ABB 1SDA055880R1 E2N1250 is a 1250 A four-pole withdrawable SACE Emax air circuit breaker moving part with PR121/P-LI electronic protection, 690 V AC operational voltage and 65 kA breaking capacity at 400 V AC.

SKU: 1SDA055880R1MPN: 1SDA055880R1
Price
List Price £13,300.16 ex VAT
Your Price (ex VAT) Save 25%
£9,975.12 25% OFF
You save £3,325.04 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £9,975.12
Trade pricing is personalised to your account

Manufacturer Lead Time

£9,975.12

Why Choose the ABB E2N1250 PR121/P-LI 1250A 4-Pole Withdrawable Air Circuit Breaker?

The ABB 1SDA055880R1 is a SACE Emax E2N air circuit breaker (ACB) moving part designed for switching and protection in demanding low-voltage electrical distribution systems. Rated at 1250 A, this four-pole withdrawable circuit breaker moving part is equipped with the PR121/P-LI R1250 electronic overcurrent release for reliable overload and instantaneous short-circuit protection.

As part of the ABB SACE Emax / New Emax range, the E2N1250 combines high short-circuit performance with electronic circuit protection for industrial and commercial power distribution. The PR121/P-LI release provides long-time and instantaneous protection functions, helping protect cables, busbars and connected electrical equipment against sustained overloads and severe short-circuit currents.

The E2N1250 PR121/P-LI is a four-pole withdrawable moving part with a rated uninterrupted current of 1250 A and a rated operational voltage of 690 V AC. Its N performance level provides a rated ultimate short-circuit breaking capacity of 65 kA at 400 V AC and 55 kA at 690 V AC, while the withdrawable construction supports servicing and replacement within compatible SACE Emax switchgear assemblies.

Key Advantages

  • High-performance 1250 A SACE Emax air circuit breaker moving part.
  • Four-pole configuration suitable for three-phase four-wire distribution systems.
  • Electronic PR121/P-LI R1250 overcurrent release.
  • LI protection provides long-time overload and instantaneous short-circuit protection.
  • 65 kA ultimate and service short-circuit breaking capacity at 400 V AC.
  • 55 kA ultimate and service short-circuit breaking capacity at 690 V AC.
  • Withdrawable moving-part construction supports maintainable switchboard installations.
  • Four auxiliary contacts with circuit-breaker open/closed position indication.

Key Features

  • ABB SACE Emax E2N1250 air circuit breaker moving part.
  • 1250 A rated uninterrupted current.
  • Four-pole configuration.
  • Withdrawable moving-part construction.
  • PR121/P-LI R1250 electronic overcurrent release.
  • Long-time and instantaneous LI protection functions.
  • 690 V AC rated operational voltage.
  • 1000 V rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • 65 kA Icu/Ics at 400 V AC.
  • 55 kA Icu/Ics at 690 V AC.
  • 55 kA short-time withstand current for 1 s.

Reliable Circuit Protection for High-Fault-Level Four-Wire Distribution

Air circuit breakers such as the ABB E2N1250 provide switching, isolation and protection for high-current low-voltage distribution circuits. The four-pole configuration is particularly suitable for three-phase four-wire systems, while the withdrawable architecture allows the circuit breaker moving part to be disconnected from its corresponding fixed part for inspection, servicing or replacement.

The PR121/P-LI electronic release provides long-time protection against sustained overload conditions and instantaneous protection against severe short-circuit currents. Combined with the E2N's high short-circuit interruption capability, this makes the 1SDA055880R1 suitable for demanding industrial and commercial distribution systems with elevated prospective fault currents.

Typical Applications

  • Industrial low-voltage switchboards and distribution panels.
  • Three-phase four-wire electrical distribution systems.
  • Main incoming circuit protection.
  • High-fault-level feeder protection.
  • Withdrawable switchgear assemblies.
  • Busbar and power distribution applications.
  • Transformer secondary distribution systems.
  • Manufacturing, commercial and infrastructure installations.

Technical Specifications

Series SACE Emax / New Emax
ABB order code 1SDA055880R1
Product group 310513-New Emax
Product type Air circuit breaker moving part
Rated current (In) 1250 A
Rated uninterrupted current (Iu) 1250 A
Rated operational current (Ie) 1250 A
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Number of poles 4
Current type AC
Installation Withdrawable
Configuration Moving part (MP)
Trip unit PR121/P-LI R1250
Release type Electronic
Protection functions Long-time and instantaneous (LI)
Instantaneous short-circuit release adjustment 1875–18750 A
Short-circuit performance level N
Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC 65 kA
Rated service short-circuit breaking capacity (Ics) at 400 V AC 65 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 55 kA
Rated service short-circuit breaking capacity (Ics) at 690 V AC 55 kA
Rated short-time withstand current (Icw) 55 kA for 1 s; 42 kA for 3 s
Ground-fault protection No
Protection rating IP2X
Power loss 130 W
Electrical durability 15,000 cycles at ≤440 V AC; 15,000 cycles at 500–690 V AC
Mechanical durability 25,000 cycles
Auxiliary contacts 4 (2 normally open and 2 normally closed)
Position indication Open / closed
Trip indication Yes
Motor operating mechanism Optional
Dimensions (W × H × D) 414 × 461 × 396.5 mm
Net weight 61 kg
Package gross weight 73 kg
EAN 8015644572204

Frequently Asked Questions

What is the ABB 1SDA055880R1 used for?

The ABB 1SDA055880R1 is a 1250 A four-pole withdrawable SACE Emax air circuit breaker moving part used for switching and protecting high-current low-voltage electrical distribution circuits.

What current rating does the ABB E2N1250 1SDA055880R1 have?

The circuit breaker moving part has a rated uninterrupted current of 1250 A.

What protection unit is fitted to the ABB 1SDA055880R1?

The breaker is fitted with an ABB PR121/P-LI R1250 electronic overcurrent release, providing long-time overload and instantaneous short-circuit protection.

What is the breaking capacity of the ABB E2N1250?

The E2N1250 provides an ultimate and service short-circuit breaking capacity of 65 kA at 400 V AC and 55 kA at 690 V AC.

Is the ABB 1SDA055880R1 fixed or withdrawable?

The 1SDA055880R1 is a four-pole withdrawable moving part designed for connection through the corresponding ABB SACE Emax fixed part in a compatible switchgear assembly.

Trusted ABB Power Distribution Technology

ABB SACE Emax air circuit breakers are designed for dependable switching and protection in demanding low-voltage power distribution systems, combining high short-circuit performance, electronic protection and flexible withdrawable switchgear integration.