Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA056627R1 is a SACE Emax E3V 2000 A three-pole fixed air circuit breaker with rear horizontal terminals and a PR122/P-LI R2000 electronic release providing long-time and instantaneous overcurrent protection.
£12,976.59
The ABB E3V2000 PR122/P-LI, order code 1SDA056627R1, is a high-performance SACE Emax air circuit breaker designed for protection and switching in demanding low-voltage power distribution systems. This three-pole fixed E3V breaker has a rated uninterrupted current of 2000 A and incorporates the PR122/P-LI R2000 electronic overcurrent release.
The PR122/P-LI release provides long-time and instantaneous overcurrent protection, helping safeguard conductors, switchboards and connected equipment against sustained overloads and severe short-circuit faults. Its overload setting range extends from 800–2000 A, while the instantaneous short-circuit release is adjustable from 3000–30000 A.
This version features a fixed three-pole construction with rear horizontal terminals and is fitted with four change-over auxiliary contacts together with circuit-breaker open/closed indication. With a rated operational voltage of 690 V AC and an ultimate short-circuit breaking capacity of up to 130 kA, the E3V2000 is engineered for demanding industrial, commercial and infrastructure power distribution.
The ABB SACE Emax E3V platform is designed for major low-voltage distribution systems where high current ratings and substantial short-circuit interruption capability are required. The 1SDA056627R1 combines a 2000 A current rating with an E3V breaking capacity reaching 130 kA, helping protect important switchboards, conductors and downstream equipment against damaging electrical faults.
Its PR122/P-LI R2000 electronic release combines adjustable long-time overload protection with instantaneous short-circuit protection. The fixed rear-horizontal-terminal construction is suited to permanent switchboard installations, while auxiliary contacts and open/closed indication allow the breaker state to be integrated into monitoring, signalling and control arrangements.
| Series | SACE Emax E3V |
|---|---|
| ABB order code | 1SDA056627R1 |
| Product type | Air circuit breaker |
| Frame / performance level | E3V |
| Frame size | E3 |
| Rated current (In) | 2000 A |
| Rated operational current (Ie) | 2000 A |
| Rated uninterrupted current (Iu) | 2000 A |
| Number of poles | 3 |
| Current type | AC |
| Configuration | Fixed |
| Terminal connection | Rear flat horizontal |
| Trip unit | PR122/P-LI R2000 |
| Release type | Electronic |
| Protection functions | Long-time (L), instantaneous (I) |
| Overload release setting range | 800–2000 A |
| Instantaneous short-circuit release setting range | 3000–30000 A |
| Rated operational voltage | 690 V AC |
| Rated voltage (Ur) | 690 V |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Ultimate short-circuit breaking capacity (Icu) | 130 kA at 220–440 V AC; 100 kA at 500–690 V AC |
| Service short-circuit breaking capacity (Ics) | 100 kA at 220–440 V AC; 85 kA at 500–690 V AC |
| Short-time withstand current (Icw) | 85 kA for 1 s; 65 kA for 3 s |
| Earth-fault protection | Not included in LI configuration |
| Auxiliary contacts | 4 change-over contacts |
| Position indication | Circuit breaker open / closed |
| Complete device with protection unit | Yes |
| Motor drive | Optional, not integrated |
| DIN rail mounting | No |
| Power loss | 130 W |
| Electrical durability | 9000 cycles at ≤440 V; 9000 cycles at 500–690 V |
| Electrical operating frequency | 20 cycles per hour |
| Mechanical durability | 20,000 cycles |
| Mechanical operating frequency | 60 cycles per hour |
| Net weight | 72 kg |
| Standard | IEC |
| Customs tariff / HS code | 85362090 |
| EAN | 8015644579678 |
The ABB 1SDA056627R1 is a SACE Emax E3V 2000 A three-pole fixed air circuit breaker with rear horizontal terminals and a PR122/P-LI R2000 electronic overcurrent release.
The PR122/P-LI electronic release provides long-time overload protection and instantaneous short-circuit protection.
The E3V2000 provides an ultimate short-circuit breaking capacity of 130 kA at 220–440 V AC and 100 kA at 500–690 V AC.
This model is a fixed three-pole air circuit breaker equipped with rear horizontal terminals for integration into a compatible low-voltage switchboard.
No. The PR122/P-LI release provides long-time and instantaneous overcurrent protection. An LSIG release configuration should be selected where integrated earth-fault protection is required.
ABB SACE Emax air circuit breakers combine high short-circuit performance, electronic overcurrent protection and robust switchboard integration to provide dependable protection for demanding industrial, commercial and infrastructure power distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.