moving part |
| Protection release | PR122/P-LSI R4000 |
| Release technology | Electronic |
| Protection functions | Long-time (L), short-time (S) and instantaneous (I) |
| Rated operational voltage | 690 V AC |
| Ultimate short-circuit breaking capacity (Icu) at 400 V AC | 75 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 75 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500 V AC | 75 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 75 kA |
| Service short-circuit breaking capacity (Ics) at 400 V AC | 75 kA |
| Service short-circuit breaking capacity (Ics) at 440 V AC | 75 kA |
| Service short-circuit breaking capacity (Ics) at 500 V AC | 75 kA |
| Service short-circuit breaking capacity (Ics) at 690 V AC | 75 kA |
| Rated short-time withstand current (Icw), 1 s | 75 kA |
| Rated short-time withstand current (Icw), 3 s | 75 kA |
| Short-circuit performance level | S |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Standard | IEC |
| Weight | 116 kg |
| EAN | 8015644581527 |
| HS code | 85362090 |
The ABB 1SDA056812R1 is the withdrawable moving part of an E4S4000 SACE Emax air circuit breaker, rated at 4000 A with four poles and a PR122/P-LSI R4000 electronic overcurrent release.
The ABB E4S4000 PR122/P-LSI 1SDA056812R1 has a rated uninterrupted current of 4000 A.
The PR122/P-LSI electronic release provides long-time overload protection (L), short-time short-circuit protection (S) and instantaneous short-circuit protection (I).
ABB 1SDA056812R1 is a withdrawable circuit-breaker moving part designed for use with the corresponding ABB SACE Emax fixed part.
The E4S4000 PR122/P-LSI has a rated operational voltage of 690 V AC.
The E4S4000 provides rated ultimate and service short-circuit breaking capacities of 75 kA across its specified AC operating-voltage range, including 400 V, 440 V, 500 V and 690 V AC.
ABB SACE Emax air circuit breakers are widely used in industrial, commercial and infrastructure power distribution systems where dependable high-current switching, advanced electronic protection and serviceable withdrawable switchgear construction are required.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.