Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA054379R1 SACE Tmax T5L400 fixed four-pole 400 A moulded case circuit breaker with PR222DS/P-LSIG electronic trip unit, adjustable LSIG protection and 120 kA breaking capacity at 380–415 V AC.
£4,862.86
The ABB 1SDA054379R1 is a high-performance SACE Tmax T5L 400 moulded case circuit breaker (MCCB) designed for reliable protection and isolation of demanding low-voltage electrical distribution systems. Configured as a fixed four-pole breaker with front terminals, it combines a 400 A rated current with ABB's PR222DS/P-LSIG electronic trip unit.
Part of the proven ABB SACE Tmax T5 series, the T5L400 provides comprehensive electronic LSIG protection, covering long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault conditions. The adjustable electronic release enables protection characteristics to be coordinated with cables, downstream equipment and other protective devices in industrial and commercial distribution networks.
The PR222DS/P-LSIG release provides a 160–400 A overload adjustment range, a 240–4,000 A short-time delayed short-circuit adjustment range and a 600–4,800 A instantaneous short-circuit adjustment range. Earth-fault protection is adjustable from 0.2–1 × In, while the neutral setting can be selected as OFF, 50% or 100%. Combined with a 120 kA ultimate breaking capacity at 380–415 V AC, this makes the 1SDA054379R1 a capable solution for demanding four-pole power distribution systems.
The ABB SACE Tmax T5L platform is designed for demanding low-voltage power distribution where high breaking performance and flexible protection settings are important. With a 400 A frame and rated current, the 1SDA054379R1 provides substantial circuit capacity while allowing protection settings to be coordinated with cables, downstream equipment and other protective devices.
Its PR222DS/P-LSIG electronic trip unit addresses long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault conditions. The combination of adjustable LSIG protection, selectable neutral settings and high interruption capability provides comprehensive protection and coordination for industrial and commercial four-pole electrical distribution networks.
| Series | SACE Tmax T5 |
|---|---|
| ABB order code | 1SDA054379R1 |
| Product group | 310511-T-Max T4 - T8 |
| Product type | Moulded case circuit breaker (MCCB) |
| Frame | T5 400 |
| Performance level | L |
| Rated current (In) | 400 A |
| Number of poles | 4 |
| Trip unit | PR222DS/P-LSIG electronic release |
| Protection functions | LSIG — long-time, short-time, instantaneous and earth fault |
| Overload protection adjustment | 160–400 A |
| Short-time delayed short-circuit adjustment | 240–4,000 A |
| Instantaneous short-circuit adjustment | 600–4,800 A |
| Earth-fault protection adjustment | 0.2–1 × In |
| Neutral setting | OFF / 50% / 100% |
| Rated operational voltage | 690 V AC |
| Ultimate breaking capacity (Icu) at 220/230 V AC | 200 kA |
| Ultimate breaking capacity (Icu) at 380/415 V AC | 120 kA |
| Ultimate breaking capacity (Icu) at 440 V AC | 100 kA |
| Ultimate breaking capacity (Icu) at 500 V AC | 85 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 70 kA |
| Mounting type | Fixed |
| Terminal type | Front terminals |
| Electrical durability | 7,000 cycles |
| Mechanical durability | 20,000 cycles |
| Dimensions (H × W × D) | 205 × 186 × 103.5 mm |
| Weight | approx. 4.7 kg |
| EAN | 8015644554774 |
The ABB 1SDA054379R1 is a 400 A four-pole electronic moulded case circuit breaker designed to protect low-voltage electrical distribution systems against overload, short-circuit and earth-fault conditions.
The breaker has a rated current of 400 A and uses the ABB SACE Tmax T5L 400 frame with a PR222DS/P-LSIG electronic trip unit.
The PR222DS/P-LSIG provides LSIG protection comprising long-time overload, short-time delayed short-circuit, instantaneous short-circuit and adjustable earth-fault protection.
The electronic release provides an overload adjustment range of 160–400 A, a short-time delayed short-circuit range of 240–4,000 A, an instantaneous short-circuit range of 600–4,800 A and earth-fault protection adjustable from 0.2–1 × In.
The 1SDA054379R1 is a fixed four-pole circuit breaker with front terminals, designed for integration into low-voltage switchboards and electrical distribution panels.
ABB SACE Tmax moulded case circuit breakers combine high interruption performance with flexible electronic LSIG protection, providing dependable overload, short-circuit and earth-fault protection for demanding industrial and commercial low-voltage distribution systems.
We use cookies