1SDA056432R1 ABB E3H 2000 PR121/P-LI 2000A 3P Fixed Air Circuit Breaker

1SDA056432R1 ABB E3H 2000 PR121/P-LI 2000A 3P Fixed Air Circuit Breaker

ABB 1SDA056432R1 E3H 2000 three-pole fixed air circuit breaker rated at 2000 A with rear horizontal flat terminals and a PR121/P-LI R2000 electronic trip unit providing overload and instantaneous short-circuit protection for demanding low-voltage power distribution.

SKU: 1SDA056432R1MPN: 1SDA056432R1
Price
List Price £16,696.63 ex VAT
Your Price (ex VAT) Save 25%
£12,522.47 25% OFF
You save £4,174.16 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £12,522.47
Trade pricing is personalised to your account

Manufacturer Lead Time

£12,522.47

Why Choose the ABB E3H 2000 PR121/P-LI 2000A 3P Fixed Air Circuit Breaker?

The ABB 1SDA056432R1 is a high-performance SACE Emax E3H air circuit breaker designed for switching and protection in demanding low-voltage power distribution systems. Rated at 2000 A, this three-pole fixed circuit breaker incorporates an ABB PR121/P-LI R2000 electronic overcurrent release, providing dependable overload and instantaneous short-circuit protection.

Part of the ABB SACE Emax E3 series, the E3H 2000 combines a 2000 A continuous current rating with high short-circuit interruption capability. It provides a rated ultimate short-circuit breaking capacity of 100 kA at 400 V AC and a rated service short-circuit breaking capacity of 85 kA at 400 V AC, making it suitable for installations with substantial prospective fault currents.

The PR121/P-LI release provides long-time overload (L) and instantaneous short-circuit (I) protection. This version uses a three-pole fixed configuration with rear horizontal flat terminals and is fitted with four change-over auxiliary contacts plus circuit-breaker open/closed position indication for integration into low-voltage switchboards.

Key Advantages

  • 2000 A SACE Emax air circuit breaker for high-current low-voltage distribution.
  • E3H high-breaking-capacity performance for systems with substantial prospective fault currents.
  • PR121/P-LI electronic trip unit provides long-time overload and instantaneous short-circuit protection.
  • 100 kA ultimate short-circuit breaking capacity at 400 V AC.
  • 85 kA service short-circuit breaking capacity at 400 V AC.
  • 75 kA short-time withstand current for 1 s supports demanding distribution applications.
  • Adjustable overload protection from 800–2000 A.
  • Three-pole fixed construction with rear horizontal terminals provides a robust permanent switchboard arrangement.
  • Four change-over auxiliary contacts and open/closed indication support switchboard monitoring and control.

Key Features

  • ABB SACE Emax E3H 2000 air circuit breaker.
  • 2000 A rated uninterrupted current.
  • Three-pole configuration.
  • PR121/P-LI R2000 electronic overcurrent release.
  • LI protection: long-time overload and instantaneous short-circuit functions.
  • 690 V AC rated operational voltage.
  • 1000 V rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • 100 kA Icu at 400 V AC.
  • 85 kA Ics at 400 V AC.
  • 75 kA Icw for 1 s and 65 kA for 3 s.
  • Fixed construction with rear horizontal flat terminal connections.

High-Performance LI Protection for 2000A Power Distribution

Air circuit breakers such as the ABB E3H 2000 provide switching, isolation and automatic protection for important low-voltage distribution circuits. The PR121/P electronic release monitors circuit current and commands the breaker to open when configured overload or instantaneous short-circuit thresholds are exceeded, helping protect conductors, busbars, switchgear and connected equipment.

The combination of LI electronic protection, 100 kA Icu at 400 V AC and 75 kA short-time withstand capability for 1 s makes the 1SDA056432R1 suitable for demanding high-current distribution. Its fixed construction and rear horizontal flat terminals provide a robust arrangement for permanent installation within compatible low-voltage switchboards.

Typical Applications

  • Main incoming protection in low-voltage switchboards.
  • Industrial power distribution systems.
  • High-fault-level feeder and distribution circuits.
  • Manufacturing and process plant electrical systems.
  • Commercial and infrastructure power distribution.
  • Transformer-fed low-voltage distribution boards.
  • Generator and standby power switchboards.
  • Fixed switchgear requiring high-current LI electronic protection.

Technical Specifications

Series SACE Emax E3
ABB order code 1SDA056432R1
Product type Air circuit breaker
Frame E3
Short-circuit performance level H
Rated current (In) 2000 A
Rated uninterrupted current (Iu) 2000 A
Rated operational current (Ie) 2000 A
Number of poles 3
Current type AC
Trip unit PR121/P-LI R2000
Release type Electronic
Protection functions LI – long-time overload and instantaneous short-circuit
Overload release adjustment range 800–2000 A
Instantaneous short-circuit release adjustment range 3000–30,000 A
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC 100 kA
Rated service short-circuit breaking capacity (Ics) at 400 V AC 85 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 85 kA
Rated service short-circuit breaking capacity (Ics) at 690 V AC 85 kA
Rated short-time withstand current (Icw), 1 s 75 kA
Rated short-time withstand current (Icw), 3 s 65 kA
Power loss 130 W
Installation Fixed
Terminal connection Rear flat horizontal
Auxiliary contacts 4 change-over contacts
Position indication Open / closed
Motor operator Optional
Electrical durability at ≤440 V 9000 cycles
Electrical durability at 500–690 V 9000 cycles
Mechanical durability 20,000 cycles
Dimensions (W × H × D) 404 × 418 × 302 mm
Net weight 60 kg
Standard IEC
EAN 8015644577728
Customs tariff number 85362090
Product group 310513-New Emax

Frequently Asked Questions

What is the ABB 1SDA056432R1?

The ABB 1SDA056432R1 is a SACE Emax E3H 2000 three-pole fixed air circuit breaker rated at 2000 A and equipped with a PR121/P-LI R2000 electronic overcurrent release.

What protection functions does the PR121/P-LI provide?

The PR121/P-LI provides long-time overload (L) and instantaneous short-circuit (I) protection functions.

What is the current rating of the ABB E3H 2000 1SDA056432R1?

The circuit breaker has a rated uninterrupted current of 2000 A, with adjustable overload protection from 800–2000 A.

What is the breaking capacity of the ABB E3H 2000?

At 400 V AC, the E3H 2000 has a rated ultimate short-circuit breaking capacity of 100 kA and a rated service short-circuit breaking capacity of 85 kA.

What installation and terminal arrangement does the ABB 1SDA056432R1 use?

The 1SDA056432R1 is a three-pole fixed air circuit breaker with rear horizontal flat terminals, designed for permanent installation within compatible low-voltage switchboards.

Trusted ABB Protection for Demanding Power Systems

ABB SACE Emax air circuit breakers combine electronic overcurrent protection, high short-circuit interruption capability and robust switchboard integration for demanding low-voltage power distribution systems.