1SDA055939R1 ABB E2N 2000 PR122/P-LI 2000A 3-Pole Withdrawable Air Circuit Breaker Moving Part

1SDA055939R1 ABB E2N 2000 PR122/P-LI 2000A 3-Pole Withdrawable Air Circuit Breaker Moving Part

ABB 1SDA055939R1 is a SACE Emax E2N 2000 A three-pole withdrawable air circuit breaker moving part with a PR122/P-LI electronic overcurrent release for high-current low-voltage power distribution protection.

SKU: 1SDA055939R1MPN: 1SDA055939R1
Price
List Price £15,725.56 ex VAT
Your Price (ex VAT) Save 25%
£11,794.17 25% OFF
You save £3,931.39 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £11,794.17
Trade pricing is personalised to your account

Manufacturer Lead Time

£11,794.17

Why Choose the ABB 1SDA055939R1 E2N 2000 Air Circuit Breaker?

The ABB 1SDA055939R1 is a SACE Emax E2N 2000 withdrawable air circuit breaker moving part designed for dependable switching and protection in high-current low-voltage power distribution systems. This three-pole unit combines a 2000 A rated current with ABB's PR122/P-LI electronic overcurrent release, providing long-time overload and instantaneous short-circuit protection for demanding industrial, commercial and infrastructure installations.

As part of the ABB SACE Emax range, the E2N 2000 is engineered for protection of switchboards, transformers, generators and high-current distribution feeders. The PR122/P-LI release provides electronic LI protection, with an overload setting range of 800–2000 A and an instantaneous short-circuit release adjustment range of 3000–30000 A.

This model is supplied as the moving part of a three-pole withdrawable circuit breaker. It has a rated operational voltage of 690 V AC, an ultimate short-circuit breaking capacity of 65 kA at 400 V AC and a short-time withstand current of 55 kA for 1 s, providing robust performance for high-current switchgear applications.

Key Advantages

  • High-capacity 2000 A air circuit breaker moving part for demanding low-voltage distribution.
  • Three-pole configuration for three-phase electrical systems.
  • Withdrawable (W) construction supports convenient servicing and switchboard maintenance.
  • Advanced PR122/P-LI electronic overcurrent release.
  • LI functionality provides long-time overload and instantaneous short-circuit protection.
  • 65 kA ultimate short-circuit breaking capacity at 400 V AC for high-fault-level applications.

Key Features

  • ABB SACE Emax E2N 2000 circuit breaker moving part.
  • 2000 A rated uninterrupted current.
  • Three-pole circuit breaker configuration.
  • Withdrawable (W) version.
  • PR122/P-LI electronic trip unit.
  • Long-time overload protection.
  • Instantaneous short-circuit protection.
  • 690 V AC rated operational voltage.
  • Four change-over auxiliary contacts.
  • Circuit breaker open/closed position indication.

Reliable LI Protection for High-Current Power Distribution

Air circuit breakers such as the ABB SACE Emax E2N provide switching, isolation and automatic overcurrent protection for high-current low-voltage distribution circuits. The electronic trip unit monitors circuit current and initiates breaker operation when configured protection thresholds are exceeded, helping protect switchgear, conductors and connected electrical equipment against damaging overload and short-circuit currents.

The PR122/P-LI release gives this E2N 2000 long-time overload and instantaneous short-circuit protection. Combined with its 2000 A rating, three-pole arrangement, withdrawable construction and high short-circuit performance, the ABB 1SDA055939R1 is well suited to demanding high-current switchboard installations where maintainability and dependable circuit protection are essential.

Typical Applications

  • Industrial low-voltage switchboards and distribution panels.
  • Main incoming circuit protection.
  • High-current three-phase distribution feeders.
  • Transformer and generator protection systems.
  • Manufacturing plants and process facilities.
  • Commercial and infrastructure power distribution systems.

Technical Specifications

Series SACE Emax
ABB order code / MPN 1SDA055939R1
ABB product group 310513-New Emax
Product type Air circuit breaker moving part
Frame E2N 2000
Rated current (In) 2000 A
Rated uninterrupted current (Iu) 2000 A
Rated operational current (Ie) 2000 A
Number of poles 3
Version Withdrawable (W) moving part
Trip unit PR122/P-LI
Release type Electronic
Protection functions Long-time and instantaneous (LI)
Overload release setting range 800–2000 A
Instantaneous short-circuit release setting range 3000–30000 A
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Ultimate short-circuit breaking capacity (Icu) at 400/415 V AC 65 kA
Service short-circuit breaking capacity (Ics) at 400/415 V AC 65 kA
Ultimate short-circuit breaking capacity (Icu) at 690 V AC 55 kA
Service short-circuit breaking capacity (Ics) at 690 V AC 55 kA
Short-time withstand current (Icw), 1 s 55 kA
Short-time withstand current (Icw), 3 s 42 kA
Short-circuit performance level N
Auxiliary contacts 4 change-over contacts
Position indication Circuit breaker open / closed
Integrated earth-fault protection No
Motor drive integrated No
Motor drive optional Yes
Mechanical durability 25,000 cycles
Electrical durability at ≤440 V 10,000 cycles
Electrical durability at 500–690 V 8,000 cycles
Power loss 330 W
Standard IEC
Product net dimensions (W × H × D) 324 × 461 × 396.5 mm
Product net weight 49 kg
EAN 8015644572792

Frequently Asked Questions

What is the ABB 1SDA055939R1?

The ABB 1SDA055939R1 is the moving part of a SACE Emax E2N 2000 three-pole withdrawable air circuit breaker, rated at 2000 A and equipped with a PR122/P-LI electronic overcurrent release.

What protection functions does the PR122/P-LI release provide?

The PR122/P-LI provides long-time overload and instantaneous short-circuit protection, collectively identified as LI protection.

Is the ABB 1SDA055939R1 fixed or withdrawable?

The ABB 1SDA055939R1 is a withdrawable (W) version supplied as the moving part of the E2N 2000 circuit breaker system.

What is the rated current of the ABB 1SDA055939R1?

The circuit breaker moving part has a rated uninterrupted current of 2000 A and a rated operational voltage of 690 V AC.

What is the breaking capacity of the ABB E2N 2000?

The E2N 2000 provides an ultimate short-circuit breaking capacity of 65 kA at 400/415 V AC and 55 kA at 690 V AC.

Does the ABB 1SDA055939R1 provide earth-fault protection?

No. This model uses the PR122/P-LI release for long-time and instantaneous protection. Earth-fault protection is not integrated into this LI configuration.