1SDA054379R1 ABB T5L400 PR222DS/P-LSIG 400 A 4-Pole MCCB

1SDA054379R1 ABB T5L400 PR222DS/P-LSIG 400 A 4-Pole MCCB

ABB 1SDA054379R1 SACE Tmax T5L400 fixed four-pole 400 A moulded case circuit breaker with PR222DS/P-LSIG electronic trip unit, adjustable LSIG protection and 120 kA breaking capacity at 380–415 V AC.

SKU: 1SDA054379R1MPN: 1SDA054379R1
Price
List Price £6,483.81 ex VAT
Your Price (ex VAT) Save 25%
£4,862.86 25% OFF
You save £1,620.95 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £4,862.86
Trade pricing is personalised to your account

Manufacturer Lead Time

£4,862.86

Why Choose the ABB T5L400 PR222DS/P-LSIG 400 A 1SDA054379R1 Circuit Breaker?

The ABB 1SDA054379R1 is a high-performance SACE Tmax T5L 400 moulded case circuit breaker (MCCB) designed for reliable protection and isolation of demanding low-voltage electrical distribution systems. Configured as a fixed four-pole breaker with front terminals, it combines a 400 A rated current with ABB's PR222DS/P-LSIG electronic trip unit.

Part of the proven ABB SACE Tmax T5 series, the T5L400 provides comprehensive electronic LSIG protection, covering long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault conditions. The adjustable electronic release enables protection characteristics to be coordinated with cables, downstream equipment and other protective devices in industrial and commercial distribution networks.

The PR222DS/P-LSIG release provides a 160–400 A overload adjustment range, a 240–4,000 A short-time delayed short-circuit adjustment range and a 600–4,800 A instantaneous short-circuit adjustment range. Earth-fault protection is adjustable from 0.2–1 × In, while the neutral setting can be selected as OFF, 50% or 100%. Combined with a 120 kA ultimate breaking capacity at 380–415 V AC, this makes the 1SDA054379R1 a capable solution for demanding four-pole power distribution systems.

Key Advantages

  • High-performance ABB SACE Tmax T5L 400 moulded case circuit breaker.
  • 400 A rated current for substantial industrial and commercial loads.
  • Four-pole configuration for multipole low-voltage distribution systems.
  • PR222DS/P-LSIG electronic trip unit for precise and adjustable circuit protection.
  • LSIG protection functions cover overload, short-time, instantaneous and earth-fault conditions.
  • 160–400 A overload adjustment range for flexible protection coordination.
  • Selectable OFF, 50% or 100% neutral setting.
  • 120 kA ultimate breaking capacity at 380–415 V AC for high-fault-level installations.
  • Fixed mounting with front terminals for straightforward switchboard integration.

Key Features

  • ABB SACE Tmax T5L 400 circuit breaker platform.
  • 400 A rated current.
  • 4-pole construction.
  • PR222DS/P-LSIG solid-state electronic release.
  • Long-time overload protection.
  • Short-time delayed short-circuit protection.
  • Instantaneous short-circuit protection.
  • Adjustable earth-fault protection.
  • Adjustable overload protection from 160–400 A.
  • Adjustable short-time protection from 240–4,000 A.
  • Adjustable instantaneous protection from 600–4,800 A.
  • Earth-fault adjustment from 0.2–1 × In.
  • 120 kA Icu at 380–415 V AC.
  • Fixed circuit breaker configuration with front terminals.

Reliable Electronic Protection for Power Distribution

The ABB SACE Tmax T5L platform is designed for demanding low-voltage power distribution where high breaking performance and flexible protection settings are important. With a 400 A frame and rated current, the 1SDA054379R1 provides substantial circuit capacity while allowing protection settings to be coordinated with cables, downstream equipment and other protective devices.

Its PR222DS/P-LSIG electronic trip unit addresses long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault conditions. The combination of adjustable LSIG protection, selectable neutral settings and high interruption capability provides comprehensive protection and coordination for industrial and commercial four-pole electrical distribution networks.

Typical Applications

  • Industrial low-voltage power distribution systems.
  • Main and sub-distribution switchboards.
  • Three-phase four-wire electrical distribution panels.
  • Manufacturing and process installations.
  • Commercial and infrastructure power distribution.
  • Applications requiring adjustable electronic earth-fault protection.

Technical Specifications

Series SACE Tmax T5
ABB order code 1SDA054379R1
Product group 310511-T-Max T4 - T8
Product type Moulded case circuit breaker (MCCB)
Frame T5 400
Performance level L
Rated current (In) 400 A
Number of poles 4
Trip unit PR222DS/P-LSIG electronic release
Protection functions LSIG — long-time, short-time, instantaneous and earth fault
Overload protection adjustment 160–400 A
Short-time delayed short-circuit adjustment 240–4,000 A
Instantaneous short-circuit adjustment 600–4,800 A
Earth-fault protection adjustment 0.2–1 × In
Neutral setting OFF / 50% / 100%
Rated operational voltage 690 V AC
Ultimate breaking capacity (Icu) at 220/230 V AC 200 kA
Ultimate breaking capacity (Icu) at 380/415 V AC 120 kA
Ultimate breaking capacity (Icu) at 440 V AC 100 kA
Ultimate breaking capacity (Icu) at 500 V AC 85 kA
Ultimate breaking capacity (Icu) at 690 V AC 70 kA
Mounting type Fixed
Terminal type Front terminals
Electrical durability 7,000 cycles
Mechanical durability 20,000 cycles
Dimensions (H × W × D) 205 × 186 × 103.5 mm
Weight approx. 4.7 kg
EAN 8015644554774

Frequently Asked Questions

What is the ABB 1SDA054379R1 used for?

The ABB 1SDA054379R1 is a 400 A four-pole electronic moulded case circuit breaker designed to protect low-voltage electrical distribution systems against overload, short-circuit and earth-fault conditions.

What is the current rating of the ABB T5L400 1SDA054379R1?

The breaker has a rated current of 400 A and uses the ABB SACE Tmax T5L 400 frame with a PR222DS/P-LSIG electronic trip unit.

What protection does the PR222DS/P-LSIG trip unit provide?

The PR222DS/P-LSIG provides LSIG protection comprising long-time overload, short-time delayed short-circuit, instantaneous short-circuit and adjustable earth-fault protection.

What are the protection adjustment ranges of the ABB 1SDA054379R1?

The electronic release provides an overload adjustment range of 160–400 A, a short-time delayed short-circuit range of 240–4,000 A, an instantaneous short-circuit range of 600–4,800 A and earth-fault protection adjustable from 0.2–1 × In.

How is the ABB 1SDA054379R1 installed?

The 1SDA054379R1 is a fixed four-pole circuit breaker with front terminals, designed for integration into low-voltage switchboards and electrical distribution panels.

Trusted Protection from ABB

ABB SACE Tmax moulded case circuit breakers combine high interruption performance with flexible electronic LSIG protection, providing dependable overload, short-circuit and earth-fault protection for demanding industrial and commercial low-voltage distribution systems.