1SDA056796R1 ABB E4S4000 PR122/P-LSI 4000 A 4-Pole Fixed Air Circuit Breaker

1SDA056796R1 ABB E4S4000 PR122/P-LSI 4000 A 4-Pole Fixed Air Circuit Breaker

ABB 1SDA056796R1 E4S4000 is a 4000 A four-pole fixed SACE Emax air circuit breaker with rear flat horizontal terminals and a PR122/P-LSI R4000 electronic release providing long-time, short-time and instantaneous overcurrent protection.

SKU: 1SDA056796R1MPN: 1SDA056796R1
Price
List Price £38,650.27 ex VAT
Your Price (ex VAT) Save 25%
£28,987.70 25% OFF
You save £9,662.57 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £28,987.70
Trade pricing is personalised to your account

Manufacturer Lead Time

£28,987.70

Why Choose the ABB E4S4000 PR122/P-LSI Air Circuit Breaker?

The ABB E4S4000 PR122/P-LSI, order code 1SDA056796R1, is a high-current SACE Emax air circuit breaker (ACB) designed for switching and overcurrent protection in demanding low-voltage power-distribution systems. Part of the ABB SACE Emax E4 series, this four-pole fixed circuit breaker combines a 4000 A rated uninterrupted current with the PR122/P-LSI R4000 electronic overcurrent release.

The PR122/P-LSI release provides long-time overload, short-time short-circuit and instantaneous short-circuit protection. These LSI functions allow the breaker to protect high-current conductors, switchboards and downstream equipment against sustained overloads and short circuits while supporting selective coordination within complex industrial and infrastructure distribution networks.

This configuration is a four-pole fixed circuit breaker with rear flat horizontal terminals. Rated for operation up to 690 V AC, the E4S4000 provides an ultimate short-circuit breaking capacity of 75 kA across its specified AC voltage range and is fitted with four auxiliary contacts plus circuit-breaker open/closed position indication.

Key Advantages

  • High-current 4000 A SACE Emax air circuit breaker for major low-voltage distribution systems.
  • PR122/P-LSI R4000 electronic release provides comprehensive LSI overcurrent protection.
  • Long-time, short-time and instantaneous protection supports coordinated fault protection.
  • Four-pole configuration supports three-phase systems requiring neutral switching.
  • Fixed construction with rear flat horizontal terminals for permanent switchboard integration.
  • 75 kA ultimate and service short-circuit breaking capacity at 400 V AC.
  • Four auxiliary contacts and open/closed position indication support switchboard signalling and control.

Key Features

  • ABB SACE Emax E4S4000 air circuit breaker.
  • 4000 A rated uninterrupted current.
  • Four-pole fixed version.
  • PR122/P-LSI R4000 electronic overcurrent release.
  • L protection: long-time overload protection.
  • S protection: short-time short-circuit protection.
  • I protection: instantaneous short-circuit protection.
  • 690 V AC rated operational voltage.
  • 75 kA rated ultimate short-circuit breaking capacity.
  • 75 kA rated service short-circuit breaking capacity.
  • 75 kA short-time withstand current for 1 s and 3 s.
  • Rear flat horizontal terminal arrangement.
  • Four auxiliary contacts: 2 NO + 2 NC.
  • Integrated circuit-breaker open/closed position indication.
  • Optional motor operator for powered operation.

Reliable LSI Protection for 4000 A Power Distribution

The ABB SACE Emax E4S4000 is engineered for switching and protection at main incomer, bus-coupler and high-current feeder levels within substantial low-voltage distribution systems. Its PR122/P-LSI electronic release provides long-time protection against sustained overloads, short-time protection for coordinated fault clearing and instantaneous intervention against severe short-circuit currents.

The combination of a 4000 A current rating, four-pole construction and 75 kA short-circuit capability makes the 1SDA056796R1 suitable for major industrial and infrastructure switchboards. Its fixed construction and rear flat horizontal terminals support permanent busbar integration, while the auxiliary contacts provide circuit-breaker status information for associated monitoring, signalling and control systems.

Typical Applications

  • Main low-voltage distribution switchboards.
  • High-current industrial power-distribution systems.
  • Manufacturing and process plants.
  • Commercial and infrastructure electrical installations.
  • Transformer secondary and main incomer protection.
  • High-current feeder and bus-coupler applications.
  • Power distribution and control assemblies.

Technical Specifications

Product group New Emax
Series SACE Emax E4
ABB order code 1SDA056796R1
Product type Air circuit breaker
Frame E4
Short-circuit performance level S
Rated current (In) 4000 A
Rated uninterrupted current (Iu) 4000 A
Rated operational current (Ie) 4000 A
Number of poles 4P
Rated operational voltage 690 V AC
Rated voltage 690 V
Release PR122/P-LSI R4000
Release type Electronic
Protection functions LSI — long-time, short-time and instantaneous
Overload release adjustment range 1600–4000 A
Short-time delayed short-circuit release adjustment range 2400–40,000 A
Instantaneous short-circuit release adjustment range 6000–60,000 A
Integrated earth-fault protection No
Version Fixed
Terminal connection Rear flat horizontal
Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC 75 kA
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 75 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC 75 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 75 kA
Rated service short-circuit breaking capacity (Ics) at 400 V AC 75 kA
Rated service short-circuit breaking capacity (Ics) at 440 V AC 75 kA
Rated service short-circuit breaking capacity (Ics) at 500 V AC 75 kA
Rated service short-circuit breaking capacity (Ics) at 690 V AC 75 kA
Rated short-time withstand current (Icw), 1 s 75 kA
Rated short-time withstand current (Icw), 3 s 75 kA
Auxiliary contacts 4
Auxiliary contact arrangement 2 NO + 2 NC
Position indication Open / closed
Operating element Pushbutton
Motor operator Optional
Product net weight 111 kg
EAN 8015644581367
HS code 85362090
Standard IEC

Frequently Asked Questions

What is the ABB 1SDA056796R1 used for?

The ABB 1SDA056796R1 is a 4000 A four-pole SACE Emax air circuit breaker designed for switching and LSI overcurrent protection in high-current low-voltage power-distribution systems.

What protection release is fitted to the ABB E4S4000?

This circuit breaker is fitted with the ABB PR122/P-LSI R4000 electronic overcurrent release, providing long-time overload, short-time short-circuit and instantaneous short-circuit protection.

What is the rated current of the ABB E4S4000 PR122/P-LSI?

The circuit breaker has a rated uninterrupted current of 4000 A and a rated operational voltage of 690 V AC.

Is the ABB 1SDA056796R1 fixed or withdrawable?

The 1SDA056796R1 is a four-pole fixed circuit breaker with rear flat horizontal terminals for permanent installation within a low-voltage switchboard.

What does LSI mean on the PR122/P release?

LSI denotes long-time overload, short-time short-circuit and instantaneous short-circuit protection. This configuration does not include the G earth-fault protection function found on LSIG releases.

Trusted Protection for Industrial Power Systems

ABB SACE Emax air circuit breakers provide dependable switching and electronic protection for demanding low-voltage distribution systems, combining high current capability, robust short-circuit performance and configurable electronic protection for critical electrical infrastructure.