1SDA056554R1 ABB E3V800 PR121/P-LSIG 800A 4-Pole Withdrawable Air Circuit Breaker

1SDA056554R1 ABB E3V800 PR121/P-LSIG 800A 4-Pole Withdrawable Air Circuit Breaker

ABB 1SDA056554R1 is a SACE Emax E3V800 800 A four-pole withdrawable air circuit breaker moving part with a PR121/P-LSIG R800 electronic overcurrent release providing long-time, short-time, instantaneous and earth-fault protection for demanding low-voltage power distribution systems.

SKU: 1SDA056554R1MPN: 1SDA056554R1
Price
List Price £16,697.61 ex VAT
Your Price (ex VAT) Save 25%
£12,523.21 25% OFF
You save £4,174.40 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £12,523.21
Trade pricing is personalised to your account

Manufacturer Lead Time

£12,523.21

Why Choose the ABB E3V800 PR121/P-LSIG 800A 4-Pole Air Circuit Breaker?

The ABB 1SDA056554R1 is a high-performance SACE Emax E3V air circuit breaker moving part designed for protection and switching in demanding low-voltage electrical distribution systems. Rated at 800 A, this four-pole withdrawable configuration incorporates ABB’s PR121/P-LSIG R800 electronic overcurrent release for comprehensive protection of industrial, commercial and infrastructure power networks.

As part of the ABB SACE Emax range, the E3V800 combines very high short-circuit performance with electronic protection. The PR121/P-LSIG trip unit provides long-time, short-time, instantaneous and earth-fault protection functions, helping safeguard electrical installations against overloads, short circuits and earth faults.

The E3V800 PR121/P-LSIG has a rated uninterrupted current of 800 A, a rated operational voltage of 690 V AC and an ultimate short-circuit breaking capacity of 130 kA at 400 V AC. This version is supplied as a four-pole withdrawable moving part with four auxiliary change-over contacts and circuit-breaker open/closed position indication, making it suitable for maintainable switchboards requiring four-pole switching and comprehensive LSIG protection.

Key Advantages

  • High-performance ABB SACE Emax E3V air circuit breaker moving part for demanding low-voltage distribution.
  • 800 A rated current for industrial, commercial and infrastructure installations.
  • Four-pole construction for applications requiring switching of all four conductors.
  • PR121/P-LSIG R800 electronic overcurrent release for comprehensive circuit protection.
  • LSIG protection provides long-time, short-time, instantaneous and earth-fault protection.
  • 130 kA ultimate short-circuit breaking capacity at 400 V AC for demanding fault levels.
  • Withdrawable construction supports efficient inspection, servicing and circuit-breaker replacement.

Key Features

  • ABB SACE Emax E3V800 circuit breaker moving part.
  • 800 A rated uninterrupted current.
  • Four-pole withdrawable configuration.
  • PR121/P-LSIG R800 electronic overcurrent release.
  • Long-time overload protection.
  • Short-time short-circuit protection.
  • Instantaneous short-circuit protection.
  • Integrated earth-fault protection.
  • 690 V AC rated operational voltage.
  • 130 kA Icu at 400 V AC.
  • 100 kA Ics at 400 V AC.
  • 85 kA short-time withstand current for 1 s.
  • 12 kV rated impulse withstand voltage.
  • Four auxiliary change-over contacts with circuit-breaker open/closed position indication.

High-Performance LSIG Protection for Low-Voltage Distribution

Air circuit breakers such as the ABB SACE Emax E3V800 provide switching, isolation and protection for important low-voltage distribution circuits. The four-pole configuration enables switching of three phase conductors and the neutral, making it suitable for electrical systems where complete four-pole isolation is required.

The PR121/P-LSIG electronic trip unit provides long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection. Combined with the E3V frame’s 130 kA ultimate breaking capacity at 400 V AC and withdrawable construction, this makes the 1SDA056554R1 particularly suitable for main incomers, feeders and critical distribution circuits requiring comprehensive protection, high fault-interruption performance and convenient maintenance.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial power distribution systems.
  • Main incomer and feeder circuit protection.
  • Three-phase systems requiring neutral switching.
  • Manufacturing and process plants.
  • Commercial and infrastructure electrical installations.
  • Power distribution centres and withdrawable switchgear assemblies.

Technical Specifications

Product group 310513-New Emax
Series SACE Emax
Order code / MPN 1SDA056554R1
Product type Air circuit breaker moving part
Frame E3V
Rated current (In) 800 A
Rated operational current (Ie) 800 A
Rated uninterrupted current (Iu) 800 A
Number of poles 4
Execution Withdrawable moving part
Current type AC
Trip unit PR121/P-LSIG R800 electronic overcurrent release
Release type Electronic
Protection functions Long-time, short-time, instantaneous and earth-fault (LSIG)
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC 130 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC 100 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 100 kA
Rated service short-circuit breaking capacity (Ics) at 400 V AC 100 kA
Rated service short-circuit breaking capacity (Ics) at 500 V AC 85 kA
Rated service short-circuit breaking capacity (Ics) at 690 V AC 85 kA
Rated short-time withstand current (Icw) 85 kA for 1 s
Short-circuit performance level V
Overload release setting range 320–800 A
Short-time delayed short-circuit release adjustment range 800–8000 A
Instantaneous short-circuit release adjustment range 1200–12000 A
Earth-fault protection Integrated
Power loss 36 W
Electrical durability at up to 440 V 12000 cycles
Electrical durability at 500–690 V 12000 cycles
Mechanical durability 20000 cycles
Auxiliary contacts 4 change-over contacts
Position indication Circuit breaker open/closed
Motor drive Optional
Standard IEC
Product dimensions (W × H × D) 558 × 461 × 396.5 mm
Product net weight 81 kg
EAN 8015644578947
HS code 85362090

Frequently Asked Questions

What is the ABB 1SDA056554R1 used for?

The ABB 1SDA056554R1 is a SACE Emax E3V800 air circuit breaker moving part used for switching and protecting low-voltage electrical distribution circuits, particularly applications requiring four-pole switching, high breaking capacity and comprehensive LSIG protection.

What is the rated current of the ABB E3V800 1SDA056554R1?

The circuit breaker moving part has a rated uninterrupted current of 800 A and is equipped with a PR121/P-LSIG R800 electronic overcurrent release.

What protection functions does the PR121/P-LSIG trip unit provide?

The PR121/P-LSIG electronic overcurrent release provides long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection.

What is the breaking capacity of the ABB E3V800 1SDA056554R1?

The E3V800 has a rated ultimate short-circuit breaking capacity of 130 kA at 400 V AC and 100 kA at 690 V AC. Its rated service short-circuit breaking capacity is 100 kA at 400 V AC and 85 kA at 690 V AC.

Is the ABB 1SDA056554R1 fixed or withdrawable?

The 1SDA056554R1 is a four-pole withdrawable moving part for the ABB SACE Emax E3V800 circuit breaker system, supporting convenient inspection, servicing and replacement within compatible switchgear.

Trusted ABB Protection for Critical Power Systems

ABB SACE Emax air circuit breakers are engineered for dependable protection and switching in demanding low-voltage power distribution systems, combining high breaking performance with electronic protection and maintainable withdrawable configurations.