ABB 1SDA054312R1 T4L 250 MA is a 200 A three-pole fixed moulded case circuit breaker for motor protection with front terminals, an adjustable 1,200–2,800 A magnetic release and a 120 kA ultimate breaking capacity at 380–415 V AC.

SKU: 1SDA054312R1MPN: 1SDA054312R1
Price
List Price £2,286.08 ex VAT
Your Price (ex VAT) Save 25%
£1,714.56 25% OFF
You save £571.52 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,714.56
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,714.56

Why Choose the ABB T4L 250 MA 200-2800 3P F F Circuit Breaker?

The ABB 1SDA054312R1 is a high-performance SACE Tmax T4L moulded case circuit breaker (MCCB) for motor protection, designed to provide reliable short-circuit protection and switching in industrial low-voltage electrical systems. Part of the proven ABB SACE Tmax T4 series, this three-pole circuit breaker combines a 250 A frame with a 200 A MA magnetic-only trip unit.

The MA release provides instantaneous magnetic short-circuit protection without thermal overload protection, making it particularly suitable for motor circuits where overload protection is provided separately by an overload relay or electronic motor protection device. Its adjustable magnetic release operates over a range of 1,200–2,800 A, allowing the protection threshold to accommodate motor starting currents while providing rapid interruption during severe short-circuit conditions.

With a rated current of 200 A, three-pole construction, fixed installation and front terminals, the T4L 250 MA 200-2800 is designed for integration into motor control centres, industrial switchboards and machinery panels. The T4L performance level provides an ultimate short-circuit breaking capacity of 120 kA at 380–415 V AC, delivering robust fault protection for demanding industrial motor applications.

Key Advantages

  • High-performance ABB SACE Tmax T4L motor-protection circuit breaker.
  • 200 A rated current for higher-current industrial motor circuits.
  • Three-pole configuration suitable for three-phase motor applications.
  • MA magnetic-only trip unit designed for short-circuit protection.
  • Adjustable instantaneous magnetic protection from 1,200–2,800 A.
  • High ultimate short-circuit breaking capacity of 120 kA at 380–415 V AC.
  • 690 V AC / 750 V DC rated operational voltage.
  • Fixed installation with front terminals for straightforward switchboard and motor control centre integration.

Key Features

  • ABB SACE Tmax T4 series.
  • T4L 250 frame with L short-circuit performance level.
  • 200 A rated current.
  • 250 A rated uninterrupted frame current.
  • 3-pole circuit breaker configuration.
  • MA magnetic-only release for short-circuit protection.
  • 1,200–2,800 A adjustable instantaneous magnetic trip range.
  • 120 kA Icu at 380–415 V AC.
  • 1,000 V rated insulation voltage.
  • 8 kV rated impulse withstand voltage.
  • Fixed circuit-breaker construction with front terminals.
  • Designed for motor circuits using separate overload protection.

Reliable Short-Circuit Protection for Industrial Motors

Magnetic-only moulded case circuit breakers such as the ABB SACE Tmax T4L MA are designed for motor circuits where overload protection is handled by a separate protective device. The MA release responds rapidly to high short-circuit currents while its adjustable threshold allows the breaker to accommodate the temporary inrush currents associated with motor starting.

The 1,200–2,800 A magnetic adjustment range provides flexibility when coordinating the 1SDA054312R1 with motor starters, contactors and overload protection devices. Combined with the T4L's 120 kA breaking capacity at 380–415 V AC, this makes the breaker well suited to demanding industrial motor control centres and machinery installations where high prospective fault currents may be present.

Typical Applications

  • Three-phase industrial motor protection.
  • Motor control centres and starter assemblies.
  • Pumps, fans and compressor motor circuits.
  • Conveyors and material handling equipment.
  • Manufacturing and process machinery.
  • Industrial switchboards and control panels.
  • Motor circuits using separate overload relays.
  • Installations with high prospective short-circuit currents.

Technical Specifications

Series SACE Tmax T4
ABB order code 1SDA054312R1
Product group 310511-T-Max T4 - T8
Product type Moulded case circuit breaker (MCCB) for motor protection
Frame T4 250
Short-circuit performance level L
Rated current (In) 200 A
Rated uninterrupted current (Iu) 250 A
Number of poles 3P
Trip unit MA magnetic-only release
Instantaneous magnetic trip range (I3) 1,200–2,800 A
Rated operational voltage 690 V AC / 750 V DC
Rated insulation voltage (Ui) 1,000 V
Rated impulse withstand voltage (Uimp) 8 kV
Ultimate short-circuit breaking capacity (Icu) at 220–230 V AC 200 kA
Ultimate short-circuit breaking capacity (Icu) at 380–415 V AC 120 kA
Ultimate short-circuit breaking capacity (Icu) at 440 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 500 V AC 85 kA
Ultimate short-circuit breaking capacity (Icu) at 690 V AC 70 kA
Mounting type Fixed
Terminal type Front terminals
Electrical durability 8,000 operating cycles
Mechanical durability 20,000 operating cycles
Power loss 9.9 W per pole at rated operating conditions
Dimensions (H × W × D) 205 × 105 × 103.5 mm
Net weight approx. 2.35 kg
Standards IEC 60947
EAN 8015644554095

Frequently Asked Questions

What is the ABB 1SDA054312R1 used for?

The ABB 1SDA054312R1 is a three-pole moulded case circuit breaker for motor protection, providing adjustable magnetic short-circuit protection for industrial motor circuits.

What is the rated current of the ABB T4L 250 MA 1SDA054312R1?

The circuit breaker has a rated current of 200 A and is built on the ABB SACE Tmax T4 250 A frame.

What is the magnetic trip range of the ABB 1SDA054312R1?

The MA release provides an adjustable instantaneous magnetic trip range of 1,200–2,800 A, allowing short-circuit protection to be coordinated with motor starting characteristics.

Does the ABB T4L 250 MA provide thermal overload protection?

No. The MA trip unit is magnetic-only and provides short-circuit protection, so motor overload protection should be provided by a suitable separate overload relay or motor protection device.

What breaking capacity does the ABB 1SDA054312R1 provide?

The T4L circuit breaker provides an ultimate short-circuit breaking capacity of 120 kA at 380–415 V AC, making it suitable for demanding industrial motor circuits with high prospective fault currents.

Trusted ABB Protection for Industrial Motor Systems

ABB SACE Tmax motor-protection circuit breakers provide dependable short-circuit protection for industrial motor circuits, combining adjustable magnetic releases, compact construction and high breaking capacity for motor control centres, machinery and demanding automation applications.