Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA056785R1 E4S4000 is a 4000 A three-pole fixed SACE Emax air circuit breaker with a PR121/P-LSI electronic trip unit providing LSI protection for high-current low-voltage power distribution systems.
£25,458.78
The ABB 1SDA056785R1 is a high-performance SACE Emax E4S air circuit breaker designed for switching and protection in high-current low-voltage electrical distribution systems. Identified as E4S4000 PR121/P-LSI, this three-pole fixed circuit breaker combines a 4000 A rated current with ABB's PR121/P-LSI electronic overcurrent release for dependable circuit protection.
As part of the ABB SACE Emax / New Emax range, the E4S4000 is engineered for demanding industrial, commercial and infrastructure power distribution applications. The S short-circuit performance level provides an ultimate short-circuit breaking capacity of 75 kA at 400 V AC, with the same 75 kA rating maintained across the specified 220–690 V AC range. Its fixed construction and rear horizontal terminals provide a robust arrangement for permanent installation within low-voltage switchboards.
The integrated PR121/P-LSI electronic trip unit provides long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection. With a rated operational voltage of 690 V AC, three-pole configuration and 4000 A rated uninterrupted current, the 1SDA056785R1 is ideal for main incoming, feeder and distribution protection duties in substantial low-voltage installations.
Air circuit breakers such as the ABB E4S4000 provide switching and protection for high-current low-voltage distribution systems. The circuit breaker interrupts abnormal current conditions to help protect cables, busbars, switchgear and connected equipment against damage caused by overloads and short circuits.
The PR121/P-LSI electronic release provides long-time overload, short-time delayed and instantaneous short-circuit protection, with adjustable protection thresholds to suit the electrical installation. Combined with the E4S's 75 kA breaking performance and robust fixed construction, this makes the 1SDA056785R1 suitable for major distribution boards, switchboards and industrial installations where dependable and selective electrical protection is required.
| Series | SACE Emax / New Emax |
|---|---|
| Product group | 310513-New Emax |
| ABB order code | 1SDA056785R1 |
| Product type | Air circuit breaker |
| Frame | E4 |
| Short-circuit performance level | S |
| Rated current (In) | 4000 A |
| Rated operational current (Ie) | 4000 A |
| Rated uninterrupted current (Iu) | 4000 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Number of poles | 3 |
| Current type | AC |
| Trip unit | PR121/P-LSI |
| Trip unit type | Electronic |
| Protection functions | L, S and I |
| Overload release adjustment range | 1600–4000 A |
| Short-time delayed short-circuit adjustment range | 4000–40000 A |
| Instantaneous short-circuit adjustment range | 6000–60000 A |
| Ultimate short-circuit breaking capacity (Icu) at 400 V AC | 75 kA |
| Service short-circuit breaking capacity (Ics) at 400 V AC | 75 kA |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 75 kA |
| Service short-circuit breaking capacity (Ics) at 415 V AC | 75 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500 V AC | 75 kA |
| Service short-circuit breaking capacity (Ics) at 500 V AC | 75 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 75 kA |
| Service short-circuit breaking capacity (Ics) at 690 V AC | 75 kA |
| Rated short-time withstand current (Icw), 1 s | 75 kA |
| Rated short-time withstand current (Icw), 3 s | 75 kA |
| Installation type | Fixed |
| Terminal connection | Rear horizontal |
| Version | F |
| Auxiliary contacts | 4 change-over contacts |
| Position indication | Open / closed |
| Mechanical endurance | 15,000 operations |
| Electrical endurance at ≤440 V AC | 5,000 operations |
| Electrical endurance at 500–690 V AC | 4,000 operations |
| Power loss | 360 W |
| Dimensions (H × W × D) | 418 × 566 × 302 mm |
| Net weight | 81 kg |
| Standard | IEC |
| EAN | 8015644581251 |
| Customs tariff number | 85362090 |
The ABB 1SDA056785R1 is a 4000 A three-pole fixed air circuit breaker used for switching and protecting high-current low-voltage electrical distribution systems.
This circuit breaker is fitted with the ABB PR121/P-LSI electronic trip unit, providing long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection.
The circuit breaker has a rated operational and uninterrupted current of 4000 A.
The E4S4000 has an ultimate short-circuit breaking capacity (Icu) and service short-circuit breaking capacity (Ics) of 75 kA at 400 V AC.
The 1SDA056785R1 is a fixed SACE Emax circuit breaker with rear horizontal terminals, designed for permanent installation within low-voltage switchboards and power distribution assemblies.
ABB SACE Emax air circuit breakers are designed for demanding low-voltage power distribution applications, combining high breaking performance, electronic protection and robust construction for dependable high-current electrical system protection.
We use cookies