1SDA056020R1 ABB E2S2000 PR122/P-LSI 2000A 3-Pole Fixed Air Circuit Breaker

1SDA056020R1 ABB E2S2000 PR122/P-LSI 2000A 3-Pole Fixed Air Circuit Breaker

ABB 1SDA056020R1 E2S2000 PR122/P-LSI is a 2000 A three-pole fixed SACE Emax air circuit breaker with an R2000 LSI electronic overcurrent release, 85 kA breaking capacity at 415 V AC and rear flat horizontal terminals for demanding low-voltage power distribution systems.

SKU: 1SDA056020R1MPN: 1SDA056020R1
Price
List Price £15,651.95 ex VAT
Your Price (ex VAT) Save 25%
£11,738.96 25% OFF
You save £3,912.99 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £11,738.96
Trade pricing is personalised to your account

Manufacturer Lead Time

£11,738.96

Why Choose the ABB E2S2000 PR122/P-LSI 2000A Air Circuit Breaker?

The ABB E2S2000 PR122/P-LSI, order code 1SDA056020R1, is a high-performance three-pole fixed air circuit breaker (ACB) designed for switching and protection in demanding low-voltage electrical distribution systems. Part of the established ABB SACE Emax series, this E2S circuit breaker combines a rated current of 2000 A with the PR122/P electronic overcurrent release for dependable protection in industrial, commercial and infrastructure power networks.

This configuration is supplied as a fixed three-pole circuit breaker with horizontal rear flat terminals. The fitted PR122/P-LSI R2000 electronic overcurrent release provides long-time, short-time and instantaneous protection functions, helping protect electrical systems against sustained overloads and short-circuit faults while supporting selective protection coordination throughout the distribution network.

The E2S performance level provides an ultimate and service short-circuit breaking capacity of 85 kA at 415 V AC and 65 kA at 690 V AC, together with a short-time withstand current of 65 kA for 1 s. Four auxiliary contacts and open/closed circuit-breaker position indication support status signalling, monitoring and integration into high-current low-voltage switchboards.

Key Advantages

  • High-performance ABB SACE Emax E2S air circuit breaker for demanding low-voltage power distribution.
  • 2000 A rated current for high-current industrial and commercial installations.
  • Three-pole fixed configuration for three-phase electrical distribution systems.
  • PR122/P-LSI electronic overcurrent release for accurate and configurable circuit protection.
  • Long-time, short-time and instantaneous protection against overload and short-circuit conditions.
  • 85 kA ultimate and service short-circuit breaking capacity at 415 V AC.
  • 65 kA short-time withstand current for 1 s for robust fault-current performance.
  • Horizontal rear flat terminals support practical integration into switchboards and power distribution assemblies.

Key Features

  • ABB SACE Emax E2S series.
  • 2000 A rated uninterrupted current.
  • Three-pole construction.
  • Fixed installation version.
  • Horizontal rear flat terminals (HR).
  • PR122/P electronic overcurrent release.
  • R2000 release rating.
  • LSI protection: long-time, short-time and instantaneous.
  • 690 V AC rated operational voltage.
  • 85 kA breaking capacity at 415 V AC.
  • 65 kA breaking capacity at 690 V AC.
  • Four auxiliary contacts plus open/closed position indication.

Advanced Protection for Low-Voltage Power Distribution

Air circuit breakers such as the ABB SACE Emax E2S2000 provide switching, isolation and protection for high-current low-voltage distribution circuits. The E2S performance class combines high short-circuit interruption capability with strong short-time withstand performance, making this breaker suitable for main distribution boards, incomers, feeders and other critical positions where substantial prospective fault currents may be present.

The PR122/P electronic overcurrent release provides LSI protection for demanding electrical networks. Long-time protection responds to sustained overload conditions, short-time protection supports selective coordination during fault events, and instantaneous protection rapidly interrupts severe short-circuit currents to help safeguard conductors, switchgear, transformers and connected electrical equipment.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial power distribution systems.
  • Main incomer and high-current feeder protection.
  • Manufacturing and process plants.
  • Commercial buildings and infrastructure installations.
  • Motor control centres and power distribution assemblies.
  • Transformer secondary and generator distribution circuits.
  • High fault-level low-voltage switchgear requiring selective overcurrent protection.

Technical Specifications

Series SACE Emax
ABB order code 1SDA056020R1
EAN 8015644573607
Product type Air circuit breaker (ACB)
Frame / performance level E2S
Short-circuit performance level S
Rated current (In) 2000 A
Rated operational current (Ie) 2000 A
Rated uninterrupted current (Iu) 2000 A
Number of poles 3
Current type AC
Installation version Fixed
Terminal configuration Rear flat horizontal terminals
Trip unit PR122/P
Overcurrent release rating R2000
Release type Electronic
Protection functions LSI
Long-time protection L
Short-time protection S
Instantaneous protection I
Overload release adjustment range 800–2000 A
Integrated ground-fault protection No
Rated operational voltage 690 V AC
Rated voltage 690 V
Rated insulation voltage 1000 V
Rated impulse withstand voltage 12 kV
Ultimate short-circuit breaking capacity (Icu) at 400 V AC 85 kA
Service short-circuit breaking capacity (Ics) at 400 V AC 85 kA
Ultimate short-circuit breaking capacity (Icu) at 415 V AC 85 kA
Service short-circuit breaking capacity (Ics) at 415 V AC 85 kA
Ultimate short-circuit breaking capacity (Icu) at 440 V AC 85 kA
Service short-circuit breaking capacity (Ics) at 440 V AC 85 kA
Ultimate short-circuit breaking capacity (Icu) at 500 V AC 65 kA
Service short-circuit breaking capacity (Ics) at 500 V AC 65 kA
Ultimate short-circuit breaking capacity (Icu) at 690 V AC 65 kA
Service short-circuit breaking capacity (Ics) at 690 V AC 65 kA
Short-time withstand current (Icw) for 1 s 65 kA
Short-time withstand current (Icw) for 3 s 50 kA
Auxiliary contacts 4
Position indication Circuit breaker open / closed
Power loss 180 W
Net weight 55 kg
Standard IEC
HS code 85362090
ABB product group 310513-New Emax

Frequently Asked Questions

What is the ABB 1SDA056020R1 used for?

The ABB 1SDA056020R1 is a 2000 A three-pole fixed air circuit breaker designed for switching and protecting high-current low-voltage electrical distribution systems.

What protection functions does the PR122/P-LSI trip unit provide?

The PR122/P-LSI electronic overcurrent release provides long-time, short-time and instantaneous protection, commonly abbreviated as LSI, helping protect electrical circuits against overload and short-circuit conditions.

What is the rated current of the ABB E2S2000 PR122/P-LSI?

The E2S2000 circuit breaker and its R2000 overcurrent release are rated at 2000 A, with an overload release adjustment range of 800–2000 A.

Is the ABB 1SDA056020R1 fixed or withdrawable?

The ABB 1SDA056020R1 is a fixed three-pole circuit breaker fitted with rear flat horizontal terminals.

What is the breaking capacity of the ABB E2S2000?

The E2S2000 provides an ultimate and service short-circuit breaking capacity of 85 kA at 415 V AC and 65 kA at 690 V AC, with a short-time withstand current of 65 kA for 1 s.

Trusted Protection for Critical Power Systems

ABB SACE Emax air circuit breakers are engineered for dependable low-voltage power distribution, combining high-current switching capability, configurable electronic protection and robust short-circuit performance for industrial, commercial and infrastructure electrical systems.