1SCA128212R1001 ABB 160 A 3-Pole BS Switch Fuse with Integrated Back Nuts

1SCA128212R1001 ABB 160 A 3-Pole BS Switch Fuse with Integrated Back Nuts

ABB OS160GB03-42 is a 160 A 3-pole British Standard switch fuse for A2–A4 fuse links with integrated terminal nuts and a left-side front-operated mechanism, supplied without a handle and shaft.

SKU: 1SCA128212R1001Alt SKU: OS160GB03-42MPN: 1SCA128212R1001
Price
List Price £317.54 ex VAT
Your Price (ex VAT) Save 35%
£206.40 35% OFF
You save £111.14 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £206.40
Trade pricing is personalised to your account

Manufacturer Lead Time

£206.40

Why Choose the ABB OS160GB03-42 160 A 3-Pole BS Switch Fuse?

The ABB OS160GB03-42 is a robust 160 A 3-pole switch fuse designed for switching, isolation and fuse-based protection in low-voltage electrical distribution systems. Part of the ABB OS160 Gamma range, it combines dependable manual isolation with British Standard fuse protection for industrial and commercial applications.

The OS160GB03-42 uses the British Standard fuse system and accommodates A2–A4 fuse links with a maximum fuse diameter of 32 mm. The -42 configuration incorporates integrated nuts on the terminals, together with a terminal bolt set, to support straightforward installation within electrical panels and switchboards.

Rated at 160 A with a 3-pole configuration, the OS160GB03-42 is front operated with its 03 operating mechanism located on the left side. This version is supplied without a handle and operating shaft, allowing compatible ABB operating accessories to be selected separately to suit the enclosure and installation arrangement.

Key Advantages

  • Heavy-duty 160 A 3-pole switch fuse for low-voltage distribution.
  • Designed for British Standard A2–A4 fuse links.
  • Integrated terminal nuts simplify electrical installation.
  • Combines switching, isolation and fuse-based circuit protection.
  • Front-operated design with operating mechanism on the left side.
  • Robust base-mounted construction for switchboard integration.
  • Supplied without handle and shaft for flexible operating-accessory selection.

Key Features

  • ABB OS160 Gamma switch fuse.
  • 160 A rated current.
  • 3-pole configuration.
  • British Standard fuse system.
  • Suitable for A2, A3 and A4 fuse links.
  • Maximum fuse diameter of 32 mm.
  • -42 integrated terminal nuts for ease of installation.
  • Front-operated switching arrangement.
  • 03 operating mechanism positioned on the left side.
  • Base-mounted construction.
  • Lug terminals for main-circuit connections.
  • Handle and operating shaft are not included.

Reliable 160 A Switching, Isolation and Fuse Protection

The ABB OS160GB03-42 combines manual circuit switching and isolation with the protection provided by appropriately selected British Standard A2–A4 fuse links. Its 160 A, 3-pole configuration enables all three phases of a three-phase circuit to be switched together while the installed fuses provide overcurrent and short-circuit protection according to their selected characteristics.

The -42 integrated-nut terminal arrangement is designed to simplify connection during switchboard assembly, while the front-operated mechanism is positioned on the left side of the switch. As the handle and shaft are not included, suitable ABB operating accessories can be selected to match the enclosure depth and required external operating arrangement.

Typical Applications

  • Industrial three-phase power distribution systems.
  • Main and sub-distribution switchboards.
  • Three-phase feeder switching and isolation.
  • Industrial machinery and equipment supplies.
  • Electrical control panels and distribution assemblies.
  • Installations requiring British Standard A2–A4 fuse protection.

Technical Specifications

Tick the specs you need, then view products that match.

Mounting Type Base / panel
Series OS160 Gamma
ABB order code 1SCA128212R1001
Product type Switch fuse / fuse switch disconnector
ABB product group 311021-OS Fuse Switches
Rated current 160 A
Number of poles 3
Fuse system British Standard
Fuse size A2–A4
Maximum fuse diameter 32 mm
Rated voltage 690 V
Rated operational power AC-23 at 400 V 132 kW
Rated short-time withstand current 5 kA
Rated conditional short-circuit current 80 kA
Power loss 12 W per pole at rated operating conditions
Operation Front operated
Operating mechanism 03, left side
Mounting type Base mounting
Terminal type Lug terminals with integrated nuts
Handle Not included
Operating shaft Not included
Dimensions (H × W × D) 115 × 140 × 192 mm
Standard IEC 60947-3
EAN 6417019580319

Frequently Asked Questions

What is the ABB OS160GB03-42 used for?

The ABB OS160GB03-42 is a 160 A 3-pole switch fuse designed for switching, isolation and fuse-based protection in three-phase low-voltage electrical distribution systems.

What fuse links does the ABB OS160GB03-42 use?

The OS160GB03-42 uses the British Standard fuse system and is designed for A2–A4 fuse links with a maximum fuse diameter of 32 mm.

What does -42 mean on the ABB OS160GB03-42?

The -42 configuration identifies a version with integrated nuts on the terminals, designed to simplify electrical installation and supplied with the associated terminal bolt set.

Where is the operating mechanism positioned on the ABB OS160GB03-42?

The OS160GB03-42 is front operated and uses the 03 operating mechanism positioned on the left side of the switch.

Does the ABB OS160GB03-42 include a handle and shaft?

No. The OS160GB03-42 is supplied without a handle and operating shaft, allowing compatible ABB operating accessories to be selected separately for the installation.

Trusted ABB Fuse Switching Technology

ABB OS switch fuses combine dependable circuit switching and isolation with British Standard fuse protection, while integrated-nut versions provide a practical connection arrangement for professional industrial switchboard installations.