1SDA056131R1 ABB E3N2500 PR122/P-LI 2500A 3P Withdrawable Air Circuit Breaker

1SDA056131R1 ABB E3N2500 PR122/P-LI 2500A 3P Withdrawable Air Circuit Breaker

ABB 1SDA056131R1 is a SACE Emax E3N 2500 three-pole 2500 A withdrawable air circuit breaker moving part with a PR122/P-LI electronic overcurrent release for high-current low-voltage circuit protection.

SKU: 1SDA056131R1MPN: 1SDA056131R1
Price
List Price £19,486.79 ex VAT
Your Price (ex VAT) Save 25%
£14,615.09 25% OFF
You save £4,871.70 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £14,615.09
Trade pricing is personalised to your account

Manufacturer Lead Time

£14,615.09

Why Choose the ABB E3N2500 PR122/P-LI 2500A 3P Withdrawable Air Circuit Breaker?

The ABB E3N2500 PR122/P-LI, order code 1SDA056131R1, is a high-current SACE Emax air circuit breaker moving part designed for switching and protection in demanding low-voltage power distribution systems. As part of the ABB SACE Emax E3N series, this three-pole withdrawable circuit breaker is rated at 2500 A and incorporates the PR122/P-LI electronic overcurrent release.

The PR122/P-LI trip unit provides long-time overload (L) and instantaneous short-circuit (I) protection, helping protect cables, busbars, switchgear and connected equipment against sustained overcurrents and severe short-circuit faults. The electronic release combines with the E3N frame's high-current capability to provide dependable protection for substantial main distribution and feeder circuits.

This E3N2500 configuration is a three-pole withdrawable moving part intended for compatible SACE Emax switchgear. With a rated uninterrupted current of 2500 A, rated operational voltage of 690 V AC and rated ultimate short-circuit breaking capacity of 65 kA, it combines robust electrical protection with the servicing advantages of withdrawable construction.

Key Advantages

  • High-current 2500 A SACE Emax air circuit breaker moving part.
  • Advanced PR122/P electronic overcurrent release for dependable circuit protection.
  • LI protection covers long-time overload and instantaneous short-circuit conditions.
  • Three-pole configuration designed for three-phase low-voltage distribution systems.
  • Withdrawable execution supports inspection, servicing and replacement within compatible switchgear.
  • Rated ultimate short-circuit breaking capacity of 65 kA across the specified AC voltage range.

Key Features

  • ABB SACE Emax E3N 2500 air circuit breaker moving part.
  • 2500 A rated uninterrupted current.
  • Three-pole configuration.
  • PR122/P-LI electronic overcurrent release.
  • Long-time overload protection (L).
  • Instantaneous short-circuit protection (I).
  • Withdrawable / moving-part execution.
  • Rated operational voltage of 690 V AC.
  • 65 kA rated ultimate short-circuit breaking capacity at 415 V AC.
  • 65 kA rated short-time withstand current for 1 s.

Advanced LI Protection for High-Current Power Distribution

Air circuit breakers such as the ABB SACE Emax E3N2500 provide switching and protection for high-current low-voltage distribution circuits. The electronic overcurrent release monitors electrical conditions and initiates breaker operation when configured protection thresholds are exceeded, helping protect cables, busbars, switchgear and connected electrical equipment.

The PR122/P-LI release combines long-time overload and instantaneous short-circuit protection within an electronic trip unit. Together with the E3N frame's 2500 A current capability, 65 kA short-circuit performance and three-pole withdrawable construction, this configuration provides dependable protection for main distribution and high-current feeder circuits while facilitating switchboard maintenance.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial power distribution systems.
  • Manufacturing and process plant switchgear.
  • Commercial building electrical distribution.
  • Infrastructure and utility installations.
  • Main incomer and high-current feeder protection.
  • Three-phase low-voltage distribution systems.
  • Switchboards requiring withdrawable circuit breaker assemblies.

Technical Specifications

Product family SACE Emax
Series / frame E3N 2500
ABB order code 1SDA056131R1
Product type Air circuit breaker moving part
Rated current (In) 2500 A
Rated operational current (Ie) 2500 A
Rated uninterrupted current (Iu) 2500 A
Number of poles 3
Trip unit PR122/P-LI
Release type Electronic
Protection functions LI
Long-time protection L
Instantaneous protection I
Rated operational voltage 690 V AC
Rated ultimate short-circuit breaking capacity (Icu) 65 kA at 220–690 V AC
Rated service short-circuit breaking capacity (Ics) 65 kA at 220–690 V AC
Rated short-time withstand current (Icw) 65 kA for 1 s
Short-circuit performance level N
Execution Withdrawable / moving part
Standard IEC
Product group 310513-New Emax

Frequently Asked Questions

What is the ABB 1SDA056131R1?

The ABB 1SDA056131R1 is a SACE Emax E3N 2500 three-pole withdrawable air circuit breaker moving part rated at 2500 A and equipped with a PR122/P-LI electronic overcurrent release.

What is the rated current of the ABB E3N2500 PR122/P-LI?

The circuit breaker has a rated operational and uninterrupted current of 2500 A, making it suitable for high-current low-voltage power distribution applications.

What does LI protection mean on the PR122/P trip unit?

LI denotes long-time overload protection and instantaneous short-circuit protection, helping protect the electrical system against sustained overcurrents and severe short-circuit faults.

How many poles does ABB 1SDA056131R1 have?

The ABB 1SDA056131R1 is a three-pole air circuit breaker moving part designed for three-phase low-voltage power distribution systems.

Is the ABB 1SDA056131R1 fixed or withdrawable?

This model is a withdrawable moving part of the SACE Emax E3N 2500 circuit breaker system and is intended for use with compatible SACE Emax switchgear.

What is the breaking capacity of the ABB E3N2500 1SDA056131R1?

The breaker has a rated ultimate short-circuit breaking capacity of 65 kA at voltages from 220 V AC through 690 V AC and a rated short-time withstand current of 65 kA for 1 s.

Trusted by Electrical Engineers Worldwide

ABB SACE Emax air circuit breakers are widely used in demanding low-voltage power distribution systems, providing dependable high-current switching and advanced electronic protection for industrial, commercial and infrastructure installations.