Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA054311R1 T4L 250 MA is a 160 A three-pole fixed moulded case circuit breaker for motor protection with front terminals, an adjustable 960–2,240 A magnetic release and a 120 kA ultimate breaking capacity at 380–415 V AC.
£1,298.09
The ABB 1SDA054311R1 is a high-performance SACE Tmax T4L moulded case circuit breaker (MCCB) for motor protection, designed to provide reliable short-circuit protection and switching in industrial low-voltage electrical systems. Part of the proven ABB SACE Tmax T4 series, this three-pole circuit breaker combines a 250 A frame with a 160 A MA magnetic-only trip unit.
Unlike a conventional thermomagnetic MCCB, the MA release provides magnetic short-circuit protection without thermal overload protection, making it particularly suitable for motor circuits where overload protection is provided separately by a motor overload relay or electronic motor protection device. The adjustable instantaneous magnetic release has a setting range of 960–2,240 A, enabling protection to be coordinated with motor starting currents and the characteristics of the protected circuit.
With a 160 A rated current, three-pole construction, fixed installation and front terminals, the T4L 250 MA 160-2240 is designed for straightforward integration into motor control centres, switchboards and industrial distribution panels. The T4L performance level provides an ultimate short-circuit breaking capacity of 120 kA at 380–415 V AC, delivering robust fault protection in demanding motor applications.
Magnetic-only moulded case circuit breakers such as the ABB SACE Tmax T4L MA are designed for motor circuits where overload protection is handled by a separate protective device. The MA release responds rapidly to high short-circuit currents while its adjustable threshold allows the breaker to accommodate the temporary inrush currents associated with motor starting.
The 960–2,240 A magnetic adjustment range provides flexibility when coordinating the 1SDA054311R1 with motor starters, contactors and overload protection devices. Combined with the T4L's 120 kA breaking capacity at 380–415 V AC, this makes the breaker well suited to demanding industrial motor control centres and machinery installations where high prospective fault currents may be present.
| Series | SACE Tmax T4 |
|---|---|
| ABB order code | 1SDA054311R1 |
| Product group | 310511-T-Max T4 - T8 |
| Product type | Moulded case circuit breaker (MCCB) for motor protection |
| Frame | T4 250 |
| Performance level | L |
| Rated current (In) | 160 A |
| Rated uninterrupted current (Iu) | 250 A |
| Number of poles | 3P |
| Trip unit | MA magnetic-only release |
| Instantaneous magnetic trip range (I3) | 960–2,240 A |
| Rated operational voltage | 690 V AC / 750 V DC |
| Rated insulation voltage (Ui) | 1,000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Ultimate short-circuit breaking capacity (Icu) at 220–230 V AC | 200 kA |
| Ultimate short-circuit breaking capacity (Icu) at 380–415 V AC | 120 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500 V AC | 85 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 70 kA |
| Mounting type | Fixed |
| Terminal type | Front terminals |
| Electrical durability | 8,000 operating cycles |
| Mechanical durability | 20,000 operating cycles |
| Power loss | 7.4 W per pole at rated operating conditions |
| Dimensions (H × W × D) | 205 × 105 × 103.5 mm |
| Net weight | approx. 2.35 kg |
| EAN | 8015644554088 |
The ABB 1SDA054311R1 is a three-pole moulded case circuit breaker for motor protection, providing adjustable magnetic short-circuit protection for industrial motor circuits.
The circuit breaker has a rated current of 160 A and is built on the ABB SACE Tmax T4 250 A frame.
The MA release provides an adjustable instantaneous magnetic trip range of 960–2,240 A, allowing short-circuit protection to be coordinated with motor starting characteristics.
No. The MA trip unit is magnetic-only and provides short-circuit protection. Motor overload protection should therefore be provided by a suitable separate overload relay or motor protection device.
The T4L circuit breaker provides an ultimate short-circuit breaking capacity of 120 kA at 380–415 V AC, making it suitable for demanding industrial motor circuits with high prospective fault currents.
ABB SACE Tmax motor-protection circuit breakers provide dependable short-circuit protection for industrial motor circuits, combining adjustable magnetic releases, compact construction and high breaking capacity for motor control centres, machinery and demanding automation applications.