Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA054579R1 is a SACE Tmax T5H 400 fixed three-pole MCCB breaking part with front terminals, a 400 A rated uninterrupted current and 70 kA ultimate and service short-circuit breaking capacity at 400/415 V AC.
£901.13
The ABB T5H 400 Breaking Part 3P F F, order code 1SDA054579R1, is a fixed three-pole breaking unit for the ABB SACE Tmax T5 moulded case circuit breaker platform. Designed as the switching and fault-interruption section of a configurable Tmax T5 assembly, it provides a 400 A rated uninterrupted current and front-terminal construction for integration into industrial power-distribution equipment.
The T5H designation identifies the H short-circuit performance level. This breaking unit provides an ultimate and service short-circuit breaking capacity of 70 kA at 400/415 V AC, with further ratings of 65 kA at 440 V AC, 50 kA at 500 V AC and 40 kA at 690 V AC.
With a rated operational voltage of up to 690 V AC and 750 V DC, together with 1000 V insulation voltage and 8 kV impulse withstand voltage, the 1SDA054579R1 provides a robust foundation for demanding industrial distribution applications. Its fixed three-pole construction is designed for use with compatible ABB Tmax T5 protection releases and accessories.
The ABB T5H 400 breaking part provides the current-carrying, switching and fault-interruption functions within a compatible Tmax T5 circuit breaker configuration. The modular Tmax design allows the breaking unit to be combined with an appropriate protection release so that the completed assembly can be configured for the overload and short-circuit protection requirements of the installation.
The H performance level delivers substantial fault-interruption capability, including 70 kA at 400/415 V AC and 40 kA at 690 V AC. Together with its 400 A current rating, fixed three-pole construction and front terminals, the 1SDA054579R1 is well suited to demanding industrial switchboards and distribution systems with high prospective fault currents.
| Series | SACE Tmax T5 |
|---|---|
| Order code | 1SDA054579R1 |
| EAN | 8015644556778 |
| Product type | MCCB breaking part |
| Frame | T5 400 |
| Short-circuit performance level | H |
| Rated uninterrupted current (Iu) | 400 A |
| Number of poles | 3 |
| Rated operational voltage | up to 690 V AC / 750 V DC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Icu / Ics at 220–230 V AC | 100 kA / 100 kA |
| Icu / Ics at 380–415 V AC | 70 kA / 70 kA |
| Icu / Ics at 440 V AC | 65 kA / 65 kA |
| Icu / Ics at 500 V AC | 50 kA / 50 kA |
| Icu / Ics at 690 V AC | 40 kA / 40 kA |
| DC breaking capacity at 250 V DC | 70 kA with 2 poles in series |
| DC breaking capacity at 500 V DC | 50 kA with 2 poles in series |
| DC breaking capacity at 750 V DC | 36 kA with 3 poles in series |
| Rated short-time withstand current (Icw) | 5 kA for 1 s |
| Mounting | Fixed |
| Terminal position | Front |
| Operating mechanism | Toggle handle |
| Integrated earth-leakage protection | No |
| Integrated motor operator | No |
| Optional motor operator | Yes |
| Protection rating | IP20 |
| Standard | IEC |
The ABB 1SDA054579R1 is a T5H 400 fixed three-pole breaking part with front terminals for the ABB SACE Tmax T5 moulded case circuit breaker platform.
The T5H 400 breaking unit has a rated uninterrupted current of 400 A.
The T5H 400 provides both an ultimate short-circuit breaking capacity and service short-circuit breaking capacity of 70 kA at 400 V AC.
At 690 V AC, the T5H 400 has an ultimate and service short-circuit breaking capacity of 40 kA.
The breaking unit has a three-pole configuration and is designed for fixed installation with front terminals.
Yes. The breaking unit is rated for operation up to 750 V DC, with the applicable poles connected in series according to the system voltage and ABB installation requirements.
ABB SACE Tmax circuit breaker components are used in demanding industrial and commercial power-distribution systems worldwide, providing robust fault interruption, configurable protection and dependable performance for critical electrical installations.
We use cookies