1SDA055692R1 ABB E1B1600 PR122/P-LSI 1600A 4P Withdrawable Air Circuit Breaker

1SDA055692R1 ABB E1B1600 PR122/P-LSI 1600A 4P Withdrawable Air Circuit Breaker

ABB 1SDA055692R1 SACE Emax E1B1600 four-pole withdrawable air circuit breaker moving part rated at 1600 A with a PR122/P-LSI electronic trip unit providing LSI protection for low-voltage power distribution systems.

SKU: 1SDA055692R1MPN: 1SDA055692R1
Price
List Price £15,660.21 ex VAT
Your Price (ex VAT) Save 25%
£11,745.16 25% OFF
You save £3,915.05 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £11,745.16
Trade pricing is personalised to your account

Manufacturer Lead Time

£11,745.16

Why Choose the ABB E1B1600 PR122/P-LSI 1600A 4P Withdrawable Air Circuit Breaker?

The ABB E1B1600 PR122/P-LSI, order code 1SDA055692R1, is a high-performance SACE Emax air circuit breaker moving part designed for switching and protection in low-voltage power distribution systems. Rated at 1600 A, this four-pole unit combines the E1B breaker frame with the PR122/P-LSI electronic overcurrent release for reliable protection of high-current electrical installations.

This model is supplied as a withdrawable moving part (W MP) for use with the corresponding ABB Emax E1 fixed part. The withdrawable configuration enables convenient isolation and removal of the breaker for inspection, servicing or replacement, making it particularly suitable for industrial switchboards where maintainability and continuity of service are important.

The PR122/P-LSI electronic trip unit provides long-time overload, short-time short-circuit and instantaneous short-circuit protection. With a rated uninterrupted current of 1600 A, a rated operational voltage of 690 V AC and an ultimate short-circuit breaking capacity of 42 kA at 380–415 V AC, the E1B1600 provides dependable protection for demanding industrial and commercial power distribution systems.

Key Advantages

  • Heavy-duty ABB SACE Emax air circuit breaker for low-voltage power distribution.
  • 1600 A rated uninterrupted current for high-current electrical installations.
  • Four-pole withdrawable configuration for three-phase systems requiring neutral switching.
  • Advanced PR122/P-LSI electronic overcurrent release.
  • Provides long-time, short-time and instantaneous protection.
  • 42 kA ultimate breaking capacity at 380–415 V AC.
  • Withdrawable construction supports efficient inspection, maintenance and replacement.

Key Features

  • ABB SACE Emax E1B series.
  • 1600 A rated uninterrupted current.
  • Four-pole (4P) construction.
  • Withdrawable moving part (W MP) configuration.
  • PR122/P-LSI electronic overcurrent release.
  • LSI protection functions: long-time, short-time and instantaneous protection.
  • 690 V AC rated operational voltage.
  • 42 kA Icu at 380–415 V AC.
  • 42 kA Icw for 1 s.
  • 1000 V rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • Designed for installation with the corresponding E1 withdrawable fixed part.

Reliable Protection for Low-Voltage Power Distribution

Air circuit breakers such as the ABB SACE Emax E1B1600 provide switching and protection for high-current low-voltage distribution circuits. The withdrawable arrangement enables the breaker moving part to be separated from its corresponding fixed part, supporting efficient isolation, inspection and maintenance in switchboards where service continuity is a priority.

The PR122/P-LSI electronic trip unit provides coordinated protection against overloads and short circuits through its long-time, short-time and instantaneous protection functions. Combined with the four-pole E1B platform, it provides a robust solution for main incomers, feeders and distribution circuits requiring high breaking capacity and maintainable switchgear.

Typical Applications

  • Industrial low-voltage switchboards.
  • Main incoming power distribution circuits.
  • High-current feeder protection.
  • Three-phase distribution systems requiring neutral switching.
  • Manufacturing and process plants.
  • Commercial and infrastructure power systems.

Technical Specifications

Series SACE Emax
Order code 1SDA055692R1
Product type Air circuit breaker moving part
Frame / sub-type E1B
Rated current 1600 A
Rated uninterrupted current 1600 A
Number of poles 4P
Version Withdrawable
Configuration Moving part (W MP)
Trip unit PR122/P-LSI
Release type Electronic
Protection functions Long-time, short-time and instantaneous
Rated operational voltage 690 V AC
Rated insulation voltage 1000 V
Rated impulse withstand voltage 12 kV
Rated ultimate short-circuit breaking capacity (Icu) at 380–415 V AC 42 kA
Rated service short-circuit breaking capacity (Ics) at 380–415 V AC 42 kA
Rated short-time withstand current (Icw) 42 kA for 1 s; 36 kA for 3 s
Short-circuit performance level B
Current type AC
Standard IEC
Mechanical durability 25,000 cycles
Dimensions (H × W × D) 461 × 414 × 396.5 mm
Net weight 54 kg
EAN 8015644570323

Frequently Asked Questions

What is the ABB 1SDA055692R1?

It is an ABB SACE Emax E1B 1600 A four-pole withdrawable air circuit breaker moving part equipped with a PR122/P-LSI electronic overcurrent release.

What is the rated current of the ABB E1B1600 1SDA055692R1?

The circuit breaker has a rated uninterrupted current of 1600 A.

What protection does the PR122/P-LSI trip unit provide?

The PR122/P-LSI provides long-time, short-time and instantaneous protection, commonly identified as LSI protection.

What is the breaking capacity of this E1B circuit breaker?

The E1B configuration has a rated ultimate short-circuit breaking capacity of 42 kA at 380–415 V AC.

Is the ABB 1SDA055692R1 fixed or withdrawable?

The 1SDA055692R1 is a withdrawable moving part designed for installation with the corresponding fixed part of an ABB SACE Emax circuit-breaker assembly.

Trusted by Power Distribution Professionals Worldwide

ABB SACE Emax air circuit breakers are engineered for dependable switching and protection in demanding low-voltage power distribution systems, combining high-current performance, advanced electronic protection and maintainable withdrawable switchgear configurations.